Installation
Technical specification
Table 3: Technical specification
Features
Description
Supply voltage
24 V AC / DC (± 15%), 50 / 60 HZ Galvanically Isolated
Power consumption
Idle: Max. 20 mA @ 24 V DC
Operating: Max. 900 mA RMS @ 24 V DC
Input signals
Po
AKS 32R (or similar Ratiometric pressure transmitter)
S2
Measuring range: -60 – +120 °C / -76 – 248 °F
S4
PT1000 or Digital input from external contact.
EEV Driver
Max. current 900mA RMS
Supported valves:
ETS 12.5, 25, 50, 100, 250, 400; ETS 6, CCMT 16-42; CTR; ETS Colibri 12-100C and User defined
Data communication
Type
RS485 – Modbus RTU (Not terminated internally)
Baud rate
19200
Address settings
Selectable via Software (default 164)
Connector
Pluggable
Internal Termination
No
Galvanic isolation
No
Environmental conditions
Storage
-34 °C to 71 °C / -30 °F to 160 °F
Operating
-25 °C to 60 °C / -13 °F to 140 °F
Humidity
<95% RH, non-condensing
Dimensions
25 × 50 × 80 mm / 0.98 × 1.97 × 3.15 inch
Battery backup
18 – 28 V DC, > 49 VmAh (Recommend using Danfoss EKE 2U)
Operation
Standalone or via MODBUS data communication
Connector type
4 way Mini fit receptacle Molex 39-01-2040 or similar
2 way Mini fit receptacle Molex 39-01-2020 or similar
Crimp: 24- 18 AWG Molex 39-020-0039 or similar.
Gateway
Standard RS485 to USB convertor. (eg; ADAM-4561, ICP DAS I-7561U-G)
Note:
check compatibility of gateway tool with PC operating system
Display
None
PC suite
None (EIM 365 is to be connected and configured using supervisor systems).
© Danfoss | Climate Solutions | 2022.09
BC415322248492en-000101 | 5
Superheat controller, type EIM 365 (PV01)