Montageanleitung / Installation Guide 

 

Verteilersysteme / distribution units - Multifamily

4 | © Danfoss | Produced by Danfoss Redan A/S | 2017.05

VI.LZ.P1.5B

2.

 

ANSCHLUSS, SICHERHEIT, HANDHABUNG / CONNECTION, SAFETY, HANDLING

Instructions

Please read these instructions carefully before installing and com-
missioning this unit. The manufacturer accepts no liability for loss or 
damage resulting from failure to comply with these instructions for use. 
Read and follow these instructions carefully to prevent the risk of physi-
cal injury and/or damage to property. Exceeding the recommended 
operating parameters appreciably increases the risk of personal injury 
and/or damage to property.
Installation, commissioning and maintenance must be carried out 
by qualified and authorised personnel (both plumbing and electrical 
work).
Once the system has been installed and is operating, there is normally
no need to alter the settings or other functions. The distribution system 
unit is very reliable and easy to operate.

Heat source

The distribution system is primarily designed for connection to district 
heating. Alternative energy sources can be used if the operating condi-
tions are equivalent to district heating at all times.

Application

The Danfoss stainless steel distribution systems for multi family houses 
are prefabricated distribution units with incoorporated metering 
station. The distribution systems serve to distribute floor heating and 
the metering stations serve to measure the heating consumption, 
typically for each single apartment in an apartment block.

Choise of materials

Only use materials that comply with local regulations.

Corrosion

The maximum chlorine content of the medium must not be higher 
than 300 mg/l. The risk of corrosion increases considerably if the rec-
ommended chlorine content is exceeded.

Storage

Before installation, the unit(s) must be stored in a dry, heated (i.e. 
frostfree) room.
(Relative humidity max. 80% and storage temp. 5–70°C).
The units must not be stacked higher than the limit at the factory. Units 
supplied in cardboard packaging must be lifted using the handles 
incorporated in the packaging. Units must be placed on pallets for 
transport/moving across large distances.
As far as possible, do not lift the unit by the pipes.
Retighten ALL pipe connections after transport/moving. 

Disposal

Dispose of the packaging in accordance with the local regulations for 
disposal of used packaging materials. The unit is made of materials 
that cannot be disposed of together with household waste.
Close all energy sources and disconnect all connection pipes. Discon-
nect and dismantle the product for disposal in accordance with the ap-
plicable local regulations for the disposal of the individual components.

Connection

It must be possible to cut off all energy sources to the system – includ-
ing electrical connections – at all times. 

Potential equalization/grounding

Potential equalization is an electrical equalizer connection to secure
against user contact with dangerous voltage, which may occur for
example between two piping systems. Potential equalization re-
duces  corrosion in heat exchangers, water heaters, district heating
units and plumbing installations.

Potential bonding should be carried out according to 60364-4-41:
2007 and IEC 60364-5-54: 2011.
Bonding poing is marked on the mounting plate below right corner
with an earthing symbol and there will be a hole in the station 
mounting  plate and a label with earth symbol.

Warning! Hot surfaces

Parts of the unit may be very hot and can cause burn injuries.
Be very careful when you are in the immediate vicinity of the unit

Emergencies

In the event of fire, leaks or other hazards, immediately shut off all 
sources of energy to the unit, if possible, and call for appropriate 
assistance.
If the domestic hot water is discoloured or malodorous, shut off 
all ball valves on the unit notify all users and call for professional 
assistance without delay.

Warning about damage during transport

On reception of the unit, and before installing it, check for any evi-
dence of damage during transport.
The unit must be handled and moved with the greatest care and 
attention.

NB! - Tightening of connections

Before filling the unit with water, ALL pipe connections MUST be 
retightened, as vibrations during transport may have caused leaks. 
Once the unit has been filled and the system is hot, ALL pipe connec-
tions MUST be retightened once more. 

DO NOT OVERTIGHTEN THE

PIPE CONNECTIONS

.

Handling

We recommend that you wear suitable safety footwear while 
handling and installing the unit.

 

ENGLISH - GB

NOTE:

Interventions/rework on our components results in loss of

warranty.

Summary of Contents for SGM

Page 1: ...eilersysteme mitMessstation distributionsystems withmeteringunit Danfoss vorgefertigte EdelstahlVerteilersysteme f r Fussbodenheizung Danfoss prefabricated solutions for floor heating Edelstahl Vertei...

