background image

Table 13: Te Control mode

Symbolic name

PNU

Description

Kp Te

3115

Kp proportional gain while in Te control mode

Tn Te

3116

Tn integration time while in Te control mode

Te Reference

3117

Te reference while in Te control mode

Protection or Limiter features

EIM 365 has protection features and Limiter features that prevents the system from operating under bad conditions

or gives indication towards it, these features are

• Superheat close

• MOP (Maximum operating pressure)

• LOC (Loss of Charge indication)

Superheat Close

EIM

365

Applicable

SH close is a protection feature, When the SH values go below the SH close value, the controller will close the valve

faster.

Symbolic name

PNU

Description

n22 SH close

3027

Superheat close level. If the superheat goes below

this value, the valve will close faster.

Maximum operating pressure (MOP)

EIM

365

Applicable

In order to reduce the current to the compressor it is possible to control the maximum operating pressure of the

evaporator. If the evaporator pressure exceeds the “MOP” limit, the valve opening degree is controlled by the MOP

function which will keep the pressure below the “MOP” limit. This function takes precedence over the superheat

control, so during MOP control the superheat is not controlled.

The MOP function can be disabled by setting the “MOP” to the maximum value (2000 equaling 200 bar absolute).

When the pressure reaches the set MOP point, an increase in OD is restricted. If the pressure reaches MOP + 0.5 Bar,

an increase in OD is prohibited, and instead the OD will start to decrease. If the pressure goes below the MOP point,

the controller will start to regulate the superheat normally.

The MOP controller consists of a separate PI control, which settings can be changed by setting “Kp MOP” and “Tn

MOP”. A large Kp will lead to a large change in opening degree even at small changes in the evaporator pressure but

may lead to instability. A large Tn will lead to a slow reacting system, while a small Tn will lead to a fast-reacting

system

Figure 10: MOP controlling

Danfoss

80G12.1

1

bar

Superheat controller, type EIM 365 (PV01)

© Danfoss | Climate Solutions | 2022.09

BC415322248492en-000101 | 16

Summary of Contents for EIM 365

Page 1: ...User Guide Superheat controller Type EIM 365 PV01 For commercial air conditioning and refrigeration applications...

Page 2: ...on 5 Applications 10 User Interface 11 Configuration 12 Alarms 21 Parameter list 23 Ordering 28 Certificates declarations and approvals 29 Online support 30 Superheat controller type EIM 365 PV01 Danf...

Page 3: ...ication Bus Benefits The evaporator is charged optimally for various load and suction pressure variations Increase Energy Efficiency by ensuring optimum utilization of the Evaporator It controls EEV i...

Page 4: ...t ETS 12 5 25 50 100 250 400 ETS 6 CCMT 16 42 CTR ETS Colibri 12 100C and User defined Superheat Reference Mode MSS LoadAp Startup mode Fixed OD P Control Operation Standalone Modbus RS485 not termina...

Page 5: ...onnector Pluggable Internal Termination No Galvanic isolation No Environmental conditions Storage 34 C to 71 C 30 F to 160 F Operating 25 C to 60 C 13 F to 140 F Humidity 95 RH non condensing Dimensio...

Page 6: ...100C and user defined Dimension and Mounting Figure 1 Connection diagram IMPORTANT The supply voltage is not galvanically separated from the input and output signals hence it is not recommended to use...

Page 7: ...odbus For the Modbus cable it is best to use 24AWG shielded twisted pair cable with a shunt capacitance of 16 pF ft and 100 impedance The max permissible number of devices simultaneously connected to...

Page 8: ...ut of transformer is not recommended Do not reverse the polarity of the power connection cables and avoid ground loops i e avoid connecting one field device to several controllers as this may result i...

Page 9: ...e for long M12 cables on Danfoss stepper motor valves Long cables will lead to degradation of performance You can overcome this degradation by changing the settings for the valve driver This guideline...

Page 10: ...s located within In this configuration the master controller reads the readout registers from the EIM 365 and uses the parameters to change the control behavior of the EIM 365 see parameter list Figur...

Page 11: ...specification Remember to check the PC operating system compatibility when using 3rd party convertors Figure 6 EIM 365 Danfoss 80G8127 10 1 2 3 4 1 1 1 3 1 1 2 2 2 2 2 3 4 4 GND Power Power supply Mod...

Page 12: ...ol ON Off switch in order to control start stop regulation when needed otherwise the controller will start regulating when controller is powered up Select Refrigerant O30 1 42 default value is 20 i e...

Page 13: ...d evaporating temperature This makes the regu lation more stable compared to MSS because it does not seek a usability EIM 365 Applicable Danfoss 84B1489 10 100 Superheat Qo Unstable region wet Min SH...

Page 14: ...at control is performed and no safety features are present Table 10 Manual control EIM 365 Applicable When setting the manual control register o18 Manual ctrl to 1 the controller will be in manual con...

Page 15: ...ctivate 50011 Defrost activating 0 No defrost 1 Defrost active Def Hold OD 50008 Opening degree during Def Hold Ti 1 Def HoldTi 1 50009 Defrost hold time 1 Def HoldTi 2 50010 Defrsot hold time 2 Te Co...

Page 16: ...rator If the evaporator pressure exceeds the MOP limit the valve opening degree is controlled by the MOP function which will keep the pressure below the MOP limit This function takes precedence over t...

Page 17: ...r a long period of time this could indicate that refrigerant charge was lost When the valve opening degree exceeds the trigger level LOC Trig and the superheat exceeds the superheat trigger level LOC...

Page 18: ...e in EIM controller Temperature sensor Settings The temperature sensor input is setup by default to accept PT1000 temperature sensor The values for the sensor can be adjusted to calibrate the sensor t...

Page 19: ...but since this sensor is not used in the superheat regulation little practical use Table 20 External sensor values via Modbus Symbolic name PNU Description extEvapPress P0 2643 External evaporator pre...

Page 20: ...Startup time 3017 Time for startup state in seconds n17 Startup OD 3012 Opening degree during startup state EIM 365 Startup mode 64322 1 Fixed OD 2 P Control Select 1 for Fixed OD P control The contr...

Page 21: ...s provide a stable and relatively fast regulating system If the system however fluctuates this may be due to the fact that too low superheat parameters have been selected or due set of regulation para...

Page 22: ...o cleared after the last active alarm has been cleared S2 Error 20002 S2sensor error If the sensor error occurs the valve OD will be set to 80 of the Avg opening PNU 50021 see S2alarm is auto cleared...

Page 23: ...r to the list below It should be possible to change all other parameters while the unit is running regulation parameters etc Main Menu Table 26 Main Menu Control Label Description Min Max Value Type U...

Page 24: ...s RW 49 Defrost holding timer 1 DH2 Def Hold Ti 2 0 32000 60 s RW 50 Defrost holding timer 2 Table 30 Regulation Te control Label Description Min Max Value Type Unit RW ADU Description TEC Regulation...

Page 25: ...240 RW 76 Maximum number of steps 384 x 10 microsteps 480 half steps n38 Max steps sec 10 400 16 RW 77 Steps per second n39 Start backlash 1 100 10 RW 78 Backlash steps to close in percent at startup...

Page 26: ...d 70 S2 sensor error If the sensor error occurs the valve OD will be set to 80 of the Avg opening PNU 50021 PeE Pe inp error 0 1 0 No alarm Enum 7 Read 72 AKS 32R out of range If the sensor error occu...

Page 27: ...n U2F Service Factory U2F User to factory 0 1 0 RW 82 Controller will make the current settings to be its future factory default state F2U Factory to user 0 1 0 RW 81 Apply defaults On setting the ori...

Page 28: ...IM 365 Single pack 080G1003 Accessories Table 43 Accessories Description Pack format Code No Connector kit for 5x EIM Controller Single pack 080G1601 EKE 2U battery backup Single pack 080G5555 Superhe...

Page 29: ...or all of these approvals and certain local approvals may not appear on the list Some approvals may change over time You can check the most current status at danfoss com or contact your local Danfoss...

Page 30: ...ations manuals and guides 3D models and drawings case stories brochures and much more Start searching now at www danfoss com en service and support documentation Danfoss Learning Danfoss Learning is a...

Reviews: