| 16
DKRCE.PI.RL0.H7.ML
Installation Guide | ERC 214
Parameter name - ERC 214
Code
Min
Max
Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Alarm
A--
Delay for temperature alarm
during normal conditions
A03
0
240
min
30
45
30
30
30
30
30
Delay for temperature alarm
during pull-down/start-up/defrost
A12
0
240
min
60
90
60
60
60
60
60
High temperature alarm limit
(Cabinet/Room)
A13
-100.0
200.0
C/F
8.0
10.0
8.0
-15.0
8.0
-15.0
8.0
Low temperature alarm limit
A14
-100.0
200.0
C/F
-30.0
0.0
-2.0
-30.0
-2.0
-30.0
-30.0
DI1 delay
(time delay for selected DI1 function)
A27
0
240
min
30
30
30
30
30
30
30
DI2 delay
(time delay for selected DI2 function)
A28
0
240
min
30
30
30
30
30
30
30
Condenser high alarm limit
A37
0
200
C/F
80
80
80
80
80
80
-
Condenser high block limit
A54
0
200
C/F
85
85
85
85
85
85
-
Voltage protection enable
A72
no
yES
no
no
no
no
no
no
no
Minimum cut-in voltage
A73
0
270
V
0
0
0
0
0
0
0
Minimum cut-out voltage
A74
0
270
V
0
0
0
0
0
0
0
Maximum voltage
A75
0
270
V
270
270
270
270
270
270
270
Defrost
d--
Defrost method
no=no defrost, nAt=natural,
EL=electrical, gAS=hot gas
d01
no
gAS
EL
nAt
EL
EL
EL
EL
EL
Defrost stop temperature
d02
0.0
50.0
C/F
6.0
-
-
-
6.0
6.0
6.0
Defrost interval
d03
0
240
hours
8
6
8
12
8
12
8
Max defrost time
d04
0
480
min
30
45
15
15
30
30
30
Defrost delay at power up
(or DI signal)
d05
0
240.0
min
0
0
0
0
0
0
-
Drip delay
d06
0
60
min
0
0
0
0
0
0
5
Fan delay after defrost
d07
0
60
min
0
0
0
0
0
0
5
Fan start temperature
after defrost
d08
-50.0
0.0
C/F
-5.0
-
-
-
-5.0
-5.0
-
Fan during defrost
d09
oFF
on
on
on
on
on
on
on
on
Note: hidden parameters are greyed out
ENGLISH
Summary of Contents for ERC 214
Page 1: ...Installation Guide ERC 214 Digital controller for refrigeration and defrost 4 relays...
Page 64: ...64 DKRCE PI RL0 H7 ML Installation Guide ERC 214 6 DEFROST 3 DEFROST 3 DEFROST SET UP DOWN SET...
Page 148: ...148 DKRCE PI RL0 H7 ML Installation Guide ERC 214 Notes...
Page 149: ...149 DKRCE PI RL0 H7 ML Installation Guide ERC 214 Notes...
Page 150: ...150 DKRCE PI RL0 H7 ML Installation Guide ERC 214 Notes...
Page 151: ...151 DKRCE PI RL0 H7 ML Installation Guide ERC 214 Notes...