Danfoss ERC 213 Installation Manual Download Page 2

DKRCE.PI.RL0.O2.02 / 520H11062 | 2

© Copyright Danfoss | Published by AZ | 2016.04

Installation guide | ERC 213

Installation guide - ERC 213

1 - Technical features

2 - User interface

3 - Quick-start configuration

•   Easy to use

: the four buttons, the easy-to-read menu structure and the preinstalled application solutions guarantee 

optimal usability.

•   Simple  installation

: the 16 A relay means heavy loads can be connected directly without having to use an intermediate 

relay: compressors up to 2 HP on the basis of the power factor and efficiency of the motor (over 0.65 at 230 V and over 0.85 
at 115 V). A vast range of compatible sensor types and screw terminals guarantee highly flexible installation.

•   Unit  protection

: special software functions, protecting the compressor from voltage fluctuations or high condensation 

temperature, to guarantee optimal unit performance.

•   Energy  efficiency

: defrosting on request, day/night mode and intelligent evaporator fan management guarantee 

maximum energy efficiency.

•  STEP 1: Startup
•  STEP 2: Select quick-start configuration menu

 

  Within 30 seconds of startup, press “

<

” BACK for 3 seconds. 

  The main switch “

r12

” is automatically set to OFF.

•  STEP 3: Select the preinstalled application “

o61

 

  The display automatically shows the application selection parameter “

o61

”. 

  Press SET to select the preinstalled application. 
  The display shows the default value (for example “

AP0

”, blinking). 

  Select the type of application by pressing UP/DOWN and then SET to confirm. 
   The regulator presets the parameter values on the basis of the application selected and hides any irrelevant parameters. 

Tip: you can easily switch from AP0 to AP6 and therefore select the simplified parameters list by pressing the UP button 
(circular list).

•  STEP 4: Select the sensor type “

o06

 

  The display automatically shows the sensor selection parameter “

o06

”. 

  Press SET to select the type of sensor. 
  The display shows the default value (for example “

n10

”, blinking). 

   Select the type of sensor by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) then SET to confirm. 

NOTE: all the sensors must by the same type.

App

Description

App 0

None (no preset application)

App 1

Medium temperature ventilated refrigeration units (2 – 6 °C), with timed natural defrost

App 2

Medium temperature ventilated refrigeration units (0 – 4 °C), with timed electrical defrost

App 3

Low temperature ventilated refrigeration units (-26 – -20 °C), with timed electrical defrost

App 4

Medium temperature ventilated refrigeration units (0 – 4 °C), with electrical defrost (by temperature)

App 5

Low temperature ventilated refrigeration units (-26 – -20 °C), with electrical defrost (by temperature)

App 6

None (no preset application) with simplified parameter list

Button function

Press and hold down on startup
RESET FACTORY SETTINGS (“FAC” is displayed)

Press for one second: 

BACK

Press and hold down: 

PULL-DOWN

Press for one second: 

UP

Press and hold down: 

ON/OFF

Press for one second: 

TEMPERATURE SETPOINT/OK

Press and hold down: 

MENU

Press for one second: 

DOWN

Press and hold down: 

DEFROSTING

Display icons

Night mode (energy saving)

Fan on

Defrosting

Compressor on
Blinks in pull-down mode

Alarm activated

Units (°C or °F)

Summary of Contents for ERC 213

Page 1: ...X 5V Danfoss 80G8136 02 Programming key EKA 183B Electrical input on the basis of product code Installation guide ERC 213 Digital regulator for refrigeration and defrosting 3 relays Rear mount clip fixing Drilling template Dimensions mm Assembly Wiring diagram The ERC 213 is a smart multipurpose refrigeration controller with temperature and defrost management available with 3 relays The controller...

Page 2: ...irm The regulator presets the parameter values on the basis of the application selected and hides any irrelevant parameters Tip you can easily switch from AP0 to AP6 and therefore select the simplified parameters list by pressing the UP button circular list STEP 4 Select the sensor type o06 The display automatically shows the sensor selection parameter o06 Press SET to select the type of sensor Th...

Page 3: ...l the parameter groups To scroll the parameter names 5 Quick configuration with cFg menu Press SET for three seconds to open the parameter groups Select the cFg menu and press SET to open The first menu r12 main switch is displayed Set the main switch to OFF r12 0 to change the preinstalled application Press UP DOWN to scroll through the parameters list Configure the parameter o61 to select a prei...

Page 4: ...ved The alarm bell is shown After 5 minutes of inactivity the keypad will be locked if P76 YES When the keypad is locked if any key is selected LoC appears on the display Press UP and DOWN buttons simultaneously for 3 seconds to unlock the keyboard unl is displayed for 3 seconds SET saves the temperature setpoint 7 Default application settings App Mode Description Temp Def type Def end App 0 Cooli...

Page 5: ...105 C 40 221 F Controller accuracy 1 K below 35 C 0 5 K between 35 25 C 1 K above 25 C Output Compressor relay DO1 16 A 16 16 A EN 60730 10 FLA 60 LRA at 230 V UL60730 16 FLA 72 LRA at 115 V UL60730 Defrosting relay DO2 8 A 2 FLA 12 LRA UL60730 8 A 2 2 A EN60730 Fan relay DO3 3 A 2 FLA 12 LRA UL60730 3 A 2 2 A EN60730 Display LED 3 figure display decimal point and multifunction icons C F scale Ope...

Page 6: ... 0 0 0 0 0 0 0 0 0 Thermostat reference displacement offset temperature r40 50 0 50 0 K 0 0 0 0 0 0 0 0 0 0 0 0 Pull down duration r96 0 960 min 0 0 0 0 0 0 Pull down limit temperature r97 100 0 200 0 C F 0 0 0 0 0 0 0 0 0 0 0 0 Alarm A Delay for temperature alarm during normal conditions A03 0 240 min 30 45 30 30 30 30 30 Delay for temperature alarm during pull down start up defrost A12 0 240 min...

Page 7: ...FAo FAo FAo FAo FAo FAo FAo Fan stop evaporator temperature 50 0 OFF F04 50 0 50 0 C F 50 0 50 0 50 0 Fan ON cycle F07 0 15 min 2 2 2 2 2 2 2 Fan OFF cycle F08 0 15 0 min 2 2 2 2 2 2 2 Compressor c Compressor minimum ON time C01 0 30 min 0 0 0 0 0 0 0 Compressor minimum OFF time C02 0 30 min 2 2 2 2 2 2 2 Compressor OFF delay at door open C04 0 15 min 0 0 0 0 0 0 1 Zero crossing selection C70 no y...

Page 8: ...arm dEF defrost Pud pull down o37 oFF Pud oFF oFF oFF oFF oFF oFF oFF Predefined applications o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 Save settings as factory WARNING the earlier factory settings are overwritten o67 no yES no no no no no no DO2 config dEF defrost ALA alarm o71 dEF ALA dEF ALA dEF dEF dEF dEF dEF Display at defrost Air actual air temperature FrE freezed temperature d d is displayed o91...

Page 9: ...Name ERC 213 Code Min Max Unit App 0 Def App 1 App 2 App 3 App 4 App 5 App 6 Readouts u Controller Status S0 cooling ON Heating ON S2 wait for compressor ON time to elapse S3 wait for compressor OFF time to elapse restart time S4 drip OFF delay after defrost S10 cooling stop S11 cooling stopped by thermostat heating OFF S14 defrosting state S15 fandelaystateafterdefrost S17 door open DI input S20 ...

Reviews: