background image

FRCC.EI.003.A1.02   © Danfoss Commercial Compressors 03/08

3

A1

A3

A2

MPM

12 14

11

N

2

1

L1

S

sh 180

This Performer® compressor motor 
is protected by an external module 
protecting against overheating and 
high current draw.

Control circuit ..........................................................CC
Control device ..........................................................TH
Optional short cycle timer (3 min)  .................180 s
Control relay ............................................................KA
Liquid Line Solenoid valve ................................ LLSV
Compressor contactor ..........................................KM

Safety lock out relay ................................................KS
Pump-down control & L.P. switch ....................... BP
H.P. safety switch ....................................................HP
Fused disconnect ....................................................Q1
Fuses ...........................................................................F1
External overload protection ................................F2

Compressor motor ...................................................M
Motor safety thermostat .................................... thM
Discharge gas thermostat .................................DGT
Motor Protection Module ................................ MPM
Thermistor chain........................................................S

Legend:

All Wiring diagrams are with pump-down cycle

Instructions

1 – Introduction

These  instructions  pertain  to  the  Performer® 
SM, SY, SZ & SH scroll compressors used for air-
conditioning  systems.  They  provide  necessary 
information regarding safety and proper usage 
of this product.

2 – Handling and storage

  •   Handle  the  compressor  with  care.  Use  the 

dedicated handles in the packaging. Use the 
compressor  lifting  lug  and  use  appropriate 
and safe lifting equipment.

  •   Store  and  transport  the  compressor  in  an 

upright position.

  •   Store the compressor between -35°C and 50°C.
  •   Don’t expose the compressor and the packa

-

ging to rain or corrosive atmosphere.

3 – Safety measures before assembly

  Never  use  the  compressor  in  a  flammable 

atmosphere.

  •   The  compressor  ambient  temperature  may 

not exceed 50°C during off-cycle.

  •   Mount  the  compressor  on  a  horizontal  flat 

surface with less than 3° slope.

  •   Verify that the power supply corresponds to 

the  compressor  motor  characteristics  (see  
nameplate).

  •   When installing SZ or SH, use equipment spe

-

cifically  reserved  for  HFC  refrigerants  which 
was never used for CFC or HCFC refrigerants.

  •   Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

  •   Use clean and dehydrated system components.
  •   The piping connected to the compressor must be 

flexible in 3 dimensions to dampen vibrations.

4 – Assembly

  •   In parallel assemblies of SH, SM124 and SM147 

the compressor requires a rigid mounting on 
the rails. Use the rigid spacers from the tandem 
mounting  kit  or  the  rigid  spacers  delivered 
with dedicated tandem compressors.

  •   Slowly  release  the  nitrogen  holding  charge 

through the schrader port.

  •   Remove  the  gaskets  when  brazing  rotolock 

connectors.

  •   Always use new gaskets for assembly.
  •   Connect  the  compressor  to  the  system  as 

soon  as  possible  to  avoid  oil  contamination 
from ambient moisture.

  •   Avoid material entering into the system while 

cutting  tubes.  Never  drill  holes  where  burrs 
cannot be removed.

  •   Braze with great care using state-of-the-art tech

-

nique and vent piping with nitrogen gas flow.

  •   Connect the required safety and control de

-

vices. When the schrader port is used for this, 

remove the internal valve.

  •   Do  not  exceed  the  maximum  tightening 

torque for rotolock connections: 

Rotolock connections Tightening torque

1” rotolock

80 Nm

1 1/4 “ rotolock

90 Nm

1 3/4” rotolock

110 Nm

2 1/4” rotolock

130 Nm.

5 – Leak detection

  Never  pressurize  the  circuit  with  oxygen  or 

dry air. This could cause fire or explosion.

  •   SM 084 to 185, SY 380, SZ 084 to 185, SZ 380, SH 

090 to 180:  Pressurize the system on HP side 
first  and  then  on  LP  side.  Never  let  the  pres-
sure on LP side exceed the pressure on HP side 

with more than 5 bar. Such pressure difference 
could cause internal compressor damage.

  •   SY  240  &  300,  SZ  240  &  300,  SH  240  to  380: 

Pressurize  the  system  slowly  on  LP  side. The 
pressure increase from 0 up to the maximum 
system  test  pressure  at  LP  side  shall  take  at 

least 2 minutes. When the 2 minutes time span 

is not respected, the pressure on LP side could 
exceed the pressure on HP side with more than 
5 bar and cause internal compressor damage.

  •   Do not use dye for leak detection.
  •   Perform a leak detection test on the complete 

system.

  •   The low side test pressure must not exceed 20 

bar for SM/SY/SZ and 30 bar for SH compressors.

  •   When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

  •   Never  use  the  compressor  to  evacuate  the 

system.

  •   Connect a vacuum pump to both the LP & HP 

sides.

  •   Pull down the system under a vacuum of 500 

µm Hg (0.67 mbar) absolute.

  •   Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 
this may cause internal damage.

7 – Electrical connections

  •   Switch off and isolate the main power supply. 

See overleaf for wiring details.

  •   All electrical components must be selected as per 

local standards and compressor requirements.

  •   Refer to page  2 for electrical connections details.
  •   The Performer® scroll compressor only works 

correctly in one rotation direction. Line pha-
ses L1, L2, L3 must absolutely be connected 

Reviews: