Danfoss EIM 336 Manual Download Page 12

12 

DKRCC.PS.RQ0.B7.02 /520H8832  

© Danfoss A/S (AC-MCI / sw), 2014-11

Manual 

Superheat Controller EIM 336

Parameter list

Row text

Explanation

PNU

The Parameter Number in the EIM 336 controller. 

All parameters are addressed as holding register. 

The Modbus PDU address corresponds to PNU-1. 

If no translation table is used, this is the register 

number in modbus.

Min.

Minimum value

Def.

Factory default value

Max.

Maximum value

e2

Is the value stored in EEPROM

W

Is writing to the register possible

*10

The scaling of the parameter. All values are read/

written as integers over modbus. Parameters 

need to be scaled, these are marked with a 

checkmark. This means that 0.1 is sent as 1 over 

modbus, 1.0 is sent as 10 etc.

Symbolic name

The name of the parameter

Description 

Short parameter description

Group

PNU

Parameter Symbolic name Min.

Max.

Default

Units e2 W *10 Description

Control

Regulation 

Control

117

r12

Main switch

0

1

0

ü

Start/stop of regulation. With this setting the 

regulation can be started and stopped. This can 

also be accomplished with the external hardware 

main switch. See also appendix 1

2075

o18

Manl control

0

1

0

ü

0 = Superheat control, 1= Manual control

2064

o45

Manual OD 

0

100 /

480

0

% /

step

ü

Manual opening degree for manual control .

Used when the o18 Manual Control is set to 1.

0%/0 step = fully closed, 

100%/480 step = fully open.

% is chosen by  default. 

See PNU 64309 for changing to step.

3017

n15

Startup time

0

1000

0

s

ü

ü

Time for startup state (in seconds)

3012

n17

Startup OD

0

100

0

%

ü

ü

Opening degree during startup state

64308

OOD

OD while OFF

0

100

0

%

ü

ü 

Opening degree during Off state

Regulation

Super Heat 

Control

3015

n09

Max. superheat

2

20

16

K

ü

ü

ü

Maximum superheat reference setting

3021

n10

Min. superheat

1

20

4

K

ü

ü

ü

Minimum superheat reference setting

3025

n20

KpT0

-1

20

-1

ü

ü

ü

Pressure feedback gain 

Automatic = -1, OFF = 0 , Fixed = 1 and above

3027

n22

SH close

0

16

0.5

K

ü

ü

ü

Superheat close level. If the superheat goes below 

this value, the valve will close faster

3103

TSH

Tn SH

10

1800

600

ü

ü

Tn integration time for the superheat control.

Lower value give fast regulation response.

Very low value give the risk of unstable regulation.

For D

anfoss only!

3105

SHL

SH Low

3

20

6

K

ü

ü

ü

Superheat low setting for non-linear control

3106

SHH

SH High

8

40

16

K

ü

ü

ü

Superheat high setting for non-linear control

3107

GaH

Gain High

0.5

10

1

ü

ü

ü

Expected gain at SH high for non-linear control

3108

GaL

Gain Low

0.1

50

12.5

ü

ü

ü

Expected gain at SH low for non-linear control

3109

TaH

Tau High

10

600

45

ü

ü

Expected tau at SH high for non-linear control

3110

TaL

Tau Low

10

600

110

ü

ü

Expected tau at SH low for non-linear control

3111

Aph

Alpha

15

600

130

ü

ü

Design time constant. 

A large alpha means a slow response, a small 

alpha mean a fast response.

3120

CoS

Comp Speed

0

100

0

%

ü

ü

Compressor speed

Tn=2x Tn if compressor speed is set to 0%

Tn= Tn if the compressor speed is set between 25 - 

100% - ref. parameter 3103

64301

n09

x

Max. superheat 

shdw

2

20

16

K

ü

ü

Copy of 3015. If it is required to write Max 

superheat frequently, this should be used instead

64302

n10

x

Min. superheat 

shdw

1

20

4

K

ü

ü

Copy of 3021. If it is required to write Min 

superheat frequently, this should be used instead

64303

TSH

x

Tn SH shdw

10

1800

600

ü

Copy of 3103. If it is required to write TnSH 

frequently, this should be used instead.

64304

Aph

x

Alpha shdw

15

600

130

ü

Copy of 3111.  If it is required to write alpha 

frequently, this should be used instead.

 

  Note:

Some parameters have what is called a "config lock". This means

that they can only be changed when the main switch of the EIM 336

is set to OFF (r12 = 0). This applies for instance to the type of

refrigerant (o30). So if you want to change the refrigerant, the

main switch (r12) must first be set to 0, then the refrigerant type

(o30) can be changed.

The following parameters require the main switch (r12) to be OFF:

n37 Max steps

n38 Max steps/sec

o03 Unit address

o30 Refrigerant

Please refer to the list below.

It should be possible to change all other parameters while the unit

is running (regulation parameters etc.).

Shdw (

x

): 

Shdw values are stored in the volatile memory and will 

revert back to the previously stored value in its main parameter if the 

power failure occurs. Altering the main parameter will automatically 

change the shdw value. If frequent change in parameter required, it 

is recommended to use shdw parameter. 

Summary of Contents for EIM 336

Page 1: ...ess noise The EIM 336 is the superheat controller that can be used to control the opening degree of a valve based on the superheat of the evaporator This is applicable in applications such as air cond...

Page 2: ...allation sensors 17 Warnings 17 Acronyms and abbreviations used in this manual LOC Loss of charge indication SH Superheat MOP Maximum operating pressure MSS Minimum stable superheat Te Saturated sucti...

Page 3: ...densed Superheat close When the superheat is below a set minimum value the valve will close faster in order to protect the compressor from the risk of getting liquid in the suction line Manual control...

Page 4: ...S2 PT1000 S4 PT1000 or digital input from external contact EEV driver Max current 150 mA EEV Uni or bipolar coil Data communication RS485 Modbus RTU Environment Storage 34 C to 71 C 30 F to 160 F Ope...

Page 5: ...odbus address stored in PNU no 40041 default 165 Jumper not mounted Outdoor unit condenser Modbus address stored in PNU no 40042 default 164 Com KM5 1 Drain D 2 RS485 TxD RxD 3 RS485 TxD RxD 4 Not Use...

Page 6: ...trol mode does not depend on the r12 Main Switch and will set the opening degree regardless of its setting Setting o18 Manual ctrl to 0 again the controller will assume normal control and will open or...

Page 7: ...secondary address is 164 Note Changes to these parameters will become active immediately This means that a modbus tool or controller that changes these settings will loose connection to the EIM 336 an...

Page 8: ...e controller is powered the valve will first be closed fully so that the controller starts from a known opening degree 0 In order to make sure that it is fully closed the valve will be closed 100 plus...

Page 9: ...sensor value will be used 5 Configuring the superheat control The superheat control algorithm will attempt to regulate the superheat down to the lowest stable value between the minimum superheat sett...

Page 10: ...um operation pressure If Pe goes above this value the controller will control on Pe and not on superheat Kp MOP 3113 Kp proportional gain while in MOP control mode Tn MOP 3114 Tn integration time whil...

Page 11: ...05 Timer to trigger LOC alarm LOC Alarm 50006 Loss of charge alarm flag 0 no alarm 1 LOC alarm LOC SH Trig 50007 SH error trigger level for LOC alarm LOC Tmr 3102 Loss Of Charge time readout displays...

Page 12: ...t regulation response Very low value give the risk of unstable regulation For Danfoss only 3105 SHL SH Low 3 20 6 K Superheat low setting for non linear control 3106 SHH SH High 8 40 16 K Superheat hi...

Page 13: ...ext S2 temp 200 200 0 C External S2 This value can be used instead of a sensor This register must be written at least every 5 seconds otherwise the sensor value will be used 2646 TS4 ext S4 Air temp 2...

Page 14: ...ain Switch 64309 Manual OD as steps 0 1 0 Enable the manual OD in o45 to be entered as halfsteps Readouts are still in percent Service Alarm 2046 RAL Reset alarm 0 1 0 1 clear alarm 20001 EKC Error 0...

Page 15: ...troller will go to either the low or high boundary de pending on the error The highest value will be shown if the signal is above the maximum value The lowest value will be shown if the signal is belo...

Page 16: ...it 3 Bit 2 Bit 1 Bit 0 Unused MOP Active Close Timer active Sensor Errors Control state Variables parameters CTRLstatus bit 0 3 Controlstate 0 closed 1 Error 2 Inject 3 De humidify 4 Force OD 5 Defros...

Page 17: ...ght after the evaporator If the measured value is 1 2 K lower than the actual value of Pe right after the evaporator it may cause the evaporator to flood This is the case when the pressure transmitter...

Reviews: