© Danfoss | DCS (CC) | 2020.06
2 | AN23308644013405-001401 - 118A0549C
Installation and servicing of the conden-
sing units by qualified personnel only. Follow
these instructions and sound refrigeration
engineering practice relating to installation,
commissioning, maintenance and service.
The condensing unit must only be used for
its designed purpose(s) and within its scope of
application.
Under all circumstances, the EN378 (or
other applicable local safety regulation)
requirements must be fulfilled.
The condensing unit is delivered under nitro-
gen gas pressure (1 bar) and hence it cannot
be connected as it is; refer to the «installation»
section for further details.
The condensing unit must be handled with cau-
tion in the vertical position (maximum offset
from the vertical : 15°)
OP-MSXM034MLW05E
Application
Refrigerant
M.W.P. HP
114X7062
MBP
(1) R404A, R452A, R507,
R448/9A
(1) 28 bar
LP (1) 7 bar
IP54
(2) R134a
(2) R513A
(2) 23 bar
(2) 5 bar
Voltage
380-400V~3N~50Hz
LRA
30,5 A
7,5 A
MCC
Serial No.
Barcode Serial No:
123456CG4818
118UXXXX
A
B
C
D
E
F
G
OIL INSIDE POE 46
MADE IN INDIA
EAN No.
Danfoss A/S, 6430 Nordborg, Denmark
XXXXXXXXXXXXX
A
: Model
B
: Code number
C
: Application, Protection
D
: Refrigerant
E
: Housing Service Pressure (Maximum working
pressure)
F
: Supply voltage, Locked Rotor Ampere,
Maximum Continuous Current
G
: Serial Number and bar code
L
M
N
O
L
[mm]
M
[mm]
N
[mm]
O
[mm]
250
650
550
550
Picture 1 : Minimum mounting distances
Optyma™
Slim Pack
OP-LSQM / LSHM / MSXM / MSHM /
MSGM / MSYM / MSBM
Name plate
Instructions
* For exact values please refer name plate in unit
OP - MSXM 034 ML W05 G
1 2 3 4
5
6
7
8
1
Application
M = MBP
L = LBP
2
Package
Condensing unit family: S = Slim Pack
3
Refrigerant
H = R404A/R507 ;
G = R134a, R513A ;
Q = R452A, R404A/R507
X = R404A/R507, R134a, R407A, R407F, R448A, R513A,
R449A,R452A ;
Y = R404A/R507, R448A, R449A;
B = R404A/R507, R449A, R452A;
P = R448A/R449A, R407A/F, R404A/R507,
O = R452A, R404A/R507, R448A, R449A
4
Condenser
M = Microchannel heat condenser
5
Swept volume
Displacement in cm
3:
Example 034 = 34 cm
3
6
Compressor platform
MLZ, LLZ = Scroll Compressor
MTZ & NTZ = Reciprocating Compressor
7
Version
W05/W09: Optyma™ Slim Pack
8
Voltage code
G = 230V/1-phase compressor & 230V/1 phase fan
E = 400V/3-phase compressor & 230V/1-phase fan
Optyma™
Slim Pack
W05
W09
IP level
IP54
Compressor technology
Scroll/Reciprocating
Control box (pre-wired E-panel)
yes
Microchannel condenser
yes
Fan speed controller
-
yes
Main switch (circuit breaker)
-
yes
Filter drier (flare connections)
yes
Sight glass
yes
Crankcase heater
yes
HP/LP adjustable pressostat
Auto/Manual reset mode
Discharge gas thermostat (provision)
yes*
HP/LP Alarm (provision)
yes*
Version control
Designation system for the
Optyma