PVED-CLS Spool calibration
Navigate to the Spool calibration section via System Navigator > Auto-Calibration > Spool Calibration
Calibrate closed loop spool dead-band with the following steps.
1. Select Go to calibration mode
2. Turn the steering wheel so that Service Mode State changes to Spool Calibration Getting Armed
3. Stop turning the steering wheel and secure the wheels in a central position so that it changes to
Spool Calibration Armed, then press Start Calibration
Wheels will turn back and forth (or machine will articulate).
Application Guide
PVED-CLS startup guide
Parameter setting