Installation & Maintenance

Problem

Possible cause

Confirmation method/Remarks

Fan motor doesn’t rotate, 

or rotates at full speed

"F.V.S. pressure setting is 

inadequate"

Check the operation of the fan motor. 

• Pressure setting value may be too high if the fan motor rotates 

continuously at low speed or stops.

=> Turn the F.V.S. pressure adjustment screw in (-) direction to set 

the F.V.S. pressure lower.

• Pressure setting value may be too low if the fan motor rotates 

continuously at full speed.

=> Turn the F.V.S. pressure adjustment screw in (+) direction to set 

the F.V.S. pressure higher.

Note:

- In the event that the F. V. S. pressure setting value is lost  

(for XGE-4*), rotate the pressure setting screw fully toward the 

(-) symbol, then rotate it 9 times*1 towards the (+) symbol. This 

should return the F.V.S. pressure setting value to around the factory 

standard setting value of 1.9 MPa.

- Always conduct a test run after changing the setting to confirm 

the system operates correctly.

PCB was damaged by drop 

impact

If voltage output cannot be obtained, the internal ceramic PCB may 

be damaged.

Overcurrent was applied

Check if the rated value of the fan motor is within tolerance.

=> Max. 3A (or 4A conditionally) 

• Check if a load is restricting the fan motor rotation. (Such as snow 

or freezing.)

• Check if a line-to-line short circuit is detected at a connection 

point of the fan motor.

• It is recommended to protect the circuit with a thermal relay or 

circuit protector.

Note: Make sure to remove the cause of burn-out before 

conducting a test run. Otherwise, burn-out may occur again.

Surge voltage was applied

Check if a lightning surge or similar occurred or not.

PCB burn-out

Burn-out may be caused by water leakage due to an improperly 

fitted plug.

Check the following items to find any problems with the fitting.

• Is it tightened to the prescribed torque?

• Is the plug fitted with the attached gasket?

• Is there a gap between the plug and body?
When a screw other than attached one is used, the body may be 

damaged allowing water to leak inside, causing burn-out. Do not 

use screws other than those attached.
Burn-out of PCB may be caused by water leaking from the 

damaged part of the body.

Control is unstable.

In particular, check the connection of the pressure coupling for any 

leakage. Leakage may occur when copper gasket is not used or 

misaligned.
Check the pressure introduction position

• Receiver valve fully opened

• Filter drier clogged off,

• Shreader core press down.

It is recommended to detect the pressure from the exit side of 

condenser.

Cannot fix the plug

Plug fitting screw stripping

Screws may become stripped when they are tightened with a 

torque greater than the prescribed value. Please tighten with the 

prescribed torque.

Summary of Contents for OP-HJZM

Page 1: ...Installation and maintenance condensing unit manual OP HJZM HNXM HRXM LNYM LRYM LJHM Manual http cc danfoss com...

Page 2: ...e of the condensing unit must be carried out by qualified personnel only Follow these instructions and best practices on refrigeration engineering during installation commissioning maintenance and ser...

Page 3: ...t or pallet jack for handling Use appropriate and safe lifting equipment Store and transport the unit in an upright position Store the unit between 30 F and 120 F Don t expose the packaging to rain or...

Page 4: ...erial Use clean and dehydrated system components The suction piping connected to the compressor must be flexible in 3 dimensions to dampen vibrations Furthermore piping has to be done in such a way th...

Page 5: ...applied to this product it causes transformation of characteristics or the destruction Operation will become unstable when using other than sine waves for the power supply In this case proper control...

Page 6: ...Such as snow or freezing Check if a line to line short circuit is detected at a connection point of the fan motor It is recommended to protect the circuit with a thermal relay or circuit protector No...

Page 7: ...intenance Switch off the system and isolate the main power supply Ensure that power supply cannot be switched on during installation All electrical components must be selected as per local standards a...

Page 8: ...rify that all electrical connections are properly fastened and in compliance with local regulations When a crankcase heater is required it must be energized at least 12 hours before initial start up a...

Page 9: ...ctions are still adequately fastened Keep the unit clean and verify the absence of rust and oxidation on the unit components tubes and electrical connections The condenser must be checked at least onc...

Page 10: ...47 4 16 5 7 8 1 2 HRXM0500 2 28 8 49 4 31 5 7 8 1 2 HRXM0600 2 28 8 49 4 31 5 7 8 1 2 HRXM0700 2 28 8 49 4 31 5 7 8 1 2 HRXM0750 2 39 1 61 2 31 5 1 1 8 5 8 HRXM1000 2 39 1 61 2 31 5 1 1 8 5 8 Unit Di...

Page 11: ...1 8 X 7 8 W D H 2X Knockout 7 8 Liquid Line C L C L Suction Line 2X Double Knockout 1 1 8 X 7 8 W H D 2X Knockout 7 8 C L Suction Line Liquid Line C L 2X Double Knockout 1 1 8 X 7 8 W D H 2X Knockout...

Page 12: ...BC251686497767en US0801 Electrical wiring diagrams Wiring Diagram 119 8312 Wiring Diagram 119 8313 Electrical Code N HJZM0150 HNXM0200 0400 HRXM0500 LJHM0150 0200 Electrical Code Q HNXM0200 0400 HRXM...

Page 13: ...51686497767en US0801 Electrical wiring diagrams X 4 2 1 N 3 N O LOAD N C LOAD Wiring Diagram 119 8315 Wiring Diagram 119 8493 Electrical Code Q HJZM0150 LJHM0150 0200 Electrical Code Q LNYM0400 0500 L...

Page 14: ...Manual 14 BC251686497767en US0801 Electrical wiring diagrams Wiring Diagram 119 8640 Wiring Diagram 119 8641 Electrical Code R HRZM0600 1000 Electrical Code R LRYM0600 0800...

Page 15: ...op the refrigerant flow through the evaporator 10 Suction pressure decreases and the compressor contactor opens when the pressure drops below the cut out setting on the low pressure control The compre...

Page 16: ...ensions Length Height in mm in mm HJXM0150 0200 LJHM0150 0300 26 660 19 480 HJXM0200 0300 29 740 22 550 LNYM0400 0500 HJXM0350 0400 31 780 27 700 HRXM0500 0700 LRYM0600 0800 46 1170 28 720 HRXM0750 10...

Page 17: ......

Page 18: ...erter Scrolls Danfoss Turbocor Compressors Danfoss Scrolls Danfoss Optyma Condensing Units Danfoss Maneurop Reciprocating Compressors BC251686497767en US0801 Danfoss DCS CC 2019 11 Our products can be...

Reviews: