Danfoss EIM 336 Manual Download Page 9

© Danfoss A/S (AC-MCI / sw), 2014-11 

DKRCC.PS.RQ0.B7.02 /520H8832   

 9

Manual 

Superheat Controller EIM 336

4. 

Using external sensor values

In some applications, the suction pressure and/or the refrigerant 

temperature on the evaporator outlet, is measured by a system 

controller. This is often the case if the suction pressure is used to 

trigger low temperature/pressure alarms by the systems main 

controller. In these cases the sensors can be omitted from the EIM 

336, and the sensor values can be received via modbus instead. 

This requires that the systems main controller continuously 

transmits these values to the EIM 336. If no new sensor value is 

received within 5 seconds of the last transmission, the sensor will 

revert to using the physical sensors.

The suction gas temperature S2 and the evaporator pressure 

Pe can be set by writing to the registers “ext S2 Temp” and “ext 

EvapPress P0” respectively. 

Note

 that the external evaporator pressure is received in millibar 

so 8.4 bar absolute must be sent as 8400. 

It is possible to set the S4 temperature as an external sensor value 

also, but since this sensor is not used in the superheat regulation, 

this has little practical use.

Related parameters:

Symbolic name

PNU

Description 

ext EvapPress P0

2643

External evaporator pressure. This value can be used instead of a sensor. 

This register must be written at least every 5 second, otherwise the sensor value will be used. 

The entered value is in millibar

ext S2 temp

2644

External S2. This value can be used instead of a sensor. 

This register must be written at least every 5 second, otherwise the sensor value will be used.

ext S4 air temp.

2646

External S4. This value can be used instead of a sensor. This register must be written at least every 5 second, otherwise the 

sensor value will be used.

5.

 Configuring the superheat control

The superheat control algorithm will attempt to regulate the 

superheat down to the lowest stable value between the minimum 

superheat setting, “n10 Min SH” and the maximum superheat 

setting, “n09 Max SH”. If a fixed superheat reference is desired 

instead, the “n10 Min SH” and “n09 Max SH” can both be set to 

the desired reference value. This will disable the minimum stable 

superheat search algorithm and the controller will instead regulate 

the superheat according to this reference. 

The time constant for the superheat control can be changed by 

setting “Tn SH”. 

The alpha value is the design time constant and should be in 

reasonable proximity to the time constant of the evaporator. A 

large alpha means a slow reaction, a small alpha means a fast 

reaction.

If the superheat drops below “n22 SH close”, the controller will 

close the valve faster to avoid the risk of liquid in the compressors 

suction line. 

Symbolic name

PNU

Description 

n09 Max SH

3015

Maximum superheat reference setting.

n10 Min SH

3021

Minimum superheat reference setting.

n20 Kp T0

3025

Pressure feedback gain.

n22 SH close

3027

Superheat close level. If the superheat goes below this value, the valve will close faster.

--- Tn SH

3103

Integration time for superheat control

--- Alpha

3111

Design time constant. A large alpha means a slow response, a small alpha mean a fast response.

--- Max SH shdw

64301

Copy of 3015. If it is required to write n09 frequently, this should be used instead.

--- Min SH shdw

64302

Copy of 3021. If it is required to write n10 frequently, this should be used instead.

--- Tn SH shdw

64303

Copy of 3103. If it is required to write TnSH frequently, this should be used instead.

--- Alpha shdw

64304

Copy of 3111.  If it is required to write alpha frequently, this should be used instead.

 

  Note:

Main Switch r12 should be ON to start the regulation. This can also be 

accomplished with the external hardware mainswitch. 

See appendix 1 for details.

Summary of Contents for EIM 336

Page 1: ...ess noise The EIM 336 is the superheat controller that can be used to control the opening degree of a valve based on the superheat of the evaporator This is applicable in applications such as air cond...

Page 2: ...allation sensors 17 Warnings 17 Acronyms and abbreviations used in this manual LOC Loss of charge indication SH Superheat MOP Maximum operating pressure MSS Minimum stable superheat Te Saturated sucti...

Page 3: ...densed Superheat close When the superheat is below a set minimum value the valve will close faster in order to protect the compressor from the risk of getting liquid in the suction line Manual control...

Page 4: ...S2 PT1000 S4 PT1000 or digital input from external contact EEV driver Max current 150 mA EEV Uni or bipolar coil Data communication RS485 Modbus RTU Environment Storage 34 C to 71 C 30 F to 160 F Ope...

Page 5: ...odbus address stored in PNU no 40041 default 165 Jumper not mounted Outdoor unit condenser Modbus address stored in PNU no 40042 default 164 Com KM5 1 Drain D 2 RS485 TxD RxD 3 RS485 TxD RxD 4 Not Use...

Page 6: ...trol mode does not depend on the r12 Main Switch and will set the opening degree regardless of its setting Setting o18 Manual ctrl to 0 again the controller will assume normal control and will open or...

Page 7: ...secondary address is 164 Note Changes to these parameters will become active immediately This means that a modbus tool or controller that changes these settings will loose connection to the EIM 336 an...

Page 8: ...e controller is powered the valve will first be closed fully so that the controller starts from a known opening degree 0 In order to make sure that it is fully closed the valve will be closed 100 plus...

Page 9: ...sensor value will be used 5 Configuring the superheat control The superheat control algorithm will attempt to regulate the superheat down to the lowest stable value between the minimum superheat sett...

Page 10: ...um operation pressure If Pe goes above this value the controller will control on Pe and not on superheat Kp MOP 3113 Kp proportional gain while in MOP control mode Tn MOP 3114 Tn integration time whil...

Page 11: ...05 Timer to trigger LOC alarm LOC Alarm 50006 Loss of charge alarm flag 0 no alarm 1 LOC alarm LOC SH Trig 50007 SH error trigger level for LOC alarm LOC Tmr 3102 Loss Of Charge time readout displays...

Page 12: ...t regulation response Very low value give the risk of unstable regulation For Danfoss only 3105 SHL SH Low 3 20 6 K Superheat low setting for non linear control 3106 SHH SH High 8 40 16 K Superheat hi...

Page 13: ...ext S2 temp 200 200 0 C External S2 This value can be used instead of a sensor This register must be written at least every 5 seconds otherwise the sensor value will be used 2646 TS4 ext S4 Air temp 2...

Page 14: ...ain Switch 64309 Manual OD as steps 0 1 0 Enable the manual OD in o45 to be entered as halfsteps Readouts are still in percent Service Alarm 2046 RAL Reset alarm 0 1 0 1 clear alarm 20001 EKC Error 0...

Page 15: ...troller will go to either the low or high boundary de pending on the error The highest value will be shown if the signal is above the maximum value The lowest value will be shown if the signal is belo...

Page 16: ...it 3 Bit 2 Bit 1 Bit 0 Unused MOP Active Close Timer active Sensor Errors Control state Variables parameters CTRLstatus bit 0 3 Controlstate 0 closed 1 Error 2 Inject 3 De humidify 4 Force OD 5 Defros...

Page 17: ...ght after the evaporator If the measured value is 1 2 K lower than the actual value of Pe right after the evaporator it may cause the evaporator to flood This is the case when the pressure transmitter...

Reviews: