Design Guide | APP and iSave overload protection
61
180R9357 | AQ265943679828en-00100
2
IOM iSave 50 - 70 | 0
3
.202
3
4.
Examples of VLT
overload limit settings
Below is two examples of how to calculate the
torque limit settings for an APP pump.
All calculations are made in the Danfoss HPP
calculation tool (please contact Danfoss HPP for
help).
Example 1:
Settings are made according to actual operating
pressure (see graph #2 in chapeter 2.1).
Example 2:
Settings are made according to maximum
allowable operating pressure (see graph #1 in
chapter 2.1)
• 77 m³/h and 60 barg max. operating pressure
• Design pressure 60 barg
√
Calculated
operating torque: 934 Nm at 1,490
rpm and 60 barg.
√ Selected motor:
• 160 kW, 4 pole
• Efficiency: 95.8%
• Power factor (cosφ): 0.87
• Power supply: 400 [V]
• Rated speed: 1,490 rpm
• Max. current: 275 [A]
• Max. operating torque: 1,026 Nm
√ Calculate torque at 20% higher than
934 Nm = > 1,121 Nm
Parameter 4-16 setting = 107%
√ Calculate starting torque at 40% higher than
934 Nm = > 1,308 Nm
Parameter 4-18 setting = 121%
√ Calculated DC-hold: Parameter 2-00 is 49%
√ Selected delay before start
Parameter 1-71 is 4
(see chapter 5.3)
√ Trip delay torque limit:
Parameter 14-25 is 30 sec.
√ Calculated starting current: 334 [A]
√ Calculated operating current at 60 barg:
257 [A]
• 77 m³/h and 60 barg max. operating pressure
• Design pressure 80 barg
√
Calculated
maximum
operating torque:
1,246 Nm at 1,490 rpm and 80 barg.
√ Calculated operatin torque: 934 Nm at 1,490
rpm and 60 barg.
√ Selected motor:
• 200 kW, 4 pole
• Efficiency: 96%
• Power factor (cosφ): 0.88
• Power supply: 400 [V]
• Rated speed: 1,490 rpm
• Max. current: 340 [A]
• Max. operating torque: 1,282 Nm
√ Calculate torque at 20% higher than
934 Nm = > 1,121 Nm
Parameter 4-16 setting = 90%
√ Calculate starting torque at 40% higher than
934 Nm = > 1,308 Nm
Parameter 4-18 setting = 102%
√ Calculated DC-hold:
Parameter 2-00 is 47%
√ Selected delay before start
Parameter 1-71 is 4.5
√ Trip delay torque limit:
Parameter 14-25 is 30 sec.
√ Calculated starting current: 345 [A]
√ Calculated operating current at 60 barg:
271 [A]
Summary of Contents for iSave 50
Page 20: ...Operating guide iSave 50 70 20 180R9357 AQ265943679828en 001002 IOM iSave 50 70 03 2023...
Page 23: ...Data sheet iSave Energy Recovery Device iSave 50 iSave 70 hpp danfoss com...
Page 50: ...Danfoss DCS im 2020 01 180R9213 521B1164 DKCFN PI 003 F8 02 50...
Page 51: ...Design guide Energy Recovery Device iSave Membrane cleaning of RO system hpp danfoss com...
Page 56: ...Danfoss DCS im 2017 09 521B1165 DKCFN PI 00 G6 02 56...
Page 57: ...ro solutions com Design Guide APP pumps and iSave overload protection hpp danfoss com...
Page 66: ...Danfoss DCS im 2018 08 180R9372 521B1412 DKCFN PI 003 O2 02 66...
Page 74: ...Danfoss DCS im 2019 05 180R9084 521B0540 DKCFN PI 000 D7 02 74...
Page 75: ...Parts list Energy recovery device iSave 50 70 hpp danfoss com...
Page 86: ...86 Danfoss DCS im 2021 03 180R9392_AX299849991270en 000701...
Page 87: ...M a n u a l Electric Motors Motor Manual hoyermotors com...
Page 91: ...91 180R9357 AQ265943679828en 001002 IOM iSave 50 70 03 2023...