Reference manual  RS8ED102  ©  Danfoss  03-2006 

EKC 316A

Basic Settings

Before using the EKC 316A controller, there are settings that 
have to be made for each individual application. These are the 
refrigerant type, the pressure transducer range and the total 
number of steps for the ETS valve. It is good practice and some 
cases necessary to set the Main Switch r12 to OFF when making 
these changes. 

Refrigerant Type.

It is possible to choose from a list of 28 different refrigerants in the 
controller. If refrigerant is not found on the list, it is possible using 
AKM and setting o30 to 13 to plug in the Antione constants for the 
unlisted refrigerant.

Setting and checks to be made before 
start

Refrigerant setting

Before refrigeration can be started, the refrigerant must be defined. You can select the 
following refrigerants:
1=R12.  2=R22.  3=R134a.  4=R502.  5=R717.  6=R13.  7=R13b1.  8=R23.  9=R500.  
10=R503.  11=R114.  12=R142b. 13=User defined. 14=R32. 15=R227.  16=R401A.  
17=R507. 18=R402A.  19=R404A. 20=R407C.  21=R407A.  22=R407B.  23=R410A.  
24=R170.  25=R290.  26=R600.  27=R600a.  28=R744.  29=R1270.  

(Warning: Wrong selection of refrigerant may cause damage to the compressor).

o30

Refrigerant

ETS Valve type

Each ETS valve has a specified number of steps as given below:

Total steps

ETS 50:                     2625 [+160 / -0] steps

ETS 100:                  3530 [+160 / -0] steps

ETS 250 and 400: 3810 [+160 / -0] steps

The parameters ”n37” to ”n42” are settings for step motor ETS 100. The settings 

in n37 must be changed when another valve is used. The other settings should 

not be changed.

Number of steps from 0% to 100% open

n37

Max. steps (0 - 5000 step)

The number of steps can be set in the controller at address n37:

”n37” to ”n42” are adapted to valve type ETS 100 and should only be changed through the 
use of another valve.

Number of steps from 0-100% opening degree (x10) 

(ETS = 262. ETS 100 = 353)

n37

000 stp**

5000 stp ** 263

In practise, the EKC316A display can only manage 3 digits. 
Therefore the set value at address n37 is always 10 times greater 
i.e. if n37 is set to 263 then the true value is 2630. The same applies 
to the n37 address in the AKM system.

Working range  for pressure transmitter

Depending on the application a pressure transmitter with a given working range 

is used. This working range (say, -1 to 12 bar) must be set in the controller. The min. 

value is set.

o20

MinTransPres.

The max. value is set

o21

MaxTransPres.

The range of the pressure transmitter can be set by entering the 
transmitter’s minimum value at address o20 and maximum value 
at address o21.

Summary of Contents for EKC 316A

Page 1: ...REFRIGERATION AND AIR CONDITIONING Controller for operation of evaporator on water chiller EKC 316A Reference manual...

Page 2: ...an extern analogue signal 11 Operating the valve manually by an extern analogue signal with MOP active 11 Battery back up 13 Troubleshooting 13 Alarms 14 References 15 Installation The EKC 316A is nor...

Page 3: ...following checks can be made to the connec tion between the EKC316A controller and the stepper motor of the ETS valve 1 With the power o check that resistance between terminals 21 and 22 and terminal...

Page 4: ...essor o30 Refrigerant ETS Valve type Each ETS valve has a speci ed number of steps as given below Total steps ETS 50 2625 160 0 steps ETS 100 3530 160 0 steps ETS 250 and 400 3810 160 0 steps The para...

Page 5: ...n more capacity is required NO function n41 Valve type Menu Danfoss only Compensation direction 1 Compensation takes place when the valve opens normal setting 2 Compensation takes place when the valve...

Page 6: ...l opening degree dependant on the Kp factor the measured superheat SH and SH closes as given in the following relationship Initial OD kp factor SH SH close The regulation modes for controlling superhe...

Page 7: ...alve is that there are three settings to de ne the operating curve Problems of start up Sometimes in one to one applications the valve does not open su ciently on start up and troublesome low pressure...

Page 8: ...ontrol Refrigerant Temp S2 Superheat Ref SHref Superheat S2 S1 ETS Valve Evaporator Kp factor and Tn settings Instability cause by too much Proportional Gain can be corrected by reducing to value of t...

Page 9: ...Evaporator ETS Valve PI Control S3 S1 Kp factor and Tn settings KpT0 and Tn T0 settings The feedback of the inner loop is temperature di erence between media temperature S3 and S1 This value represen...

Page 10: ...wer response of the media temperature NOTE The settings Atten factor address n43 and Min Lim Ref address n45 should not be changed without the help of trained sta The S3 sensor has to be connected whe...

Page 11: ...signal connected to terminals 16 and 17 of the controller This can be done by setting parameter o18 to 4 for 0 to 20 mA signal or 5 for 4 to 20 mA signal The analogue input 0 or 4 mA will correspond...

Page 12: ...signal can be used when o10 is set to 6 When the sections 1 and 2 are active the function in section 2 will choose the lowest value of OD that comes from either sections 1 or the PI Control This mean...

Page 13: ...placed much higher than condenser outlet check pressure di er ence Evaporator superheat too high 1 Check superheat performance the set tings SH min and SH max 2 Check valve capacity 3 Check that the...

Page 14: ...terminals 8 9 Low Temperature alarm A2 Check ETS valve is full open and relay at terminals 8 9 No refrigerant selected A11 Select refrigerant Supply to stepper motor A43 Check connections from EKC316A...

Page 15: ...8ED102 Danfoss 03 2006 15 References 1 Controller for operation of evaporator on water chillers EKC316A Manual RS8CX502 2 Electrically operated expansion valves type ETS ETS Technical Lea et DKRCC PD...

Page 16: ...reserves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in spec...

Reviews: