background image

4

FRCC.EI.003.A1.02   © Danfoss Commercial Compressors 03/08

Instructions

to  compressor  terminals  T1,  T2,  T3  to  avoid 
reverse rotation.

  •   Use ø 4.8 mm (3/16”) screws and ¼” ring ter

-

minals for the power connection. Fasten with 
3 Nm torque.

  •   The thermostat connection (if present) is a ¼” 

AMP-AWE spade connector.

  •   The compressor must be connected to earth 

with the 5 mm earth terminal screw.

8 – Filling the system

  •   Keep the compressor switched off.
  •   SM 084 to 185, SY 380, SZ 084 to 185, SZ 380, SH 

090 to 180:  Fill the refrigerant in liquid phase 
into the condenser or liquid receiver. The char-
ge must be as close as possible to the nominal 
system charge to avoid low pressure operation 
and excessive superheat. Never let the pressure 
on LP side exceed the pressure on HP side with 
more than 5 bar. Such pressure difference could 
cause internal compressor damage.

  •   SY 240 & 300, SZ 240 & 300, SH 240 to 380: Fill 

the refrigerant slowly in liquid phase into the 
LP side of the system. The charge must be as 
close as possible to the nominal system charge 
to avoid low pressure operation and excessive 
superheat.  The  pressure  increase  from  0  up 
to the full system charge shall take at least 2 

minutes. When the 2 minutes time span is not 

respected,  the  pressure  on  LP  side  could  ex-
ceed the pressure on HP side with more than 
5 bar and cause internal compressor damage.

  •   Keep the refrigerant charge below the indica

-

ted charge limits if possible. Above this limit; 
protect the compressor against liquid flood-
back with a pump-down cycle or suction line 
accumulator.

  •   Never leave the filling cylinder connected to 

the circuit.

Compressor models

Refrigerant charge 

limit (kg)

SM/SZ 084, 090, 100

8.5

SM/SZ 110, 120

10

SM/SZ 115, 125

11

SM/SZ 148, 160, 161

12.5

SM/SZ 175, 185

13.5

SY/SZ 240

16

SY/SZ 380

20

SH 090

5.9

SH 105, 120, 140, 161

7.9

SH 180, 240, 300

13.5

SH 380

14.5

 

9 – Verification before commissioning

  Use  safety  devices  such  as  safety  pressure 

switch and mechanical relief valve in complian-
ce with both generally and locally applicable re-
gulations and safety standards. Ensure that they 
are operational and properly set. 

 Check that the settings of high-pressure swit-

ches and relief valves don’t exceed the maximum 

service pressure of any system component.

  •   A  low-pressure  switch  is  recommended  to 

avoid  vacuum  operation.  Minimum  setting 
for  SM/SY/SZ:  1.5  bar  (absolute).  Minimum 
setting for SH: 1.6 bar (absolute).

  •   Verify that all electrical connections are pro

-

perly  fastened  and  in  compliance  with  local 
regulations.

  •   When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-
up  and  start-up  after  prolonged  shutdown. 
Exception: Due to specific R410A behavior it 
is  not  recommended  to  energize  crankcase 
heaters  on  SH  compressors  before  initial 
startup.

10 – Start-up

  •   Never start the compressor when no refrige

-

rant is charged.

  •   All service valves must be in the open position.
  •   Balance the HP/LP pressure.
  •   Energize the compressor. It must start prompt

-

ly. If the compressor does not start, check wi-
ring conformity and voltage on terminals.

  •   Eventual  reverse  rotation  can  be  detected 

by  following  phenomena;  the  compressor 

doesn’t  build  up  pressure,  it  has  abnormally 

high sound level and abnormally low power 
consumption.  In  such  case,  shut  down  the 
compressor  immediately  and  connect  the 
phases  to  their  proper  terminals.  Most  Per-
former®  scroll  compressors  are  protected 
against reverse rotation either by an internal 
reverse rotation protection or by the external 
electronic protection module. They will shut 
off automatically. Only SH 090 to 161 and SM 
124, 147 have no reverse rotation protection. 
Prolonged reverse rotation over 6 hours will 
damage these compressors.

  •   If the internal overload protector trips out (SM/

SZ 084, 090, 100, 110, 120, 124, 147, 148, 161 
and  SH  090,  105,  120,  140,  161),  it  must  cool 
down to 60°C to reset. Depending on ambient 
temperature, this may take up to several hours.

  •   If the internal pressure relief valve is opened 

(SY/SZ  240,  300,  380  and  SH  380),  the  com-
pressor sump will be warm and the compres-
sor will trip out on the motor protector.

11 – Check with running compressor

  •   Check current draw and voltage.
  •   Check  suction  superheat  to  reduce  risk  of 

slugging.

  •   Observe  the  oil  level  in  the  sight  glass  for 

about 60 minutes to ensure proper oil return 
to the compressor.

  •   Respect the operating limits.
  •    Check all tubes for abnormal vibration. Move

-

ments in excess of 1.5 mm require corrective 
measures such as tube brackets.

  •   When  needed,  additional  refrigerant  in  liquid 

phase may be added in the low-pressure side as 
far as possible from the compressor. The com-
pressor must be operating during this process.

  •   Do not overcharge the system.
  •   Never release refrigerant to atmosphere.
  •   Before leaving the installation site, carry out 

a  general  installation  inspection  regarding 
cleanliness, noise and leak detection.

  •   Record type and amount of refrigerant charge 

as well as operating conditions as a reference 
for future inspections.

12 – Maintenance

  Internal  pressure  and  surface  temperature 

are dangerous and may cause permanent injury.
Maintenance  operators  and  installers  require 
appropriate skills and tools. Tubing temperature 
may exceed 100°C and can cause severe burns.

  Ensure  that  periodic  service  inspections  to 

ensure system reliability and as required by local 
regulations are performed.

To prevent system related compressor problems, 
following periodic maintenance is recommended:

  •    Verify that safety devices are operational and 

properly set.

  •    Ensure that the system is leak tight.
  •    Check the compressor current draw.
  •    Confirm that the system is operating in a way 

consistent  with  previous  maintenance  re-
cords and ambient conditions.

  •    Check  that  all  electrical  connections  are  still 

adequately fastened.

  •    Keep the compressor clean and verify the ab

-

sence of rust and oxidation on the compres-
sor shell, tubes and electrical connections.

13 - Warranty

Always transmit the model number and serial num-
ber with any claim filed regarding this product.
The product warranty may be void in following 
cases:

  •    Absence of nameplate.
  •    External  modifications;  in  particular,  drilling, 

welding, broken feet and shock marks.

  •    Compressor opened or returned unsealed.
  •    Rust,  water  or  leak  detection  dye  inside  the 

compressor.

  •    Use of a refrigerant or lubricant not approved 

by Danfoss.

  •    Any  deviation  from  recommended  instruc

-

tions pertaining to installation, application or 
maintenance.

  •    Use in mobile applications.
  •    Use in explosive atmospheric environment.
  •    No model number or serial number transmit

-

ted with the warranty claim.

14 – Disposal

Danfoss recommends that compressors 
and compressor oil should be recycled 
by a suitable company at its site.

Reviews: