Parameter Configuration

After PTU 025 is installed, power up the frequency converter.
The LCP shows 

alarm A80, Drive initialized

, which indicates that

the frequency converter detected the new device. Press [Reset]
to reset the alarm.

Illustration 1.8 Alarm A80, Drive Initialized

Use the LCP or MCT 10 Set-up Software to configure PTU 025.
The PTU 025 option can be configured for the following
purposes:

Monitoring of the pressure transmitter signals.

Showing the readouts on the LCP or transmitting
them via the fieldbus.

Integration of the pressure monitoring into a system
solution.

PID closed-loop control based on airflow or pressure
levels.

Signals from all PTU 025 sensors are active all the time and
the frequency converter can show the values on the LCP
continuously. Use parameters in 

parameter group 31-2*

Readouts

 to monitor filters, airflow, and pressure levels on the

LCP or configure warnings or alarms. Values in 

parameter

group 31-2* Readouts

 are also available via the fieldbus.

MCT 10 Set-up Software and the frequency converter check
whether the entered pressure values are within the operating
ranges of sensors. The LCP shows a warning if the entered
pressure value is outside the operating range.

Use 

parameter 31-30 Press Sens Cmp State

 in the smart logic

control to achieve application-specific functionality. Use
parameters in 

parameter group 13-9* User-defined Alerts and

Readouts

 to configure application-specific messages, warnings,

and alarms. For more information, see the 

programming guide

.

31-** Pressure Sensor Option

Parameters related to the PTU 025 option.

31-2* Configuration

Each pressure-related status has its own below-level and
above-level trigger thresholds. The thresholds can be activated
individually. When the actual pressure level exceeds the
threshold level, the frequency converter waits for the value in 

parameter 31-23 On Delay Time

, and then performs a status

change of a status. When the actual pressure goes below the
threshold level, the value in 

parameter 31-24 Reset Delay Time

defines when the status is reset. The value in 

parameter 31-25 Pressure filter time constant

 adjusts the

dynamic of the reaction to the actual pressure input, to ensure
reliable and stable status generation.

31-20  Pressure/Speed Curve

Select the type of the pressure/speed curve.

Each pressure sensor can have a different setting.

For options 

[1] Linear

 and 

[2] Square root

, the pressure threshold

at 0 speed equals 10% of the value entered in

parameter 31-21 Below level threshold

 or 

parameter 31-22 Above

level threshold

.See 

Illustration 1.9

.

Illustration 1.9 Pressure/Speed Dependency

Option:

Function:

[0] 

*

None

The pressure threshold is

constant and does not

depend on speed.

[1]

Linear

The pressure threshold is

proportional to the speed.

[2]

Square root

The pressure threshold

depends on the speed.

The dependency is

quadratic.

31-21  Below level threshold

Range:

Function:

#

*

  [ -2500 - 2500 Pa]

Enter the below-level threshold.

Installation Instructions

Pressure Transmitter Unit PTU 025
VLT

®

 HVAC Drive FC 102

MI08A102

Danfoss A/S © 12/2017 All rights reserved.

7

Summary of Contents for PTU 025

Page 1: ...r connection 6 Tube relief plate 3 M25 star washer 7 Interface cable for the C option port 4 M25 gasket 8 Cable binders Table 1 1 Illustration 1 1 Pressure Transmitter Unit PTU 025 and Items Supplied...

Page 2: ...t in death or serious injury Stop the motor Disconnect AC mains and remote DC link power supplies including battery back ups UPS and DC link connections to other frequency converters Disconnect or loc...

Page 3: ...ween the PTU 025 unit and the enclosure This is necessary for the IP55 66 rating 2 Inside the enclosure place the star washer the ground connection and the nut See Illustration 1 3 3 Put the ground wi...

Page 4: ...1 5 2 Wire the outputs for the related signals and statuses 3 Mount the front cover of the frequency converter 4 Power up the frequency converter Ensure that the frequency converter identifies the PT...

Page 5: ...l and relay outputs Perform the configuration in parameter group 5 Main Menu Digital In Out and parameter group 6 Main Menu Analog In Out See the wiring diagram in Illustration 1 6 Illustration 1 6 Wi...

Page 6: ...stration 1 7 Illustration 1 7 Mounting Pressure Tubes NOTICE Put a tube connection on all pressure transmitter taps to minimize the amount of dirt entering the unit The minimum tube length is 80 mm 3...

Page 7: ...fic messages warnings and alarms For more information see the programming guide 31 Pressure Sensor Option Parameters related to the PTU 025 option 31 2 Configuration Each pressure related status has i...

Page 8: ...Sensor 3 Range Function 0 Pa 1000 1000 Pa Shows the readout of pressure sensor 3 31 29 Pressure Sensor 4 Range Function 0 Pa 2500 2500 Pa Shows the readout of pressure sensor 4 31 30 Press Sens Cmp St...

Page 9: ...ors and their Functions Integrating pressure signals into a system solution The pressure values can be read as analog values on the analog output or as pulses on digital outputs Use parameter 5 30 Ter...

Page 10: ...tice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this mat...

Reviews: