User Guide 

FP720 Two Channel Heating Timer

Danfoss Heating

 

VUSUH102 | BC306937065292EN-000101

 05/2019 

Select Away Mode

•  Press 

CH for 3 seconds

 to enter Away mode and 

 will be displayed.

•  Press 

CH

 again to exit Away mode.

Set Control Parameters

Press   

   button for 6 seconds to enter the parameter setting mode. Press   

   for parameter selection and 

set the parameter range via 

<

 or 

>

. Complete all adjustments.

To exit parameter setup press   

   , automatic exit after 20 seconds in no button is pressed.

No.

Parameter settings

Settings range

Default

P1

Working mode

01: Schedule timer 7 day

02: Schedule timer 5/2 day

03: Schedule timer 24hr

02

P2

Schedule periods

01: 1 period (2 events)

02: 2 periods (4 events)

03: 3 periods (6 events)

02

P3

Channel setup

01: H Domestic hot water

02: Two heating zones

01

P4

Timer display

01: 24hr

02: 12hr

01

P5

Auto daylight saving

01: On

02: Off

01

P6

Holiday mode setup

01: All channels off

02: Heating off only

01

P7

Service due setup

Installer setting only

P8

Reset

00: Reset off

01: Select reset

00