Page 2: ...s 13 8 0 Montage Mounting 15 9 0 Montage im Einbauschrank Mounting in recess box 16 10 0 Einstellung und Inbetriebnahme Adjustment and commissioning 18 11 0 Regeltechnik Fussbodenheizung Control Floor...

Page 3: ...ehobenwerden ZumTrans portieren Bef rdern ber gro e Entfernungen m ssen die Verteil ersysteme auf Paletten platziert werden HebenSiedieVerteilersystemenachM glichkeitnichtandenRohren an da dadurch Lec...

Page 4: ...by the pipes Retighten ALL pipe connections after transport moving Disposal Dispose of the packaging in accordance with the local regulations for disposal of used packaging materials The unit is made...

Page 5: ...Aus diesem Grund ist es wichtig dass Sie die berwurfmutternNICHTZUFEST ANZIEHEN Zu fest angezogene berwurfmuttern k nnen zu Leckagen f hren Leckagen die durch zufestangezogene berwurfmutternoderdurch...

Page 6: ...150 mm und H910 B850 T150 mm Die Breite 690 mm passt zu Verteilersystemen mit bis zu 8 Heizkreisen Die Breite 850 mm passt zu Verteilersystemen mit bis zu 12 Heizkreisen Montagef sse f r die Unterputz...

Page 7: ...ung Type SGCM Distribution systems with AB PM a combined automatic balancing valve with flow limiter and integrated control valve SS FH manifold safety thermostat STW 55 C TWA air vents and strainer i...

Page 8: ...und Schmutzf nger imVorlauf und R cklauf Mit elektronisch geregeltem Mischkreis Hocheffizienzpumpe und Einzelraumregelung Type E SGTZCM Distribution systems with AB PM a combined automatic balancing v...

Page 9: ...s 145H0568 Typ SGTZM mit 9 Heizkreisen mit thermostatischem Mischkreis 145H0569 Typ SGTZM mit 10 Heizkreisen mit thermostatischem Mischkreis 145H0570 Typ SGTZM mit 11 Heizkreisen mit thermostatischem...

Page 10: ...g circuits with thermostatic mixing loop 145H0568 Type SGTZM with 9 heating circuits with thermostatic mixing loop 145H0569 Type SGTZM with 10 heating circuits with thermostatic mixing loop 145H0570 T...

Page 11: ...u Hochtemperaturkreis High temperature connection 52 Thermischer Stellantrieb TWA Z Thermal actuator TWA Z 54 Sicherheitsthermostat Safety thermostat 57 Netzstecker Plug 58 Anschlussverteiler mit Durc...

Page 12: ...IZZE ANSCHLUSS DIMENSIONAL SKETCH CONNECTION FH Supply FH Vorlauf FH Return FH R cklauf DHSupply FW Vorlauf DH Return FW R cklauf MASSSKIZZE DIMENSIONAL SKETCH 754 593 129 11 07 2016 DHSupply FW Vorla...

Page 13: ...hahn Ball valve 10 Umw lzpumpe WILO YONOS 15 6 130 230V Circulation pump Wilo Yonos 15 6 130 230V 17 Entl ftung Air vent 19 Entleerungshahn und manueller Entl fter Tapping point with manual air vent 2...

Page 14: ...vent 19 Entleerungshahn und manueller Entl fter Tapping point with manual Air vent 24 Pa st ck f r W rmemengenz hler Fitting piece for heat meter 25 Elektronische Regler ECL Comfort Electronic control...

Page 15: ...k H910 B690 T150 mm 9 12 Kreise passen in den 145H4281 Unterputzschrank H910 B850 T150 mm The distributors fits on the back plate of the recess boxes and also be mounted on the wall The systems can be...

Page 16: ...ce with the labelling on the unit and or in accordance with the instruc tions in this manual Schritt Unterputzschrank wird eingemauert oder in Leichtbauwand eingebaut Step Recess box with rotatable mo...

Page 17: ...ohranschlu ist Step Installer connects the household pipes for DH supply and DH return and insulates the pipes When installing please ensure that there is enough space for pipe connection Schritt Befe...

Page 18: ...UNG UND INBETRIEBNAHME ADJUSTMENT AND COMMISSIONING Verteiler mit Anschl ssen mit Durchflussmesser Durchflussmenge l ss sich durch Drehen des Durchflussmessers einstellen Siehe bitte beigelegte Abbild...

Page 19: ...Montageanleitung Installation Guide Verteilersysteme distribution units Multifamily Danfoss Produced by Danfoss Redan A S 2017 05 19 VI LZ P1 5B von oben...

Page 20: ...n abbauen Pos A Der eine Temperaturf hler in die F hlertasche einstecken Der berwurfmutter des F hlers festschrauben Der andere F hler imW rmemengenz hlergeh use auf FW R cklauf einbauen und festschra...

Page 21: ...C power supply The power supply connection must be carried out in accordance with the applicable regulations and instructions The unit must be wired and connected to an external main switchso that it...

Page 22: ...rlaubsbetrieb usw verf gbar Siehe bitte beigelegte Instruktionsanleitung f r weitere Informa tionen Generell Ontheprimarysidetheunitsaresuppliedwithacombinedautomatic balancing valve AB PM which acts...

Page 23: ...eier MNG Oventrop valves with M30 1 5 connection generally as per attached drawing Other valves must be verified individually to ensure correct valve closing measurement and valve top geometry TWA D F...

Page 24: ...estattet Siehe bitte beigelegte Bedienungsanleitungen ber Danfoss ECL 310 und Wilo Yonos Para Pumpe Mixing circuit Distribution systems SGTCM SGTZCM and E SGTZCM include an integrated mixing circuit S...

Page 25: ...ksichtigung des Komfortanspr che so nie drig wie berhaupt m glich ist ca 30 35 Die Vorlauftemperatur soll nie 45 C berschreiten IMMER die In struktionen des Fussbodenlieferanten beachten Thermostatic...

Page 26: ...g Installation Guide Verteilersysteme distribution units Multifamily 26 Danfoss Produced by Danfoss Redan A S 2017 05 VI LZ P1 5B Schaltdiagramm Wiring diagram 11 REGELTECHNIK FUSSBODENHEIZUNG CONTROL...

Page 27: ...pplication by means of an ECL Application Key Plug Play The Application Key contains information about application languages and factory settings VariousapplicationscanbeloadedbymeansoftheECLApplicati...

Page 28: ...as Ventil geschlossen Liegt keine Kraft vom Stellantrieb an ffnet die ventilinterne Feder das Ventil 1 Installation Guide TWA Z Gen 2011 Heating Solutions VI SB I6 02 SMT SI TWA Z AB QM 24 V Class III...

Page 29: ...pe in Abh ngigkeit vom Heizbedarf des Geb udes auf die niedrigstm gliche Position unter Ber cksichti gung von Aspekten wie K hlung und Leistungsaufnahme Entl ften Entl ften Sie das System mit den Entl...

Page 30: ...ernen Energieversorgung einschalten und von Leckagen berwachen Anlage entl ften Wenn n tig die Anlage neu einstellen Sicherstellen dass alle Sicherheitseinrichtungen des Ger tes und der Anlage wieder...

Page 31: ...Montageanleitung Installation Guide Verteilersysteme distribution units Multifamily Danfoss Produced by Danfoss Redan A S 2017 05 31 VI LZ P1 5B 14 EU GUTACHTEN EU DECLARATION OF CONFORMITY...

Page 32: ...hf hren Beim Einbau sind alle rtlichen Standards und Vorschriften einzuhalten Installation und erste Inbetriebnahme d rfen nur von qualifizierten und autorisierten Personen durchgef hrt werden Die Sta...

Page 33: ...technical regulations and the applicable legislation in every respect Installation and commissioning must only be performed by trained authorised personnel The unit is checked in the factory for leak...

Page 34: ...Montageanleitung Installation Guide Verteilersysteme distribution units Multifamily 34 Danfoss Produced by Danfoss Redan A S 2017 05 VI LZ P1 5B...

Page 35: ...Montageanleitung Installation Guide Verteilersysteme distribution units Multifamily Danfoss Produced by Danfoss Redan A S 2017 05 35 VI LZ P1 5B...

Page 36: ...orherige Bekanntmachung im Rahmen des Angemessenen und Zumutbaren nderungen an ihren Produkten auch an bereits in Auftrag genommenen vorzunehmen Alle in dieser Publikation enthaltenen Warenzeichen sin...

Reviews: