WARNING:
Wrongselection of refrigerant may cause damage to the compressor.
Startup Modes
Forced opening During startup
In some applications it is necessary to open the valve quickly when the compressor turns on, to prevent too low
suction pressure. This is ensured by setting a fixed opening degree and a startup time for the controller. Note that
this will give a fixed opening degree for the duration of the start time, regardless of the superheat value. Thesetting
parameters are called Start OD% (n17) and StartUp time (n15).
EIM
365
Applicable
✓
Table 22: Forced opening During startup Parameters
Symbolic name
PNU
Description
Common EIM 336/ EIM 365
n15 Startup time
3017
Time for startup state (in seconds)
n17 Startup OD
3012
Opening degree during startup state
EIM 365
--- Startup mode
64322
1: Fixed OD; 2: P-Control
Select 1 for Fixed OD
P-control
The controller is programmed for auto proportional control that will quickly Change the opening degree based
onthe superheat of the system. The proportional control is active during the Minimum start time set by the user,
and until the Super heat crosses the reference.
EIM
365
Applicable
✓
Table 23: P-control Parameters
Symbolic name
PNU
Description
EIM 365
--- Startup mode
64322
1: Fixed OD; 2: P-Control
Select 2 for P-control
--- Min Startup Time
64324
minimum regulation time in seconds when use P-
control
n15 Startup time
3017
Time for startup state (in seconds)
Superheat controller, type EIM 365 (PV01)