Reference manual  RS8ED102  ©  Danfoss  03-2006 

EKC 316A

Alarms

Symptom

Possible Cause

Fault Message

Remedy

All Light emitting diodes 
flashing

S2 sensor cut-out.

E15

Check connections at terminals 18-19 and 
sensor.

S2 sensor short-circuited

E16

Check connections at terminals 18-19 and 
sensor.

S3 sensor cut-out

E17

Check connections at terminals 18-20 and 
sensor.

S3 sensor short-circuited

E18

Check connections at terminals 18-20 and 
sensor.

Analogue input outside range.

E19

Pressure transmitter outside 
range.

E20

Check pressure transmitter, connections at 
14-15 and pressure.

High Temperature alarm

A1

Check cooling is effective. Check thermo-
stat relay at terminals 8-9

Low Temperature alarm

A2

Check ETS valve is full open and relay at 
terminals 8-9

No refrigerant selected

A11

Select refrigerant

Supply to stepper motor

A43

Check connections from EKC316A to ETS 
valve.

Battery alarm

A44

Check the battery voltage is the nominal 
voltage.

Notes:

1) Only one alarm is displayed at a time in the controller display 

and are shown in the order given above i.e. E15 will be dis-
played if S2 is not connected. If S2 is connected successfully 
then the next alarm will be E17 if S3 is not connected. All alarms 
are displayed in the AKM system.

2) The alarm E19 will only be active if address o10 is set to 1 or 

more.

3) The alarm E17 and E18 will be only active if the Therm.Mode ad-

dress r14 is set to 1 or Reg.type address o56 is set to 3.

4) The battery alarm A44 is only active when Batt.alarm address 

A34 is set to ON.

Summary of Contents for EKC 316A

Page 1: ...REFRIGERATION AND AIR CONDITIONING Controller for operation of evaporator on water chiller EKC 316A Reference manual...

Page 2: ...an extern analogue signal 11 Operating the valve manually by an extern analogue signal with MOP active 11 Battery back up 13 Troubleshooting 13 Alarms 14 References 15 Installation The EKC 316A is nor...

Page 3: ...following checks can be made to the connec tion between the EKC316A controller and the stepper motor of the ETS valve 1 With the power o check that resistance between terminals 21 and 22 and terminal...

Page 4: ...essor o30 Refrigerant ETS Valve type Each ETS valve has a speci ed number of steps as given below Total steps ETS 50 2625 160 0 steps ETS 100 3530 160 0 steps ETS 250 and 400 3810 160 0 steps The para...

Page 5: ...n more capacity is required NO function n41 Valve type Menu Danfoss only Compensation direction 1 Compensation takes place when the valve opens normal setting 2 Compensation takes place when the valve...

Page 6: ...l opening degree dependant on the Kp factor the measured superheat SH and SH closes as given in the following relationship Initial OD kp factor SH SH close The regulation modes for controlling superhe...

Page 7: ...alve is that there are three settings to de ne the operating curve Problems of start up Sometimes in one to one applications the valve does not open su ciently on start up and troublesome low pressure...

Page 8: ...ontrol Refrigerant Temp S2 Superheat Ref SHref Superheat S2 S1 ETS Valve Evaporator Kp factor and Tn settings Instability cause by too much Proportional Gain can be corrected by reducing to value of t...

Page 9: ...Evaporator ETS Valve PI Control S3 S1 Kp factor and Tn settings KpT0 and Tn T0 settings The feedback of the inner loop is temperature di erence between media temperature S3 and S1 This value represen...

Page 10: ...wer response of the media temperature NOTE The settings Atten factor address n43 and Min Lim Ref address n45 should not be changed without the help of trained sta The S3 sensor has to be connected whe...

Page 11: ...signal connected to terminals 16 and 17 of the controller This can be done by setting parameter o18 to 4 for 0 to 20 mA signal or 5 for 4 to 20 mA signal The analogue input 0 or 4 mA will correspond...

Page 12: ...signal can be used when o10 is set to 6 When the sections 1 and 2 are active the function in section 2 will choose the lowest value of OD that comes from either sections 1 or the PI Control This mean...

Page 13: ...placed much higher than condenser outlet check pressure di er ence Evaporator superheat too high 1 Check superheat performance the set tings SH min and SH max 2 Check valve capacity 3 Check that the...

Page 14: ...terminals 8 9 Low Temperature alarm A2 Check ETS valve is full open and relay at terminals 8 9 No refrigerant selected A11 Select refrigerant Supply to stepper motor A43 Check connections from EKC316A...

Page 15: ...8ED102 Danfoss 03 2006 15 References 1 Controller for operation of evaporator on water chillers EKC316A Manual RS8CX502 2 Electrically operated expansion valves type ETS ETS Technical Lea et DKRCC PD...

Page 16: ...reserves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in spec...

Reviews: