General Operation

ICAD is equipped with an MMI (Man 

Machine Interface) from which it is possible 

to see and change different parameters to 

adapt the ICAD and the corresponding ICM 

to the actual refrigeration application. The 

operation of parameters is done by means 

of the integrated ICAD MMI (fig. 2) and 

consists of:

1

2

3

Down arrow push button (fig. 2, pos. 1) 

decreases parameter number by 1 for 

each activation
Enter push button (fig. 2, pos. 2)

Gives access to the 

Parameter list

 by 

keeping the push button activated for 

2 seconds. A 

Parameter list

 is shown 

below (parameter 

¡08

):

Gives access to change a value once 

the 

Parameter list

 has been accessed.

Acknowledge and save change of 

value of a parameter.

To exit from the 

Parameter list

 and 

return to the display of Opening 

Degree (OD) keep the push button 

activated for 2 seconds.

Up arrow push button (fig. 2, pos. 3)

Increases parameter number by 1 for 

each activation

Display (fig. 2, pos. 4)

Normally the Opening Degree (OD)  

0 - 100 % of the ICM valve is displayed. 

No activation of push buttons for 20 

seconds means that the display will 

always show OD. Like below:

Displays the parameter

Displays the actual value of a 

parameter.

Displays the status by means of text  

(fig. 2, pos. 4)

Mod

 represents that ICAD is 

positioning the ICM valve according 

to an analog input signal (Current or 

Voltage).

Low

 represents that ICAD is operating 

the ICM valve like an ON/OFF solenoid 

valve with low speed according to a 

digital input signal.

Med

 represents that ICAD is operating 

the ICM valve like an ON/OFF solenoid 

valve with medium speed according to 

a digital input signal.

High

 represents that ICAD is operating 

the ICM valve like an ON/OFF solenoid 

valve with high speed according to a 

digital input signal. Like below:

Alarms

ICAD can handle and display different 

alarms.

Description

ICM

alarm text Comments

No valve 

type 

selected

A1

At start-up 

A1

 and 

CA

 will be 

displayed

Controller 

fault

A2

Internal fault inside 

electronics

AIl input 

error

A3

Not active if 

¡01

 = 2 or 

¡02

 = 2

When 

¡03

 = 1 and AI A > 22 mA

When 

¡03

 = 2 and AI A > 22 mA

or AI A < 2 mA

When 

¡03

 = 3 and AI A >12 V

When 

¡03

 = 4 and AI A >12 V

or AI A < 1 V

Low voltage 

of fail safe 

supply

A4

If 5 V d.c. < Fail safe supply 

< 18 V d.c.

Check 

Supply to 

ICAD

A5

If supply voltage < 18 V d.c.

If an alarm has been detected the display 

at ICAD (fig. 2) will alternate between 

showing actual alarm and present Opening 

Degree.

If more than one alarm is active at the 

same time only the alarm with the highest 

priority will appear. 

A1

 has the highest 

priority, 

A5

 the lowest.

Any active alarm will activate the Common 

Digital Alarm output (Normally Open).

All alarms will automatically reset them-

selves when they physically disappear.

Old alarms (alarms that have been active, 

but have physically disappeared again) can 

be found in parameter 

¡11

.

Disposal Note

 

The Product contains  

 

electrical components 

  

And may not be 

 

disposed together 

 

with domestic waste. 

Equipment must be separate collected 

with Electrical and Electronic waste. 

According to Local and currently valid 

legislation. 

Summary of Contents for Old ICAD 600 series

Page 1: ... Pieds livre pie 3 2 5 2 5 mm 027R9778 027R9778 Fig Abb 1 Fig Abb 2 Fig Abb 3 Fig Abb 4 ICAD 600 ICAD 900 ICAD 600 ICAD 900 Fig Abb 5a ICM ICAD 600 Fig Abb 5b ICM ICAD 900 mm in Zoll pouces H 45 1 77 L3 25 1 Instruction Aktuator Actuator Stellmotor Actuateur Actuador ICAD 600 ICAD 900 ...

Page 2: ...Terre Tierra E Grå Grey Grau Gris Gris 0 4 20 mA Indgang 0 4 20 mA Input 0 4 20 mA Eingang Entrée 0 4 20 mA Entrada 0 4 20 mA F Lyserød Pink Rosa Rose Rosa 0 2 10 V Indgang 0 2 10 V Input 0 2 10 V Eingang Entrée 0 2 10 V Entrada 0 2 10V G Blå Blue Blau Bleu Azul 0 4 20 mA Udgang 0 4 20 mA Output 0 4 20 mA Ausgang Sortie 0 4 20 mA Salida 0 4 20 mA I Hvid White Weiß Blanc Blanco Nødstrømsforsyning B...

Page 3: ... ON OFF valve operation ICAD 600 900 Digitale E A für EIN AUS Betrieb eines Ventils ICAD 600 900 E S numérique pour marche arrêt de la vanne ICAD 600 900 E S digitales para control todo nada Mellemrelæer Auxiliary relays Hilfsrelais Relais auxiliaires Relés auxiliares Klemmekasse Terminal box Anschlusskasten Boîte à bornes Caja Terminal Fig Abb 8 ICAD ...

Page 4: ...gul jord bruges til spændingsførende indgang V Blå og gul jord bruges til strømførende udgang mA valgfrit ikke obligatorisk Fig 6 Digital styring 7 trådskabel A G ON OFF ICM magnetventilsstyring ICM ventil styret ved hjælp af en spændingsfri digital kontakt Tilslut digitale indgangssignaler fig 8 Se Parameterliste for konfiguration af digitale indgangssignaler Lyserød og gul jord forbindes til en ...

Page 5: ...ntil ved lav hastighed i henhold til et digitalt indgangssignal Med betyder at ICAD driver ICM ventilen som en ON OFF magnetventil ved mellemhøj hastighed i henhold til et digitalt indgangssignal High betyder at ICAD driver ICM ventilen som en ON OFF magnetventil ved høj hastighed i henhold til et digitalt indgangssignal Som vist nedenfor Alarmer ICAD kan afhjælpe og vise forskellige alarmer Beskr...

Page 6: ... 1 2 1 Definer funktion når DI er ON kortsluttede DI terminaler hvis 02 2 1 Åbn ICM ventilen DI OFF Luk ICM ventilen 2 Luk ICM ventilen DI OFF Åbn ICM ventilen Password 10 0 199 0 Indtast tal for at få adgang til parametre beskyttet med password 26 Password 11 Gamle alarmer 11 A1 A99 En liste med gamle alarmer vises Den sidst fremkomne står først Alarmlisten kan nulstilles ved at trykke på piletas...

Page 7: ...A output optional not mandatory Fig 6 Digital operation 7 wired cable A G ON OFF ICM solenoid valve operation ICM valve to be controlled by means of a digital voltfree contact Connect digital input signals fig 8 See Parameter list for configuration of digital input signals Pink and Yellow GND are connected to a voltfree contact Digital output signals are optional not mandatory White and Yellow GND...

Page 8: ...an ON OFF solenoid valve with low speed according to a digital input signal Med represents that ICAD is operating the ICM valve like an ON OFF solenoid valve with medium speed according to a digital input signal High represents that ICAD is operating the ICM valve like an ON OFF solenoid valve with high speed according to a digital input signal Like below Alarms ICAD can handle and display differe...

Page 9: ...put function 09 1 2 1 Define function when DI is ON short circuited DI terminals when 02 2 1 Open ICM valve DI OFF Close ICM valve 2 Close ICM valve DI OFF Open ICM valve Password 10 0 199 0 Enter number to access password protected parameters 26 Password 11 Old Alarms 11 A1 A99 Old alarms will be listed with the latest shown first Alarm list can be reset by means of activating down arrow and up a...

Page 10: ...7 adriges Kabel A G EIN AUS Betrieb des ICM Magnetventils ICM Ventil mittels digitalem potenzialfreiem Kontakt zu steuern Digitale Eingangssignale anschließen Abb 8 Siehe Parameterliste zur Konfiguration der digitalen Eingangs signale Rosa und Gelb GND werden an einen potenzialfreien Kontakt ange schlossen Digitale Ausgangssignale sind optional nicht obligatorisch Weiß und Gelb GND werden an ein H...

Page 11: ...gemäß einem digitalen Eingangssignal betätigt Med zeigt an dass der ICAD das ICM Ventil wie ein EIN AUS Magnetventil mit mittlerer Geschwindigkeit gemäß einem digitalen Eingangssignal betätigt High zeigt an dass ICAD das ICM Ventil wie ein EIN AUS Magnetventil mit hoher Geschwindigkeit gemäß einem digitalen Eingangssignal betätigt Siehe dazu beispielsweise unten Alarme ICAD kann verschiedene Alarm...

Page 12: ...en OD einnehmen Digitaleingangsfunktion 09 1 2 1 Funktion festlegen wenn DI auf EIN steht kurzgeschlossene DI Klemmen bei 02 2 1 ICM Ventil öffnen DI OFF ICM Ventil schließen 2 ICM Ventil schließen DI OFF ICM Ventil öffnen Kennwort 10 0 199 0 Nummer eingeben um auf kennwortgeschützte Parameter Zugriff zu erhalten 26 Kennwort 11 Alte Alarme 11 A1 A99 Alte Alarme werden mit dem ältesten zuerst aufge...

Page 13: ... mA en option facultatif Fig 6 Fonctionnement numérique Câble à 7 fils A G Fonctionnement marche arrêt de l électrovanne ICM Vanne ICM commandé par un contact numérique libre de potentiel Raccorder les signaux d entrée numériques fig 8 Voir la Liste des paramètres pour configurer les signaux d entrée numériques La borne rose et la borne jaune terre sont raccordées à un contact libre de potentiel L...

Page 14: ...électrovanne marche arrêt à basse vitesse en fonction d un signal d entrée numérique Med signifie que l ICAD fait fonctionner la vanne ICM comme une électrovanne marche arrêt à vitesse moyenne en fonction d un signal d entrée numérique High signifie que l ICAD fait fonctionner la vanne ICM comme une électrovanne marche arrêt à haute vitesse en fonction d un signal d entrée numérique Voir ci après ...

Page 15: ...est sur On terminaux entrée numérique court circuités et 02 2 1 Ouvrir la vanne ICM DI entrée numérique OFF Arrêt Fermer la vanne ICM 2 Fermer la vanne ICM DI entrée numérique OFF Arrêt Ouvrir la vanne ICM Mot de passe 10 0 199 0 Saisir le nombre qui permet d accéder aux paramètres protégés par un mot de passe 26 Mot de passe 11 Anciennes alarmes 11 A1 A99 Les anciennes alarmes sont répertoriées a...

Page 16: ... de entrada analógicas Intensidad mA o tensión V Ver la lista de parámetros para la configuración de las señales de entrada analógicas Los cables gris y amarillo Tierra se emplean para la entrada de intensidad mA Ó El cable rosa y amarillo tierra se usan para entrada de tensión V El cable azul y amarillo tierra se usan para la salida de intensidad mA opcional Fig 6 Funcionamiento todo nada 7 cable...

Page 17: ... que el ICAD posiciona la válvula ICM en función de una señal de entrada analógica Intensidad y tensión Low sigifica que el ICAD controla la válvula ICM en modo todo nada a baja velocidad en función de una entrada digital Med sigifica que el ICAD controla la válvula ICM en modo todo nada a media velocidad en función de una entrada digital High sigifica que el ICAD controla la válvula ICM en modo t...

Page 18: ... 09 1 2 1 Defina la función al estar la entrada ON conectados los terminales cuando 02 2 1 Abre la válvula ICM DI OFF Cierra la ICM 2 Cierra la válvula ICM DI OFF Abre la ICM Contraseña 10 0 199 0 Introduce un número para acceder a los parámetros protegidos por contraseña 26 Contraseña 11 Alarmas antiguas 11 A1 A99 Se presenta una lista de antiguas alarmas siendo la primera la más reciente El list...

Page 19: ... Danfoss A S AC AKC frz 10 2007 DKRCI PI HV0 A1 53 520H0546 19 ...

Page 20: ...ow mention directives standards or other normative documents provided it is used according to our instructions Description of Equipment Actuator for ICM valves Type ICAD 600 ICAD 900 Declaration of Conformity Authorised Person for the Manufacturer within the European Community Name Michael Breumsoe Title Production Manager Signature Date 02 11 2005 References of other Technical Standards and Speci...

Reviews: