Installation & Commissioning Guide

Control Features

The TP75 Series of programmable room thermostats incorporate two
special  features  that  can  be  enabled  at  the  time  of  installation  -
Optimum Start Control and Chrono-proportional Control

Optimum Start Control (OSC)

With  this  enabled  the  event  1  control  temperature,  (which  would
normally  be  an  increase  from  an  overnight  set-back  temperature),
may be programmed to be achieved by a desired time. The heating
plant will be switched on earlier than the programmed time by a period
related  to  the  start-up  curve  selected  and  the  space  temperature
sensed at the beginning of the selected start-up period. The diagram
below indicates the switch on periods for the available start-up curves.
If OSC is disabled then the unit will operate as a conventional room
thermostat, switching on the heating plant at the event 1 time with the
event 1 temperature being achieved in a time related to the prevailing
conditions.

Battery Compartment Flap lowered

This product complies with the following EC Directives:

Electro-Magnetic Compatibility Directive.
(EMC)

(89\336\EEC), (92\31\EEC)

Low Voltage Directive.
(LVD)

(73\23\EEC), (93\68\EEC)

Chrono-proportional Control

Traditional ON/OFF room thermostats control room temperature by
switching the circulating pump, and usually the boiler, on and off.
Because  of  the  thermal  inertia  of  the  heating  equipment  and  the
relatively large switching differentiials of on/off devices large space
temperature variations often occur, resulting in poor comfort conditions.
Chrono-proportional Control as implemented in the TP75 overcomes
the  problem  by  ensuring  that  the  boiler  fires  regularly  for  periods
calculated to maintain radiator temperature without overheating and
to prevent the radiator temperature falling  to a level which can allow
down draughts from cold surfaces, e.g. windows, to cause discomfort.
The control logic works on a proportional band of 2°C which assumes
that  the  boiler  will  operate  at  full  load  when  the  sensed  space
temperature is 2°C or more lower than the programmed set point.
The following graph shows the relative on/off periods per cycle against
variances in deviation from the set point.

OFF Time

S

y

stem Load

 

0%  25% 50% 75%  100%

0%

25%

50%

75%

100%

  100% 75% 50% 25%  0%

Set Temp

-0·5°C

-1·0°C

-1·5°C

-2·0°C

P

roporti

onal B

a

nd

ON Time

 

OFF 

TIME 

20 15 10  5  0 

min. 

 

ON 

TIME 

0  5  10 15 20 

min.

 

OFF 

TIME 

10 7·5 5 2·5 0 

min. 

 ON 

TIME 

2·5 

7·5 

10 

min.

3 Cycles / hour
HC75--3

6 Cycles / hour
HC75-C3

Lo

ad

 cu

rve

Ï

Desired Event 1
temperature.

Selecting 0
effectively
disables the
OSC function.

 Available 

Start-up 

Periods

With a -2°C deviation and the 30 min. curve selected the
heating plant will switch on 15 min. before the Event 1 time.

De

gr

e

e

s

 be

lo

w

 t

h

e

 de

si

re

d

te

m

p

e

rat

ur

e a

t t

h

e b

e

g

inn

in

g

o

f t

h

e O

p

ti

m

u

m

 St

ar

P

e

ri

od

 

120 

90 

60 

30 

    Event 1

 

 min. 

 min. 

 min. 

 min.       time (0)

-1°C

-2°C

-3°C

-4°C

Electronic Programmable Room Thermostats
TP75  with  integral  sensor

TP75A  with  remote  sensor

TP75B  with  remote  teleswitch

TP75AB  with  remote  sensor  &  teleswitch

Specification

Control temp. range

: 5°C to 30°C (41°F to 85°F)

Power  Supply

: 2 x AA size high quality

alkaline batteries

Switching  Action

: 1 x SPDT, type 1B

Switch  Rating

: 10 - 250Vac, 50/60 Hz, 2(1)A

Temperature  Accuracy

: ± 0.5°C

Time Keeping Accuracy

: ± 1 minute/month

Low  Battery  Warning

: 15 days duration

Memory Retention with Batteries Removed : one minute

Enclosure Rating

: IP30

Maximum Ambient Temp

: 45°C

Designed to Standard

: BS EN60730-2-9

Overall Dimensions

Unit

: Width: 135mm

Height:

88mm

Depth:

32mm

                   Remote Sensor

: Width:

61mm

Height:

45mm

Depth:

22mm

Pollution Situation

: Degree 2

Software  Classification

: Class A

Rated Impulse Voltage

: 2.5 KV

Ball Pressure Test

: 75°C