background image

Instructions  RI8KU567  ©  Danfoss  08/2010 

   EKC 102D

Start-up:

Regulation starts when the voltage is on.

Go through the survey of factory settings. Make any necessary changes in the respective parameters.

English

The buttons

Set menu

1. Push the upper button until a parameter 

is shown

2. Push the upper or the lower button and 

find that parameter you want to change

3. Push the middle button until the 

parameter value is shown

4. Push the upper or the lower button and 

select the new value

5. Push the middle button again to enter 

the value.

Set temperature

1. Push the middle button until the 

temperature value is shown

2. Push the upper or the lower button and 

select the new value

3. Push the middle button to select the 

setting.

Reading the temperature at sensor S5

• Push briefly the lower button

Manuel start or stop of a defrost

• Push the lower button for four 

seconds.

 

Light emitting diode

 = refrigeration

 = defrost
 = fan running

Flashes fast at alarm

See alarm code 

• Push briefly the upper button

SW = 1.3x

Parameters

Min.-value

Max.-value

Factory set-

ting

Actual set-

ting

Function

 Codes

Normal operation

Temperature (set point)

---

-50°C

50°C

2°C

Thermostat

Differential

r01

0,1 K

20 K

2 K

Max. limitation of setpoint setting

r02

-49°C

50°C

50°C

Min. limitation of setpoint setting

r03

-50°C

49°C

-50°C

Adjustment of temperature indication

r04

-20 K

20 K

0.0 K

Temperature unit (°C/°F)

r05

°C

°F

°C

Correction of the signal from Sair

r09

-10 K

10 K

0 K

Manual service(-1), stop regulation(0), start regulation (1)

r12

-1

1

1

Displacement of reference during night operation

r13

-10 K

10 K

0 K

Activation of reference displacement r40

r39

OFF

on

OFF

Value of reference displacement (can be activated by r39 or DI)

r40

-50 K

50 K

0 K

Alarm

Delay for temperature alarm

A03

0 min

240 min

30 min

Delay for door alarm

A04

0 min

240 min

60 min

Delay for temperature alarm after defrost

A12

0 min

240 min

90 min

High alarm limit

A13

-50°C

50°C

8°C

Low alarm limit

A14

-50°C

50°C

-30°C

Alarm delay DI1

A27

0 min

240 min

30 min

High alarm limit for condenser temperature (o70)

A37

0°C

99°C

50°C

Compressor

Min. ON-time

c01

0 min

30 min

0 min

Min. OFF-time

c02

0 min

30 min

0 min

Compressor relay must cutin and out inversely (NC-function)

c30

0 / OFF

1 / on

0 / OFF

Defrost

Defrost method (none/EL/gas)

d01

no

gas

EL

Defrost stop temperature

d02

0°C

25°C

6°C

Interval between defrost starts

d03

0 hours

48 hours

8 hours

Max. defrost duration

d04

0 min

180 min

45 min

Displacement of time on cutin of defrost at start-up

d05

0 min

240 min

0 min

Drip off time

d06

0 min

60 min

0 min

Delay for fan start after defrost

d07

0 min

60 min

0 min

Fan start temperature

d08

-15°C

0°C

-5°C

Fan cutin during defrost. 0=stopped, 1=running, 2=running during pump down and defrost

d09

0

2

1

Defrost sensor (0=time, 1=S5, 2=Sair)

d10

0

2

0

Defrost at start-up

d13

no

yes

no

Max. aggregate refrigeration time between two defrosts

d18

0 hours

48 hours

0 hours

Defrost on demand - S5 temperature’s permitted variation during frost build-up. On central plant 
choose 20 K (=off)

d19

0 K

20 K

20 K

Fans

Fan stop at cutout compressor

F01

no

yes

no

Delay of fan stop

F02

0 min

30 min

0 min

Fan stop temperature (S5)

F04

-50°C

50°C

50°C

Miscellaneous

Delay of output signals after start-up

o01

0 s

600 s

5 s

Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm when open. 
4=defrost start (pulse-pressure).  5=ext.main switch. 6=night operation 7=change reference (activate 
r40). 8=alarm function when closed. 9=alarm function when open. 10=case cleaning (pulse pressure). 
11=Inject off when open.

o02

0

11

0

Access code 1 (all settings)

o05

0

100

0

Used sensor type (Pt /PTC/NTC)

o06

Pt

ntc

Pt

Display step = 0.5 (normal 0.1 at Pt sensor)

o15

no

yes

no

Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output Off.

o46

0

2

0

Access code 2 (partly access)

o64

0

100

0

Summary of Contents for EKC 102D

Page 1: ...115 V a c 2 0 VA 50 60 Hz AU Guld Gold or Oro l max 15 m 115 V CE 250 V a c UL 240 V a c DO1 Refrigeration 10 6 A 10 A Resistive 5FLA 30LRA DO2 Defrost 10 6 A 10 A Resistive 5FLA 30LRA DO3 Fan 6 3 A...

Page 2: ...emperaturalarm efter afrimning A12 0 min 240 min 90 min H j alarmgr nse A13 50 C 50 C 8 C Lav alarmgr nse A14 50 C 50 C 30 C Alarm forsinkelse DI1 A27 0 min 240 min 30 min H j alarmgr nse for kondensa...

Page 3: ...Visning af fejlkode Visning af alarmkode Visning af statuskode E1 Fejl i regulator A 1 H j temperatur alarm S0 Der reguleres E 27 S5 f ler fejl A 2 Lav temperatur alarm S2 ON tid Kompressor E 29 Sair...

Page 4: ...elay for temperature alarm after defrost A12 0 min 240 min 90 min High alarm limit A13 50 C 50 C 8 C Low alarm limit A14 50 C 50 C 30 C Alarm delay DI1 A27 0 min 240 min 30 min High alarm limit for co...

Page 5: ...ensor u69 Fault code display Alarm code display Status code display E1 Fault in controller A 1 High temperature alarm S0 Regulating E 27 S5 sensor error A 2 Low temperature alarm S2 ON time Compressor...

Page 6: ...ungen d18 0 hours 48 hours 0 hours Bedarfsgesteuerte Abtauung die S5 Temperatur erlaubt variation bei Eis aufbauung An Centralanlagen w hle 20 K off d19 0 K 20 K 20 K L fter L fterstop bei abgeschalte...

Page 7: ...zu den ab Fabrik eingestellten Werten l sst sich wie folgt vornehmen Die Spannungszufuhr zum Regler unterbrechen Die obere und die untere Taste gleichzeitig bet tigt halten und gleichzeitig die Spannu...

Page 8: ...rages d18 0 hours 48 hours 0 hours D givrage sur demande variation admissible de la temp rature S5 en cas de formation de givre Pour les installations centralis es on choisit 20 K OFF d19 0 K 20 K 20...

Page 9: ...arme Affichage des tats E1 D faut de r gulateur A 1 Alarme temp rature haute S0 R gulation en cours E 27 Erreur de sonde S5 A 2 Alarme temp rature basse S2 Temps ON du compresseur E 29 Erreur de sonde...

Page 10: ...atura A14 50 C 50 C 30 C Retardo de la alarma asociada a DI A27 0 min 240 min 30 min L mite de alarma por alta temperatura del condensador con S5 y o70 2 A37 0 C 99 C 50 C Compresor M nimo tiempo de c...

Page 11: ...eder as Se corta la alimentaci n el ctrica al EKC Se restablece la alimentaci n el ctrica mientras se mantienen pulsados los botones alto y bajo durante unos segundos Avviamento La regolazione ha iniz...

Page 12: ...y per pulizia pressione di impulsi 11 Iniezione off se aperto o02 0 11 0 Codice di accesso 1 tutte le impostazioni o05 0 100 0 Tipo di sensore utilizzato Pt PTC NTC o06 Pt ntc Pt Visualizzazione decim...

Reviews: