HLP-V  Series

4

 Safety regulations

1. The frequency converter must be disconnected

from mains if repair work is to be carried out. Check

that the mains supply has been disconnected and

that the necessary time has passed before remov-

ing motor and mains plugs.

2. The [STOP/RESET] key on the control panel of

the frequency converter does not disconnect the

equipment from mains and is thus not to be used

as a safety switch.

3. Correct protective earthing of the equipment must

be established, the user must be protected against

supply voltage, and the motor must be protected

against overload in accordance with applicable na-

tional and local regulations.

4. The earth leakage currents are higher than 3.5

mA.

5. Protection against motor overload is not included

in the factory setting. If this function is desired,

set parameter 128 to data value 

ETR trip 

or data

value 

ETR warning

.

Note: The function is initialised at 1.16 x rated

motor current and rated motor frequency. For the

North American market: The ETR functions pro-

vide class 20 motor overload protection in accor-

dance with NEC.

6. Do not remove the plugs for the motor and main

supply while the frequency converter is connected

to mains. Check that the mains supply has been

disconnected and that the necessary time has ex-

pired before removing motor and mains plugs.

7. Please note that the frequency converter has more

voltage   inp uts  than  L1,  L2  a nd  L 3,  w hen

loadsharing (linking of DC intermediate circuit) and

external 24 V DC have been installed.

Check that all voltage inputs have been discon-

nected and that the necessary time has passed

before repair work is commenced.

 Warning against unintended start

1. The motor can be brought to a stop by means of

digital commands, bus commands, references or

a local stop, while the adjustable frequency drive

is connected to the AC line. These stop functions

are NOT sufficient to ensure that no unintended

start occures and should NOT be used for per-

sonal safety considerations.

2. While parameters are being changed, the motor

may start. Consequently, the stop key 

Stop/Re-

set

 must always be activated, following which data

can be modified.

3. A motor that has been stopped may start if faults

occur in the electronics of the adjustable frequency

drive, or if a temporary overload or a fault in the

AC line supply or the motor connection ceases.

 Installation of mechanical brake

Do not connect a mechanical brake to the output

from the frequency converter before the relevant

parameters for brake control are parameterised.

(Selection of output in parameter 319, 321, 323 or

326 and cut-in current and frequency in param-

eter 223 and 225).

 Use on isolated AC line

See section 

RFI Switch 

regarding use on isolated

AC line.

It is important to follow the recommendations re-

garding installation on IT line, since sufficient pro-

tection  of   the  complete  installation  must  be

observed. Not taking care using relevant monitor-

ing devices for IT line supply may result in damage.

Summary of Contents for Holip HLP-V Series

Page 1: ......

Page 2: ...nstallation of motor cables 23 Connection of motor 23 Direction of motor rotation 23 Electrical installation brake cable 24 Electrical installation relay outputs 24 Electrical installation 24 Volt ext...

Page 3: ...ences and limits 59 Parameters Inputs and outputs 68 Special functions 84 Parameters Serial communication 100 Parameters Technical functions and diagnostics 108 Messages 115 Trouble shooting 115 Displ...

Page 4: ...l installation Improper instal lation of the motor or the Holip may cause equipment failure serious injury or death Follow this manual and National Electri cal Codes and local safety codes NOTE Electr...

Page 5: ...e inputs than L1 L2 and L3 when loadsharing linking of DC intermediate circuit and external 24 V DC have been installed Check that all voltage inputs have been discon nected and that the necessary tim...

Page 6: ...LP V Series 5 HLP V series namelate explanation MODEL HLPV4040EBC3DV10 INPUT 3PH380 440V 50 60Hz OUTPUT 3PH380 440V 61A 73A 55 6KVA Freq Range 0 1000Hz HOLIP ELECTRONIC TECHNOLOGY CO LTD Technical dat...

Page 7: ...output Unlimited Ramp times 0 05 3600 sec Torque characteristics Starting torque HLP V 4015 4550V 160 for 1 min Starting torque 180 for 0 5 sec Acceleration torque 100 Overload torque HLP V 4015 4550...

Page 8: ...e level 0 24 V DC PNP positive logics Voltage level logical 0 5 V DC Voltage level logical 1 10 V DC Maximum voltage on input 28 V DC Input resistance Ri 2 k Scanning time per input 3 msec Resolution...

Page 9: ...trol card 50 V AC 1 A 50 VA Max terminal load DC1 on 4 5 control card 25 V DC 2 A 50 V DC 1 A 50 W Max terminal load DC1 on 4 5 control card for UL cUL applications 30 V AC 1 A 42 5 V DC 1A Terminal n...

Page 10: ...pm max error 7 5 rpm Speed accuracy closed loop 1500 rpm max error 1 5 rpm Torque control accuracy open loop 0 150 rpm max error 20 of rated torque Torque control accuracy speed feedback Max error 5 o...