Setup
Table 33: Setup
→
Modbus
Label
Description
Min.
Max.
Value/
Type
Unit
RW
ADU
Description
MBU
Setup
→
Modbus
o03
Unit Addr
1
240
165
RW
41
Primary unit address is used when jumper KM7 is
mounted
UA2
Unit Addr 2
1
240
164
RW
42
Secondary unit address is used when the jumper
KM7 is not mounted
MBa
MB Baud
0
2
1 - 19200
Enum 2
RW
43
Communication setting baud rate, 0=9600 , 1 =
19200, 2 = 38400
MPa
MB Parity
0
2
2 - Even
parity
Enum 3
RW
44
Communication setting parity, 0 = no parity, 1 =
odd parity, 2 = even
MSB
MB StopB
1
2
1 - 1 stop
bit
Enum 4
RW
45
Communication setting stop bit, 1 = 1 stop bit, 2
= 2 stop bit
Table 34: Setup
→
Valve
Label
Description
Min.
Max.
Value/
Type
Unit
RW
ADU
Description
VAL
Setup
→
Valve
n03
Valve type
0
17
16 - No
valve selec-
ted
Enum 9
RW
110
Select the type of Danfoss stepper motor valve
from the list. If you want to correct a Danfoss giv-
en valve profile. Then first select the relevant
valve and then select USER DEFINE. 0 = ETS 12.5
or 25 1 = ETS 50 2 = ETS 100 3 = ETS 250 4 = ETS
400 5 = USER DEFINE 6 = Saginomiya UKV 7 = ETS
6 8 = CCMT 2 4 8 9 = CCMT16 10 = CCMT24 11 =
CCMT30 12 = CCMT42 13 = CTR 14 = CCMT 0 15 =
CCMT 1 16 = No valve selected 17 = ETS Colibri
n37
Max steps
100
8000
240
RW
76
Maximum number of steps (384 x 10 microsteps
= 480 half steps)
n38
Max steps/sec
10
400
16
RW
77
Steps per second
n39
Start backlash
1
100
10
%
RW
78
Backlash (steps) to close in percent at startup
(power on).
n40
Backlash
0
100
20
%
RW
79
Backlash (steps) for spindle play compensation.
This is active during normal control
n56
Motor current
0
900
0
RW
80
Motor current
h22
Holding current
0
100
20
RW
109
Holding current
dcM
Decay mode
0
2
0 - Fast
Enum 10
RW
111
0 = Fast, 1 = Slow, 2 = Mixed
Table 35: Setup
→
Refrigerant
Label
Description
Min.
Max.
Value/
Type
Unit
RW
ADU
Description
REF
Setup
→
Refrigerant
RFG
Refrigerant
0
49
0 - None
Enum 5
RW
64
Refrigerant setting. 0 = None, 1 = R12, 2 = R22, 3
= R134a, 4 = R502, 5 = R717, 6 = R13, 7 = R13b1, 8
= R23, 9 = R500, 10 = R503, 11 = R114, 12 =
R142b, 13 = User, 14 = R32, 15 = R227, 16 =
R401A, 17 = R507, 18 = R402A, 19 = R404A, 20 =
R407C, 21 = R407A, 22 = R407B, 23 = R410A, 24 =
R170, 25 = R290, 26 = R600, 27 = R600a, 28 =
R744, 29 = R1270, 30 = R417A, 31 = R422A, 32 =
R413A, 33 = R422D, 34 = R427A, 35 = R438A, 36 =
R513A, 37 = R407F, 38 = R1234zeE, 39 =
R1234yf,40 = R448A,41 = R449A, 42 = R452A, 43 =
R450A, 44 = R452A, 45 = R454B, 46 = R1233zdE,
47 = R1234zeZ, 48 = R449B, 49 = R407H
RF1
Rfg. fac. A1
8000
12000
10428
RW
65
Adiabatic constant A1
RF2
Rfg. fac. A2
-4000
-1000
-2255
RW
66
Adiabatic constant A2
RF3
Rfg. fac. A3
2000
3000
2557
RW
67
Adiabatic constant A3
© Danfoss | Climate Solutions | 2022.09
BC415322248492en-000101 | 25
Superheat controller, type EIM 365 (PV01)