2

FRCC.EI.003.A1.02   © Danfoss Commercial Compressors 03/08

M

DGT

HP

180 s

TH

BP

CONTROL CIRCUIT

F1

F1

KM

KM

KM

KA

KA

A1

A2

A3

KA

KA

KS

KS

KS

L1

L3

L2

Q1

F2

T1

T3

T2

LLSV

KS

cc

thM

A1

A3

A2

mpm

s

sh 090 - 105 - 120 - 140 - 161 
sm 084 - 090 - 100 - 110 - 120 - 124 - 147 - 148 - 161 
sz 084 - 090 - 100 - 110 - 120 - 148 - 161

sm 115 - 125 - 160 - 175 - 185 
sz 115 - 125 - 160 - 175 - 185

sh 240 - 300 - 380 
sy 240 - 300 - 380 
sz 240 - 300 - 380

These  Performer®  compressors 
are protected against overheating 
and  overloading  by  an  internal 
safety  motor  protector.  However, 
an external manual reset overload 
protector  is  recommended  for 
protecting the circuit against over-
current. 

These  Performer®  compressors 
are provided with a bimetallic sin-
gle  pole  single  throw  thermostat 
which is located in the motor win-
dings.  Because  the  thermostat  is 
an automatic reset device, it must 
be wired in a lockout safety circuit 
with a manual reset to restart the 
unit.  For  over-current  protection, 
an external manual reset overload 
protector must be used. 
The  “must  trip”  value  of  these 
overload relays must be set in ac-
cordance  with  power  line  sizing 
and design and shall never exceed 
the “A max.” value stamped on the 
nameplate. 

These Performer® compressors

 

motors are protected by an ex-
ternal module protecting against 
phase loss/reversal, over heating 
and high current draw. 