Reference manual RS8ED102 © Danfoss 03-2006
EKC 316A
Alarms
Symptom
Possible Cause
Fault Message
Remedy
All Light emitting diodes
flashing
S2 sensor cut-out.
E15
Check connections at terminals 18-19 and
sensor.
S2 sensor short-circuited
E16
Check connections at terminals 18-19 and
sensor.
S3 sensor cut-out
E17
Check connections at terminals 18-20 and
sensor.
S3 sensor short-circuited
E18
Check connections at terminals 18-20 and
sensor.
Analogue input outside range.
E19
Pressure transmitter outside
range.
E20
Check pressure transmitter, connections at
14-15 and pressure.
High Temperature alarm
A1
Check cooling is effective. Check thermo-
stat relay at terminals 8-9
Low Temperature alarm
A2
Check ETS valve is full open and relay at
terminals 8-9
No refrigerant selected
A11
Select refrigerant
Supply to stepper motor
A43
Check connections from EKC316A to ETS
valve.
Battery alarm
A44
Check the battery voltage is the nominal
voltage.
Notes:
1) Only one alarm is displayed at a time in the controller display
and are shown in the order given above i.e. E15 will be dis-
played if S2 is not connected. If S2 is connected successfully
then the next alarm will be E17 if S3 is not connected. All alarms
are displayed in the AKM system.
2) The alarm E19 will only be active if address o10 is set to 1 or
more.
3) The alarm E17 and E18 will be only active if the Therm.Mode ad-
dress r14 is set to 1 or Reg.type address o56 is set to 3.
4) The battery alarm A44 is only active when Batt.alarm address
A34 is set to ON.