Manual
Superheat Controller EIM 336
Parameter list
Row text
Explanation
PNU
The Parameter Number in the EIM 336 controller.
All parameters are addressed as holding register.
The Modbus PDU address corresponds to PNU-1.
If no translation table is used, this is the register
number in modbus.
Min.
Minimum value
Def.
Factory default value
Max.
Maximum value
e2
Is the value stored in EEPROM
W
Is writing to the register possible
*10
The scaling of the parameter. All values are read/
written as integers over modbus. Parameters
need to be scaled, these are marked with a
checkmark. This means that 0.1 is sent as 1 over
modbus, 1.0 is sent as 10 etc.
Symbolic name
The name of the parameter
Description
Short parameter description
Group
PNU
Parameter Symbolic name Min.
Max.
Default
Units e2 W *10 Description
Control
Regulation
Control
117
r12
Main switch
0
1
0
ü
Start/stop of regulation. With this setting the
regulation can be started and stopped. This can
also be accomplished with the external hardware
main switch. See also appendix 1
2075
o18
Manl control
0
1
0
ü
0 = Superheat control, 1= Manual control
2064
o45
Manual OD
0
100 /
480
0
% /
step
ü
Manual opening degree for manual control .
Used when the o18 Manual Control is set to 1.
0%/0 step = fully closed,
100%/480 step = fully open.
% is chosen by default.
See PNU 64309 for changing to step.
3017
n15
Startup time
0
1000
0
s
ü
ü
Time for startup state (in seconds)
3012
n17
Startup OD
0
100
0
%
ü
ü
Opening degree during startup state
64308
OOD
OD while OFF
0
100
0
%
ü
ü
Opening degree during Off state
Regulation
Super Heat
Control
3015
n09
Max. superheat
2
20
16
K
ü
ü
ü
Maximum superheat reference setting
3021
n10
Min. superheat
1
20
4
K
ü
ü
ü
Minimum superheat reference setting
3025
n20
KpT0
-1
20
-1
ü
ü
ü
Pressure feedback gain
Automatic = -1, OFF = 0 , Fixed = 1 and above
3027
n22
SH close
0
16
0.5
K
ü
ü
ü
Superheat close level. If the superheat goes below
this value, the valve will close faster
3103
TSH
Tn SH
10
1800
600
ü
ü
Tn integration time for the superheat control.
Lower value give fast regulation response.
Very low value give the risk of unstable regulation.
For D
anfoss only!
3105
SHL
SH Low
3
20
6
K
ü
ü
ü
Superheat low setting for non-linear control
3106
SHH
SH High
8
40
16
K
ü
ü
ü
Superheat high setting for non-linear control
3107
GaH
Gain High
0.5
10
1
ü
ü
ü
Expected gain at SH high for non-linear control
3108
GaL
Gain Low
0.1
50
12.5
ü
ü
ü
Expected gain at SH low for non-linear control
3109
TaH
Tau High
10
600
45
ü
ü
Expected tau at SH high for non-linear control
3110
TaL
Tau Low
10
600
110
ü
ü
Expected tau at SH low for non-linear control
3111
Aph
Alpha
15
600
130
ü
ü
Design time constant.
A large alpha means a slow response, a small
alpha mean a fast response.
3120
CoS
Comp Speed
0
100
0
%
ü
ü
Compressor speed
Tn=2x Tn if compressor speed is set to 0%
Tn= Tn if the compressor speed is set between 25 -
100% - ref. parameter 3103
64301
n09
x
Max. superheat
shdw
2
20
16
K
ü
ü
Copy of 3015. If it is required to write Max
superheat frequently, this should be used instead
64302
n10
x
Min. superheat
shdw
1
20
4
K
ü
ü
Copy of 3021. If it is required to write Min
superheat frequently, this should be used instead
64303
TSH
x
Tn SH shdw
10
1800
600
ü
Copy of 3103. If it is required to write TnSH
frequently, this should be used instead.
64304
Aph
x
Alpha shdw
15
600
130
ü
Copy of 3111. If it is required to write alpha
frequently, this should be used instead.
Note:
Some parameters have what is called a "config lock". This means
that they can only be changed when the main switch of the EIM 336
is set to OFF (r12 = 0). This applies for instance to the type of
refrigerant (o30). So if you want to change the refrigerant, the
main switch (r12) must first be set to 0, then the refrigerant type
(o30) can be changed.
The following parameters require the main switch (r12) to be OFF:
n37 Max steps
n38 Max steps/sec
o03 Unit address
o30 Refrigerant
Please refer to the list below.
It should be possible to change all other parameters while the unit
is running (regulation parameters etc.).
Shdw (
x
):
Shdw values are stored in the volatile memory and will
revert back to the previously stored value in its main parameter if the
power failure occurs. Altering the main parameter will automatically
change the shdw value. If frequent change in parameter required, it
is recommended to use shdw parameter.