31-22  Above level threshold

Range:

Function:

#

*

  [ -2500 - 2500 Pa]

Enter the above-level threshold.

31-23  On Delay Time

Range:

Function:

60 s

*

  [0 - 3600 s]

Enter the on delay time.

31-24  Reset Delay Time

Range:

Function:

9999 s

*

  [0 - 9999 s]

Enter the reset delay time.

31-25  Pressure filter time constant

Range:

Function:

1 s

*

  [0.01 - 60 s] Enter the pressure filter time constant. A

longer value make the pressure signal more

stable but less dynamic. A shorter value

allows to eliminate signal spikes and keep

control more dynamic.

31-2* Readouts

Parameters in this group contain the actual pressure levels and
the status information. The LCP can be configured to show the
values of these parameters in different display lines. The
toggle function allows to show multiple pressure signals in the
same LCP line. The number is followed by the hash sign (#).
See 

Illustration 1.9

.

Use 

parameter 0-20 Display Line 1.1 Small

 to

parameter 0-24 Display Line 3 Large

 to configure the LCP to

show different pressure values.

Illustration 1.9 Pressure Sensor Data on the LCP

31-26  Pressure Sensor 1

Range:

Function:

0 Pa

*

  [-500 - 500 Pa]

Shows the readout of pressure sensor 1.

31-27  Pressure Sensor 2

Range:

Function:

0 Pa

*

  [-500 - 500 Pa]

Shows the readout of pressure sensor 2.

31-28  Pressure Sensor 3

Range:

Function:

0 Pa

*

  [-1000 - 1000 Pa] Shows the readout of pressure sensor

3.

31-29  Pressure Sensor 4

Range:

Function:

0 Pa

*

  [-2500 - 2500 Pa] Shows the readout of pressure sensor

4.

31-30  Press Sens Cmp State

Range:

Function:

0

*

  [0 -

255]

Shows the pressure sensor state. The state is an 8-

digit binary value, where 1 indicates an active status

and 0 indicates an inactive status. Reading from

right to left, the first 4 digits indicate the alarms for

the below-level threshold, and the last 4 digits the

alarms for the above-level threshold. For instance,

counting from right to left, sensor 1 for the below-

level threshold is at position 1, and sensor 1 for the

above-level threshold is at position 5. See

Illustration 1.9

.

NOTICE

When using this parameter in the smart logic
controller, the output status signal for the
below-level threshold and for the above-level
threshold is the same for a specific sensor.
For example, in the following cases the
output status signal is the same:

The below-level threshold for sensor
1 is active.

The above-level threshold for sensor
1 is active.

31-31  Press Sens toggle

Range:

Function:

   [0 - 4] Shows the pressure values on all sensors. The

readout switches between sensors in a loop, going

from sensor 1 to sensor 4. The sensor number is

followed by a hash sign, see 

Illustration 1.9

.

Installation Instructions

Pressure Transmitter Unit PTU 025
VLT

®

 HVAC Drive FC 102

8

Danfoss A/S © 12/2017 All rights reserved.

MI08A102

Summary of Contents for PTU 025

Page 1: ...r connection 6 Tube relief plate 3 M25 star washer 7 Interface cable for the C option port 4 M25 gasket 8 Cable binders Table 1 1 Illustration 1 1 Pressure Transmitter Unit PTU 025 and Items Supplied...

Page 2: ...t in death or serious injury Stop the motor Disconnect AC mains and remote DC link power supplies including battery back ups UPS and DC link connections to other frequency converters Disconnect or loc...

Page 3: ...ween the PTU 025 unit and the enclosure This is necessary for the IP55 66 rating 2 Inside the enclosure place the star washer the ground connection and the nut See Illustration 1 3 3 Put the ground wi...

Page 4: ...1 5 2 Wire the outputs for the related signals and statuses 3 Mount the front cover of the frequency converter 4 Power up the frequency converter Ensure that the frequency converter identifies the PT...

Page 5: ...l and relay outputs Perform the configuration in parameter group 5 Main Menu Digital In Out and parameter group 6 Main Menu Analog In Out See the wiring diagram in Illustration 1 6 Illustration 1 6 Wi...

Page 6: ...stration 1 7 Illustration 1 7 Mounting Pressure Tubes NOTICE Put a tube connection on all pressure transmitter taps to minimize the amount of dirt entering the unit The minimum tube length is 80 mm 3...

Page 7: ...fic messages warnings and alarms For more information see the programming guide 31 Pressure Sensor Option Parameters related to the PTU 025 option 31 2 Configuration Each pressure related status has i...

Page 8: ...Sensor 3 Range Function 0 Pa 1000 1000 Pa Shows the readout of pressure sensor 3 31 29 Pressure Sensor 4 Range Function 0 Pa 2500 2500 Pa Shows the readout of pressure sensor 4 31 30 Press Sens Cmp St...

Page 9: ...ors and their Functions Integrating pressure signals into a system solution The pressure values can be read as analog values on the analog output or as pulses on digital outputs Use parameter 5 30 Ter...

Page 10: ...tice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this mat...

Reviews: