Installation guide | ERC 213

Installation guide - ERC 213

EU design registration

Safety standards

Check the input voltage is correct before connecting the instrument.
Do not expose to water or damp: only use the regulator within the design operating limits, avoiding sudden temperature 
changes with high atmospheric humidity to prevent condensate forming.

Product disposal

The device (or product) must be disposed of in compliance with local waste disposal legislation.

002566703-0001

Parameter Name - ERC 213

Code

Min

Max

Unit

App. 0

(Def.)

App. 1 App. 2 App. 3 App. 4 App. 5 App. 6

Readouts

u--

Controller Status 

S0=cooling ON/Heating ON, 
S2=wait for compressor ON time to 
elapse, S3=wait for compressor OFF 
time to elapse-restart time, S4=drip 
OFF delay after defrost, 
S10=cooling stop S11=cooling 
stopped by thermostat / heating OFF, 
S14=defrosting state, 
S15=fan delay state after defrost, 
S17=door open (DI input), 
S20=emergency cooling, S25=manual 
control of outputs, 
S30=continous cycle / Pull-down, 
S32=delay of outputs at power up

u00

S0

S32

--

Air temperature (Sair)

u01

-100.0

200.0

C/F

---

Read the present regulation 
reference

u02

-100.0

200.0

C/F

---

Defrost temperature (S5)

u09

-100.0

200.0

C/F

---

-

-

-

DI1 input

u10

oFF

on

---

Status of night operation

u13

oFF

on

---

DI2 input

u37

oFF

on

---

Condenser temperature (Sc)

U09

-100.0

200.0

C/F

---

Compressor relay status

u58

oFF

on

---

Fan relay status

u59

oFF

on

---

Defrost relay status

u60

oFF

on

---

Light relay status

u63

oFF

on

---

Firmware version readout

u80

000

999

---

Alarm status

Sair air temperature sensor error

E29

S5 defrost sensor error

E27

Sc condenser sensor error

E30

High temperature alarm

A01

Low temperature alarm

A02

High voltage alarm

A99

Low voltage alarm

AA1

Condenser alarm

A61

Door alarm

A04

Standby alarm

A45

DI external alarm

A15

N.B.: hidden parameters are greyed out

Summary of Contents for ERC 213

Page 1: ...X 5V Danfoss 80G8136 02 Programming key EKA 183B Electrical input on the basis of product code Installation guide ERC 213 Digital regulator for refrigeration and defrosting 3 relays Rear mount clip fixing Drilling template Dimensions mm Assembly Wiring diagram The ERC 213 is a smart multipurpose refrigeration controller with temperature and defrost management available with 3 relays The controller...

Page 2: ...irm The regulator presets the parameter values on the basis of the application selected and hides any irrelevant parameters Tip you can easily switch from AP0 to AP6 and therefore select the simplified parameters list by pressing the UP button circular list STEP 4 Select the sensor type o06 The display automatically shows the sensor selection parameter o06 Press SET to select the type of sensor Th...

Page 3: ...l the parameter groups To scroll the parameter names 5 Quick configuration with cFg menu Press SET for three seconds to open the parameter groups Select the cFg menu and press SET to open The first menu r12 main switch is displayed Set the main switch to OFF r12 0 to change the preinstalled application Press UP DOWN to scroll through the parameters list Configure the parameter o61 to select a prei...

Page 4: ...ved The alarm bell is shown After 5 minutes of inactivity the keypad will be locked if P76 YES When the keypad is locked if any key is selected LoC appears on the display Press UP and DOWN buttons simultaneously for 3 seconds to unlock the keyboard unl is displayed for 3 seconds SET saves the temperature setpoint 7 Default application settings App Mode Description Temp Def type Def end App 0 Cooli...

Page 5: ...105 C 40 221 F Controller accuracy 1 K below 35 C 0 5 K between 35 25 C 1 K above 25 C Output Compressor relay DO1 16 A 16 16 A EN 60730 10 FLA 60 LRA at 230 V UL60730 16 FLA 72 LRA at 115 V UL60730 Defrosting relay DO2 8 A 2 FLA 12 LRA UL60730 8 A 2 2 A EN60730 Fan relay DO3 3 A 2 FLA 12 LRA UL60730 3 A 2 2 A EN60730 Display LED 3 figure display decimal point and multifunction icons C F scale Ope...

Page 6: ... 0 0 0 0 0 0 0 0 0 Thermostat reference displacement offset temperature r40 50 0 50 0 K 0 0 0 0 0 0 0 0 0 0 0 0 Pull down duration r96 0 960 min 0 0 0 0 0 0 Pull down limit temperature r97 100 0 200 0 C F 0 0 0 0 0 0 0 0 0 0 0 0 Alarm A Delay for temperature alarm during normal conditions A03 0 240 min 30 45 30 30 30 30 30 Delay for temperature alarm during pull down start up defrost A12 0 240 min...

Page 7: ...FAo FAo FAo FAo FAo FAo FAo Fan stop evaporator temperature 50 0 OFF F04 50 0 50 0 C F 50 0 50 0 50 0 Fan ON cycle F07 0 15 min 2 2 2 2 2 2 2 Fan OFF cycle F08 0 15 0 min 2 2 2 2 2 2 2 Compressor c Compressor minimum ON time C01 0 30 min 0 0 0 0 0 0 0 Compressor minimum OFF time C02 0 30 min 2 2 2 2 2 2 2 Compressor OFF delay at door open C04 0 15 min 0 0 0 0 0 0 1 Zero crossing selection C70 no y...

Page 8: ...arm dEF defrost Pud pull down o37 oFF Pud oFF oFF oFF oFF oFF oFF oFF Predefined applications o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 Save settings as factory WARNING the earlier factory settings are overwritten o67 no yES no no no no no no DO2 config dEF defrost ALA alarm o71 dEF ALA dEF ALA dEF dEF dEF dEF dEF Display at defrost Air actual air temperature FrE freezed temperature d d is displayed o91...

Page 9: ...Name ERC 213 Code Min Max Unit App 0 Def App 1 App 2 App 3 App 4 App 5 App 6 Readouts u Controller Status S0 cooling ON Heating ON S2 wait for compressor ON time to elapse S3 wait for compressor OFF time to elapse restart time S4 drip OFF delay after defrost S10 cooling stop S11 cooling stopped by thermostat heating OFF S14 defrosting state S15 fandelaystateafterdefrost S17 door open DI input S20 ...

Reviews: