background image

Manual

7

BC251686497767en-US0801

 Never pressurize the circuit with oxygen or dry 

air. This could cause fire or explosions.
 •  Do not use dye for leak detection.
 •  Perform a leak detection test on the complete 

system.

 •  The maximum test pressure is 465psi.
 •  When a leak is discovered, repair the leak and 

repeat the leak detection test.

 •  Never use the compressor to evacuate the 

system.

 •  Connect a vacuum pump to both the LP and HP 

sides.

 •  Pull down the system under a vacuum of 500 µm 

Hg (9.7psi) absolute.

 •  Do not use an ohmmeter nor apply power to the 

compressor while it is under vacuum as this may 
cause internal damage.

(If FSC fails, it is possible to run the fan motor full 
speed)

1.  Disconnect the condensing unit from power 

supply.

2. Remove wire 1 from FSC. 
3. Remove wire 2 from FSC.

4. Connect both wires together.
5.  Make sure the connection is well insulated and 

not exposed to rain or in contact with, metallic 
parts.

6.  Connect the condensing unit back to power 

supply.

Leak detection

Fan speed controller 

bypass

Vacuum dehydration

Fig.6

Installation & Maintenance

 •  Switch off the system and isolate the main power 

supply.

 •  Ensure that power supply cannot be switched on 

during installation.

 •  All electrical components must be selected as 

per local standards and unit requirements.

 •  Refer to wiring diagram for electrical connections 

details.

 •  Ensure that the power supply corresponds to the 

unit characteristics and that the power supply 
is stable (nominal voltage ±10 % and nominal 
frequency ±2.5 Hz).

 •  Dimension the power supply cables according to 

unit data for voltage and current.

 •  Protect the power supply and ensure correct 

earthing.

 •  Make the power supply according to local 

standards and legal requirements.

 •  The unit includes high and low-pressure switches 

which, when activated, cut the power supply 
to the compressor. Parameters for high and 
low-pressure cut-outs are to be adjusted by 
the installer, depending on the compressor 
model, refrigerant and application. For units 
with a 3-phase scroll compressor, correct phase 
sequence for compressor rotation direction shall 
be observed.

 •  Determine the phase sequence by using a phase 

meter to establish the phase order of line phases 
L1, L2 and L3.

 •  Connect line phases L1, L2 and L3 to main switch 

terminals T1, T2 and T3, respectively.

Electrical connections

Summary of Contents for OP-HJZM

Page 1: ...Installation and maintenance condensing unit manual OP HJZM HNXM HRXM LNYM LRYM LJHM Manual http cc danfoss com...

Page 2: ...e of the condensing unit must be carried out by qualified personnel only Follow these instructions and best practices on refrigeration engineering during installation commissioning maintenance and ser...

Page 3: ...t or pallet jack for handling Use appropriate and safe lifting equipment Store and transport the unit in an upright position Store the unit between 30 F and 120 F Don t expose the packaging to rain or...

Page 4: ...erial Use clean and dehydrated system components The suction piping connected to the compressor must be flexible in 3 dimensions to dampen vibrations Furthermore piping has to be done in such a way th...

Page 5: ...applied to this product it causes transformation of characteristics or the destruction Operation will become unstable when using other than sine waves for the power supply In this case proper control...

Page 6: ...Such as snow or freezing Check if a line to line short circuit is detected at a connection point of the fan motor It is recommended to protect the circuit with a thermal relay or circuit protector No...

Page 7: ...intenance Switch off the system and isolate the main power supply Ensure that power supply cannot be switched on during installation All electrical components must be selected as per local standards a...

Page 8: ...rify that all electrical connections are properly fastened and in compliance with local regulations When a crankcase heater is required it must be energized at least 12 hours before initial start up a...

Page 9: ...ctions are still adequately fastened Keep the unit clean and verify the absence of rust and oxidation on the unit components tubes and electrical connections The condenser must be checked at least onc...

Page 10: ...47 4 16 5 7 8 1 2 HRXM0500 2 28 8 49 4 31 5 7 8 1 2 HRXM0600 2 28 8 49 4 31 5 7 8 1 2 HRXM0700 2 28 8 49 4 31 5 7 8 1 2 HRXM0750 2 39 1 61 2 31 5 1 1 8 5 8 HRXM1000 2 39 1 61 2 31 5 1 1 8 5 8 Unit Di...

Page 11: ...1 8 X 7 8 W D H 2X Knockout 7 8 Liquid Line C L C L Suction Line 2X Double Knockout 1 1 8 X 7 8 W H D 2X Knockout 7 8 C L Suction Line Liquid Line C L 2X Double Knockout 1 1 8 X 7 8 W D H 2X Knockout...

Page 12: ...BC251686497767en US0801 Electrical wiring diagrams Wiring Diagram 119 8312 Wiring Diagram 119 8313 Electrical Code N HJZM0150 HNXM0200 0400 HRXM0500 LJHM0150 0200 Electrical Code Q HNXM0200 0400 HRXM...

Page 13: ...51686497767en US0801 Electrical wiring diagrams X 4 2 1 N 3 N O LOAD N C LOAD Wiring Diagram 119 8315 Wiring Diagram 119 8493 Electrical Code Q HJZM0150 LJHM0150 0200 Electrical Code Q LNYM0400 0500 L...

Page 14: ...Manual 14 BC251686497767en US0801 Electrical wiring diagrams Wiring Diagram 119 8640 Wiring Diagram 119 8641 Electrical Code R HRZM0600 1000 Electrical Code R LRYM0600 0800...

Page 15: ...op the refrigerant flow through the evaporator 10 Suction pressure decreases and the compressor contactor opens when the pressure drops below the cut out setting on the low pressure control The compre...

Page 16: ...ensions Length Height in mm in mm HJXM0150 0200 LJHM0150 0300 26 660 19 480 HJXM0200 0300 29 740 22 550 LNYM0400 0500 HJXM0350 0400 31 780 27 700 HRXM0500 0700 LRYM0600 0800 46 1170 28 720 HRXM0750 10...

Page 17: ......

Page 18: ...erter Scrolls Danfoss Turbocor Compressors Danfoss Scrolls Danfoss Optyma Condensing Units Danfoss Maneurop Reciprocating Compressors BC251686497767en US0801 Danfoss DCS CC 2019 11 Our products can be...

Reviews: