HLP-C
+
Inverters
The following diagram shows the factory standard connection of
Model HLP-C
+
(4) Precautions on Wiring
a
:
For main circuit wiring:
● While wiring the sizes and specifications of wires should be
selected and the wiring should be executed according to the
electrical engineering regulations to ensure the safety.
● It is better to use shield wire or wire and tube for power cord
and ground the shield layer or two ends of wire tube.
● Be sure to install a No Fuse Breaker (NFB) between the power
supply and the input terminals (R.S.T). (If using ground fault
circuit interrupter, please choose the one corresponding to
high frequency)
● The power line and the control line should be arranged
separately and should not be laid in the same ducts..
● Never connect AC power to the output terminals (U.V.W) of
the inverter.
● Output wires mustn’t be in touch of the metal part of the outer
cover, or it will cause earth short-circuit.
● Phase-shifting capacitor, LC, RC noise filters, etc, can never