Manual
16
BC251686497767en-US0801
5. If the termination thermostat fails to close,
the fail-safe set on the timer will terminate the
defrost.
6. The defrost heaters are off.
7. The low-pressure control closes when the cut-in
pressure is attained, allows the compressor to
start.
8. When the evaporator coil temperature reaches
23˚F to 30˚F, the fan delay closes and allows the
fan motors to run.
9. The system will now operate in the refrigeration
cycle until another defrost cycle is triggered by
the timer.
Sequence of operation – Field wiring
Hailguard Installation
1. Identify the hailguard size needed and trim the
hailguard (if needed) based on the table shown
below, cutting with scissors or utility knife
Model
Dimensions
Length
Height
in.
mm
in.
mm
HJXM0150-0200
LJHM0150-0300
26
660
19
480
HJXM0200-0300
29
740
22
550
LNYM0400-0500
HJXM0350-0400
31
780
27
700
HRXM0500-0700
LRYM0600-0800
46
1170
28
720
HRXM0750-1000
58
1470
38
970
2. Remove the screws from the sides and top of
the condenser.
3. Lock the hailguard into place by reattaching
the screws. Start on the left side, unrolling the
hailguard before attaching to the right side. Pull
tight as you progress.
4. The hailguard is now attached and will protect
your Optyma Slim condensing unit from hail
and other elements.
NOTE
This wiring diagram is for field reference only.
1) Two contactors one for evaporator fan and
other for defrost heater will be needed. No
extra contactors to be provided with the
unit.
2) Fuse F4 for defrost heaters and cable and
Fuse F5 for evaporator fans and cables will
not be supplied with the unit. These will
need to be purchased separately.