Danfoss Optyma Slim Pack OP-LSQM Series Instructions Manual Download Page 3

Instructions

AN23308644013404-001201  | 3

© Danfoss | DCS (CC) | 2019.01

and rigid support, and fixed from the begin-

ning. See picture 2.

 •  It is recommended to install the unit on rub-

ber grommets or vibration dampers (not sup-

plied).

 •  Slowly release the nitrogen holding charge 

through the schrader port.

 •  Connect the unit to the system as soon as pos-

sible to avoid oil contamination from ambient 

moisture.

 •  Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 

cannot be removed.

 •  Braze with great care using state-of-the-art tech-

nique and vent piping with nitrogen gas flow.

 •  Connect the required safety and control de-

vices. When the schrader port is used for this, 

remove the internal valve.

 •  It is recommended to insulate the suction pipe 

up to the compressor inlet with 19 mm thick 

insulation.

5 – Leak detection

 Never pressurize the circuit with oxygen or 

dry air. This could cause fire or explosion.

 •  Do not use dye for leak detection.

 •  Perform a leak detection test on the complete 

system.

 •  The maximum test pressure is 31*

)

 bar.

 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

*

)

 25 bar for OP-.......AJ.... & OP-.......FH.... models

6 – Vacuum dehydration
 •  Never use the compressor to evacuate the system.

 •  Connect a vacuum pump to both the LP & HP 

sides.

 •  Pull down the system under a vacuum of 500 

μm Hg (0.67 mbar) absolute.

 •  Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 

this may cause internal damage.

7 – Electrical connections
 •  Switch off and isolate the main power supply.

 •  Ensure that power supply can not be switched 

on during installation.

 •  All electrical components must be selected as 

per local standards and unit requirements.

 •  Refer to wiring diagram for electrical connec-

tions details.

 •  Ensure that the power supply corresponds 

to the unit characteristics and that the power 

supply is stable (nominal voltage ±10% and 

nominal frequency ±2,5 Hz).

 •  Dimension the power supply cables according 

to unit data for voltage and current.

 •  Protect the power supply and ensure correct 

earthing.

 •  Make the power supply according to local stan-

dards and legal requirements.

 •  The unit is equipped with high and low pressure 

switches, which directly cut the power sup-

ply to the compressor and provides 230V a.c. 

alarm signals (max. 50VA) in case of activation. 

Parameters for high and low pressure cut outs 

should be set by installer considering compres-

sor model, refrigerant and application. Units 

with Danfoss MLZ and LLZ compressors are also 

equipped with phase sequence relay to protect 

the unit against phase loss/sequence/ asym-

metry and under-/over-voltage.

For units with a 3-phase scroll compressor, cor-

rect phase sequence for compressor rotation 

direction shall be observed.

 •  Determine the phase sequence by using a 

phase meter in order to establish the phase 

orders of line phases L1, L2 and L3.

 •  Connect line phases L1, L2 and L3 to main swit-

ch terminals T1, T2 and T3 respectively.

8 – Filling the system
 •  Wear protective stuff like goggles and protec-

tive gloves.

 •  Never start the compressor under vacuum. 

Keep the compressor switched off.

 •  Before charging the refrigerant, verify that the 

oil level is between ¼ and ¾ on the compressor 

oil sight glass. If additional oil is required please 

refer to the compressors label for type of oil.

 •  Use only the refrigerant for which the unit is 

designed for.

 •  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. Ensure a slow 

charging of the system to 4 – 5 bar for R404A 

/ R507A/R407A/R407F/R448A/R449A or R452A 

and approx. 2 bar for R134a/R513A.

 •  Do not put liquid refrigerant through suction line.

 •  It is not allowed to mix additives with the oil 

and/or refrigerant

 •  The remaining charge is done until the instal-

lation has reached a level of stable nominal 

condition during operation.

 •  Never leave the filling cylinder connected to 

the circuit.

9 – Verification before commissioning

 Use safety devices such as safety pressure 

switch and mechanical relief valve in compliance 

with both generally and locally applicable regu-

lations and safety standards. Ensure that they 

are operational and properly set.

 Check that the settings of high-pressure swit-

ches and relief valves don’t exceed the maximum 

service pressure of any system component.

 •  Verify that all electrical connections are properly 

fastened and in compliance with local regulations.

 •  When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-

up and start-up after prolonged shut-down 

period.

10 – Start-up
 •  Never start the unit when no refrigerant is char-

ged.

 •  All service valves must be in the open position.

See picture 3.

 •  Check compliance between unit and power 

supply.

 •  Check that the crankcase heater is working.

 •  Check that the fan can rotate freely.

 •  Check that the protection sheet has been re-

moved from the backside of condenser.

 •  Balance the HP/LP pressure.

 •  Energize the unit. It must start promptly. If 

the compressor does not start, check wiring 

conformity, voltage on terminals and sequence 

phase.

 •  Eventual reverse rotation of  a 3-phase scroll 

compressor can be detected by following 

phenomena; unit is equipped with a phase-re-

versal relay and compressor doesn’t start, the 

compressor doesn’t build up pressure, it has 

abnormally high sound level and abnormally 

low power consumption. In such case, shut 

down the unit immediately and connect the 

phases to their proper terminals.

 •  If the rotation direction is correct the low pres-

sure indication on the low pressure gauge shall 

show a declining pressure and the high pres-

sure indication on the high pressure gauge 

shall show an increasing pressure.

11 – Check with running unit
 •  Check the fan rotation direction. Air must flow 

from the condenser towards the fan.

 •  Check current draw and voltage.

 •  Check suction superheat to reduce risk of slug-

ging.

 •  When a sight glass is provided observe the oil 

level at start and during operation to confirm 

that the oil level remains visible.

 •  Respect the operating limits.

 •  Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 

measures such as tube brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side as 

far away as possible from the compressor. The 

compressor must be operating during this pro-

cess.

 •  Do not overcharge the system.

 •  Follow the local regulations for restoring the 

refrigerant from unit.

 •  Never release refrigerant to atmosphere.

 •  Before leaving the installation site, carry out 

a general installation inspection regarding 

cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference 

for future inspections.

12 – Maintenance

 Always switch off the unit at main switch 

before remove fan panel.

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury.

Maintenance operators and installers require 

appropriate skills and tools. Tubing temperature 

may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related problems, following

Periodic  maintenance is recommended:

 •  Verify that safety devices are operational and 

properly set.

 •  Ensure that the system is leak tight.

 •  Check the compressor current draw.

 •  Confirm that the system is operating in a way 

consistent with previous maintenance records 

and ambient conditions.

 •  Check that all electrical connections are still 

adequately fastened.

 •  Keep the unit clean and verify the absence of 

rust and oxidation on the unit components, 

tubes and electrical connections.

The condenser must be checked at least once 

a year for clogging and be cleaned if deemed 

necessary. Access to the internal side of the 

condenser takes place through the fan panel. 

Microchannel coils tend to accumulate dirt on 

the surface rather than inside, which makes 

them easier to clean than fin-&-tube coils.

 •  Switch off the unit at main switch before re-

move any panel from the condensing unit.

 •  Remove surface dirt, leaves, fibres, etc. with 

a vacuum cleaner, equipped with a brush or 

other soft attachment. Alternatively, blow com-

pressed air through the coil from the inside out, 

and brush with a soft bristle. Do not use a wire 

brush. Do not impact or scrape the coil with the 

Summary of Contents for Optyma Slim Pack OP-LSQM Series

Page 1: ...alian p 22 Portugu s Portuguese p 26 Nederlands Dutch p 30 Suomi Finnish p 34 E Greek p 38 Norsk Norwegian p 42 B lgarski Bulgarian p 46 Rom n Romanian p 50 e tina Czech p 54 Polski Polish p 58 Russia...

Page 2: ...g main switch compressors contactor overload relay Fan speed controller and External main switch W09 only 2 Handling and storage It is recommended not to open the packaging before the unit is at the f...

Page 3: ...dards Ensure that they are operational and properly set Check that the settings of high pressure swit ches and relief valves don t exceed the maximum service pressure of any system component Verify th...

Page 4: ...er Condensing unit measurements are made according to standard EN 13771 2 2007 Com pressor and condensing units for refrigeration performance testing and test methods part 2 Condensing units 14 Warran...

Page 5: ...LP HP signal Contacts Cut In Cut In Cut In Cut out Cut out Cut out Differential Differential fixed Differential Voltage Use Copper wire only Tightening torque 20lb in When used acc to UL regulations H...

Page 6: ...atet m aldrig anvendes i en brandbar atmosf re Plac r aggregatet s det ikke blokerer trafik veje d re vinduer o l S rg for at der er tilstr kkelig plads omkring ag gregatet til at luften kan cirkulere...

Page 7: ...rnemidler som beskyt telsesbriller og handsker Start aldrig kompressoren under vakuum Kompressoren skal v re slukket Inden p fyldning af k lemiddel skal det kontrolle res at oliestanden er mellem 1 4...

Page 8: ...panelet Trin 3 Tag sikkerhedsafbryderen ud Trin 4 Aftagelse af betjeningspanelet 13 Overensstemmelseserkl rin Trykregulativet Pressure Equipment Di rective 2014 68 EU EN 378 2 2016 K le systemer og v...

Page 9: ...C3 10A AC11 10A DC 11 12 W 220 V A B LR A 240 8 16 48 8A 3A 61B5 12W 50VA 16A 96 240 240 120 FL A A C A D SPDT LP signal Anf rt k leregulator LP HP signal Kontakter Cut In Cut In Cut In Cut out Cut ou...

Page 10: ...nden ent nehmen Sie Bild 1 Installieren Sie den Verfl ssigungssatz NICHT an Orten die t glich l ngerer Sonneneinstrah lung ausgesetzt sind Installieren Sie denVerfl ssigungssatz NICHT in aggressiven o...

Page 11: ...tschalterklemmen T1 T2 und T3 an 8 F llen der Anlage Tragen Sie Schutzkleidung wie z B eine Schutz brille und Schutzhandschuhe Nehmen Sie den Verdichter niemals unter Vaku um in Betrieb Sorgen Sie daf...

Page 12: ...8 021 OP MSYM009 012 014 OP MSGM012 015 OP MSYM018 OP LSQM026 034 048 068 074 OP MSBM018 024 026 034 OP MSXM034 044 046 057 OP MSGM026 033 OP LSQM067 084 098 OP MSXM068 080 093 099 108 Schritt 1 Entne...

Page 13: ...12 W 220 V A B LR A 240 8 16 48 8A 3A 61B5 12W 50VA 16A 96 240 240 120 FL A A C A D SPDT ND Signal Gelistete K hlstellenregler ND HD Signal Kontakte Einschaltwert Einschaltwert Einschaltwert Abschalt...

Page 14: ...mettre la circulation de l air et l ouverture des portes R f rez vous l illustration 1 pour obtenir les distances mini males respecter entre le groupe et les murs vitez d installer le groupe un emplac...

Page 15: ...ment 8 Remplissage du syst me Portez des quipements de protection tels que des gants et des lunettes de protection Ne d marrez jamais le compresseur lorsqu il se trouve sous vide Maintenez le compress...

Page 16: ...P MSXM068 080 093 099 108 Etape 1 Retirer l enjoliveur du sectionneur de proximit avec un tournevis Etape 2 Retirer les vis de fixation Etape 3 D poser le sectionneur de proximit Etape 4 Retirer le pa...

Page 17: ...apporter sans pr a y compris ceux se trouvant d j en commande sous r serve toutefois caract ristiques d j arr t es en accord avec le client Toutes les marques de fabrique de cette documentation sont l...

Page 18: ...raturas compren didas entre 35 C y 50 C No exponga el embalaje a la lluvia o a atm sfe ras de car cter corrosivo Tras desembalar la unidad compruebe que no falte ning n componente y que no presente da...

Page 19: ...e en el sen tido apropiado Emplee un medidor de fases para establecer el orden de las fases de l nea L1 L2 y L3 Conecte las fases de l nea L1 L2 y L3 a los termi nales T1 T2 y T3 del interruptor princ...

Page 20: ...BM018 024 026 034 OP MSXM034 044 046 057 OP MSGM026 033 OP LSQM067 084 098 OP MSXM068 080 093 099 108 Paso 1 Tire de la tapa del interruptor de secciona miento con un destornillador Paso 2 Desatornill...

Page 21: ...OFF R404A R507 R407A R407F R448A R449A R452A 23 27 2 1 R134a R513A 13 17 2 1 Se al SPDT LP Controlador de refrigeraci n listado Se al LP HP Contactos Enganche Enganche Enganche Corte Corte Corte Difer...

Page 22: ...completa e priva di danni 3 Precauzioni per l installazione Non brasare se l unit di condensazione sot to pressione Non usare mai l unit in atmosfere infiamma bili Posizionare l unit in modo che non...

Page 23: ...del compressore per il tipo d olio Utilizzare solo refrigeranti per i quali l unit stata progettata Immettere il refrigerante in fase liquida nel con densatore o nel ricevitore di liquido Assicurare u...

Page 24: ...i sicu rezza e ambientali Parte 2 Progettazione cos truzione collaudo marcatura e documentazione Direttiva sulla bassa tensione 2014 35 UE EN 60335 1 2012 A11 2014 Sicurezza degli appa recchi elettric...

Page 25: ...B LR A 240 8 16 48 8A 3A 61B5 12W 50VA 16A 96 240 240 120 FL A A C A D SPDT segnale LP Regolatore di refrigerazione classificato segnale LP HP Contatti Cut In Cut In Cut In Cut out Cut out Cut out Dif...

Page 26: ...uma atmosfera corrosiva Ap s desembalar verifique se a unidade est completa e n o est danificada 3 Instala o e precau es N o solde enquanto a unidade de condensa o estiver sob press o Nunca utilize a...

Page 27: ...ar com refrigerante verifique se o n vel do leo est entre e na janela de controlo do leo do compressor Se for necess rio mais leo consulte a etiqueta do compressor para saber qual o tipo de leo Utiliz...

Page 28: ...conformidade Diretiva sobre equipamentos sob press o 2014 68 EU EN 378 2 2016 Sistemas de refri gera o e bombas t rmicas Requisitos de segu ran a e ambientais Partes 2 Projeto constru o testes marca...

Page 29: ...C11 10A DC 11 12 W 220 V A B LR A 240 8 16 48 8A 3A 61B5 12W 50VA 16A 96 240 240 120 FL A A C A D SPDT sinal de BP Controlador de refrigera o listado Sinal de BP AP Contactos Ligar Ligar Ligar Desliga...

Page 30: ...kken of het apparaat volledig en intact is 3 Voorzorgsmaatregelen bij de installatie Soldeer niet zolang de koelgroep onder druk staat Gebruik het apparaat nooit in een ontvlam bare atmosfeer Plaats h...

Page 31: ...dan het compressorlabel voor het type olie Gebruik enkel het koelmiddel waarvoor het ap paraat is ontworpen Vul het koelmiddel in vloeibare fase in de con densor of vloeistofopening Zorg ervoor dat h...

Page 32: ...r og varmepumper Sikkerheds og milj m ssige krav Del 2 Design konstruktion tests m r kning og dokumentation Lavsp ndingsdirektivet 2014 35 EU EN 60335 1 2012 A11 2014 Elektriske apparater til hus hold...

Page 33: ...enoemde koelregelaar LP HP signaal Contacten Inschakelen Inschakelen Inschakelen Uitschakelen Uitschakelen Uitschakelen Differentieel Differentieel vast Differentieel Spanning Gebruik alleen koperdraa...

Page 34: ...3 Asennuksen varotoimenpiteet l juota kun koneikko on paineistettuna l koskaan k yt koneikkoa ymp rist ss jossa on syttymisvaara Sijoita koneikko niin ettei se est p sy kulkureitteihin oviin ikkunoihi...

Page 35: ...eet ovat toimintakunnossa ja ett niiden s d t ovat oikein Tarkista ett turvakytkimien ja varoventtiilien asetukseteiv tylit mink nj rjestelm komponentin suurinta sallittua k ytt painetta Tarkista ett...

Page 36: ...oneikot j hdytystehon testaukseen ja testimenetelm t osa 2 Koneikot 14 Takuu Ilmoita aina malli ja sarjanumero kun j t t tuotetta koskevan korvausvaateen Tuotteen takuu saattaa raueta seuraavissa tapa...

Page 37: ...D SPDT LP signaali J hdytyksen ohjaus LP HP signaali Koskettimet Kytkent Kytkent Kytkent Katkaisu Katkaisu Katkaisu Ero Eroalue kiinte Ero J nnite K yt ainoastaan kuparilankaa Kiristysmomentti 2 26 N...

Page 38: ...Barcode Serial No 123456CG4818 118UXXXX A B C D E F G OIL INSIDE POE 46 MADE IN INDIA EAN No Danfoss A S 6430 Nordborg Denmark XXXXXXXXXXXXX A C D E F G L M N O L mm M mm N mm O mm 250 650 550 550 1...

Page 39: ...2 schrader schrader 19 mm 5 31 bar 25 bar OP AJ OP FH 6 LP HP 500 m Hg 0 67 mbar 7 10 2 5 Hz 230V 50VA MLZ LLZ Danfoss 3 L1 L2 L3 L1 L2 L3 T1 T2 T3 8 4 5 bar R404A R507A R407A R407F R448A R449A R452A...

Page 40: ...8 OP MSXM068 080 093 099 108 1 2 3 4 13 2014 68 EN 378 2 2016 2 2014 35 EN 60335 1 2012 A11 2014 1 2009 125 E 2015 1095 2009 125 E EN 13771 2 2007 2 14 Danfoss 15 Danfoss 16 R134a R513A FSC XGE 2C 061...

Page 41: ...7F R448A R449A R452A 23 27 2 1 R134a R513A 13 17 2 1 1 bar Pe 30in Hg KP 17W 17B KP 17B 060 539366 060 539466 LR 112A 400 V AC1 10A AC3 10A AC11 10A DC 11 12 W 220 V A B LR A 240 8 16 48 8A 3A 61B5 12...

Page 42: ...atet er under trykk Plasser aldri enheten i et brannfarlig milj Plasser enheten slik at den ikke blokkerer eller er til hindring i gangomr der d rer vinduer eller lignende Sikre at det er tilstrekkeli...

Page 43: ...inderenv rekoblettilkretsen 9 Verifikasjon f r idriftsettelse Bruk sikkerhetsanordninger som sikkerhet strykkbryterogmekanisktrykkbegrensningsventil i overensstemmelse med generelle og lokale gjeldend...

Page 44: ...kap kondenseringsenheter og prosesskj lere M ling av kondenseringsenheter foretas i samsvar med standard EN 13771 2 2007 Kj lekompressorer og kondensatorer for kj ling Ytelsespr ving og pr vingsmetode...

Page 45: ...A C A D SPDT LP signal Angitt kj leregulator LP HP signal Kontakter Innkobling Innkobling Innkobling Utkobling Utkobling Utkobling Differanse Fast differanse Differanse Spenning Bruk kun kobberlednin...

Page 46: ...rial No Barcode Serial No 123456CG4818 118UXXXX A B C D E F G OIL INSIDE POE 46 MADE IN INDIA EAN No Danfoss A S 6430 Nordborg Denmark XXXXXXXXXXXXX A B C D E F G L M N O L mm M mm N mm O mm 250 650 5...

Page 47: ...1 HFC HFO CFC HCFC 3 4 PED 97 23 EC 2 19 mm 5 31 bar 25 OP AJ OP FH 6 500 m Hg 0 67 mbar 7 10 2 5 Hz 230 V 50 VA Danfoss MLZ LLZ 3 L1 L2 L3 L1 L2 L3 T1 T2 T3 8 4 5 bar R404A R507A R407A R407F R448A R4...

Page 48: ...067 084 098 OP MSXM068 080 093 099 108 1 2 3 4 13 Pressure Equipment Directive 2014 68 EU EN 378 2 2016 2 2014 35 EN 60335 1 2012 A11 2014 1 2009 125 2015 1095 2009 125 EN 13771 2 2007 2 14 Danfoss 15...

Page 49: ...A R449A R452A 23 27 2 1 R134a R513A 13 17 2 1 1 bar Pe 30in Hg KP 17W 17B KP 17B 060 539366 060 539466 LR 112A 400 V AC1 10A AC3 10A AC11 10A DC 11 12 W 220 V A B LR A 240 8 16 48 8A 3A 61B5 12W 50VA...

Page 50: ...complet i nedeteriorat 3 M suri de precau ie la instalare Nu braza i n cazul n care grupul de conden sare se afl sub presiune Nu amplasa i niciodat grupul ntr o atmo sfer inflamabil Amplasa i grupul a...

Page 51: ...ac nivelul uleiului se situeaz ntre i pe vizorul de ulei al compresorului Dac este ne voie de mai mult ulei consulta i eticheta com presorului pentru tipul uleiului Utiliza i numai agentul frigorific...

Page 52: ...quipment Directive 2014 68 EU EN 378 2 2016 Sisteme de refrigerare i pompe de c ldur Cerin e privind siguran a i mediul nconjur tor Partea 2 Proiecta rea construc ia testarea inscrip ionarea i documen...

Page 53: ...IT PORNIT OPRIT R404A R507 R407A R407F R448A R449A R452A 23 27 2 1 R134a R513A 13 17 2 1 Semnal SPDT LP Controler pentru agentul frigorific specificat Semnal LP HP Contacte Cuplare Cuplare Cuplare Dec...

Page 54: ...Neprov d jte p jen dokud je kondenza n jednotka pod tlakem Jednotku nikdy nemontujte do snadno vzn tliv ho prost ed Um st te jednotku tak aby neblokovala nebo nep ek ela v m stech kde se chod kde jso...

Page 55: ...ed uveden m do provozu Bezpe nostn za zen jako jsou nap bezpe nostn tlakov jisti a mechanick pojistn ventil po u vejte v souladu s v eobecn mi i m stn mi plat n mi p edpisy a bezpe nostn mi normami Zk...

Page 56: ...za n ch jednotek a procesn ch chla dic ch za zen M en kondenza n ch jednotek se prov d v souladu s normou EN 13771 2 2007 Kom presory a kondenza n jednotky pro chlazen M en v konnosti a zku ebn metody...

Page 57: ...DT LP sign l Uveden regul tor ledni ky LP HP sign l Kontakty Zap nac tlak Zap nac tlak Zap nac tlak Vyp nac tlak Vyp nac tlak Vyp nac tlak Tlakov rozd l Ust len rozd l Tlakov rozd l nap t Pou vejte po...

Page 58: ...nnych czynnik w atmosferycznych po woduj cych korozj Po rozpakowaniu sprawdzi czy agregat jest kompletny oraz czy nie jest uszkodzony 3 rodki ostro no ci podczas instalacji Nie przyst powa do lutowani...

Page 59: ...rz t ochrony osobistej taki jak okulary i r kawice ochronne Nigdy nie uruchamia spr arki obci onej podci nieniem Spr arka musi by wy czona Przed dodaniem czynnika ch odniczego nale y sprawdzi we wzier...

Page 60: ...serwisowego 13 Deklaracja zgodno ci Pressure Equipment Directive 2014 68 EU EN 378 2 2016 Systemy ch odnicze i pompy ciep a wymagania bezpiecze stwa i rodowiskowe Cz 2 Projektowanie budo wa testowanie...

Page 61: ...12 W 220 V A B LR A 240 8 16 48 8A 3A 61B5 12W 50VA 16A 96 240 240 120 FL A A C A D 17 Ustawienia fabryczne presostatu Czynniki ch odnicze Nastawy wysokiego ci nienia bar g Nastawy niskiego ci nienia...

Page 62: ...5 A MCC Serial No Barcode Serial No 123456CG4818 118UXXXX A B C D E F G OIL INSIDE POE 46 MADE IN INDIA EAN No Danfoss A S 6430 Nordborg Denmark XXXXXXXXXXXXX A B C D E F G L M N O L mm M mm N mm O m...

Page 63: ...63 Danfoss DCS CC 2019 01 4 PED 97 23 EC 2 19 5 31 25 OP AJ OP FH 6 500 0 67 7 10 2 5 230 50 Danfoss MLZ LLZ 3 L1 L2 L3 L1 L2 L3 T1 T2 T3 8 4 5 R404A R507A R407A R407F R448A R449A R452 A 2 R134a R513...

Page 64: ...OP MSXM068 080 093 099 108 1 2 3 4 13 2014 68 EU EN 378 2 2016 2 2014 35 EU EN 60335 1 2012 A11 2014 1 2009 125 EC EU 2015 1095 2009 125 EC EN 13771 2 2007 2 14 Danfoss 15 Danfoss je byly p ed ny k re...

Page 65: ...7B 060 539366 060 539466 LR 112A 400 V AC1 10A AC3 10A AC11 10A DC 11 12 W 220 V A B LR A 240 8 16 48 8A 3A 61B5 12W 50VA 16A 96 240 240 120 FL A A C A D 17 R404A R507 R407A R407F R448A R449A R452A 23...

Page 66: ...mm 530 mm A B C D E 10 327 mm 344 mm OP LSHM015 018 OP MSHM010 012 015 018 OP MSGM012 015 018 021 OP LSQM014 018 OP MSYM009 012 014 30 mm 44 mm 464 mm 1035 mm 690 mm 431 mm 750 mm 444 mm 10 A B C D E...

Page 67: ...V lvula do dispositivo de l quido D Entrada de ar E Sa da de ar Cabos el tricos Nota todas as dimens es s o apresentadas em mm Nederlands Legende A Isolatieschakelaar alleen W09 B Zuigsignaalklep C Vl...

Page 68: ...Code G W05 OP MSHM010 012 015 OP LSHM015 018 OP MSGM012 015 018 026 Code G W05 OP LSQM026 034 048 068 074 OP MSGM033 OP MSBM018 024 026 034 OP MSXM034 044 46 057 Instructions 68 AN23308644013404 00120...

Page 69: ...Code G W05 OP MSXM068 080 093 WD3 Code E W05 OP MSBM026 034 B B WD4 Instructions AN23308644013404 001201 69 Danfoss DCS CC 2019 01...

Page 70: ...Code E W05 OP LSQM048 068 074 OP MSXM034 044 046 057 WD5 Code E W05 OP MSXM068 080 099 108 OP LSQM067 084 098 WD6 Instructions 70 AN23308644013404 001201 Danfoss DCS CC 2019 01...

Page 71: ...G W05 OP MSYM009 012 014 OP LSQM014 018 OP MSHM018 OP MSGM21 WD7 Code G W09 OP LSQM014 018 OP MSGM018 021 OP MSYM009 012 014 OP MSBM018 WD8 Instructions AN23308644013404 001201 71 Danfoss DCS CC 2019...

Page 72: ...Code G W09 OP MSGM012 015 026 WD9 B B Code E W09 OP LSQM048 068 074 OP MSBM026 034 OP MSXM034 044 046 057 WD10 Instructions 72 AN23308644013404 001201 Danfoss DCS CC 2019 01...

Page 73: ...G W09 OP LSQM026 034 048 068 074 OP MSBM024 026 034 OP MSXM034 044 046 057 OP MSGM033 WD12 WD11 Code E W09 OP MSXM068 080 099 108 OP LSQM067 084 098 Instructions AN23308644013404 001201 73 Danfoss DCS...

Page 74: ...l circuit F4 Compressor thermal protector K1 Contactor K2 Start relay M1 Compressor M2 Fan motor R1 R2 R2 Bleeder resistor S1 Room thermostat option X1 Terminals Option remove bridge WD13 Dansk Legend...

Page 75: ...X1 Liitin Vaihtoehto poista silta Portugu s Lenda BK preto BU azul BN marrom GY cinza RD vermelho WH branco A1 Rel de tens o A1 Rel de tens o opcional B1 Controlador de velocidade do ventilador B1 Con...

Page 76: ...F4 Tepeln ochranakompresoru K1 Styka K2 Rozb hov rel M1 Kompresor M2 Motorventil toru R1 R2 R2 Vyb jec rezistor S1 Prostorov termostat nap n X1 Svorky Varianta odstra tepropojku Rom n Legend BK negru...

Reviews: