Setup
(continued)
14
DKRCC.PS.RQ0.B5.02 / 520H8256
© Danfoss A/S (AC-MCI / sw), 2014-11
Manual
Superheat Controller EIM 336
Group
PNU
Parameter
Symbolic name
Min.
Max.
Default Units
e2
W
*10
Description
Regfrigerant
2551
o30
Refrigerant
0
31
23
ü
ü
1 = R12
2 = R22
3 = R134a
4 = R502
5 = R717
6 = R13
7 = R13b1
8 = R23
9 = R500
10 = R503
11 = R114
12 = R142b
13 = User
defined
14 = R32
15 = R227
16 = R401A
17 = R507
18 = R402A
19 = R404A
20 = R407C
21 = R407A
22 = R407B
23 = R410A
24 = R170
25 = R290
26 = R600
27 = R600a
28 = R744
29 = R1270
30 = R417A
31 = R422A
32=R413A
33=R422D
34=427A
35=R438A
36=Opteon
XP10
37 =R407F
2548
RF1
Rfg. fac. A1
8000
12000
10428
ü
ü
Adiabatic constant A1
2549
RF2
Rfg. fac. A2
-4000
-1000
-2255
ü
ü
Adiabatic constant A2
2550
RF3
Rfg. fac. A3
1000
3000
2557
ü ü
Adiabatic constant A3
Sensors
113
r09
Adjust S2
-10
0
0
K
ü
ü
ü
S2 Offset adjustment to correct the
sensor signal due to long wires etc.
2033
o21
Max. transducer
pressure
1
200
16
bar
(abs.)
ü
ü
ü
Maximum transducer pressure (in bar
absolute * 10)
2034
o20
Min. transducer
pressure
0
1
0
bar
(abs.)
ü
ü
ü
Minimum transducer pressure (in bar
absolute * 10)
System
50020
-
Avg KT0 time
10
3600
180
ü
ü
Average time for KT0 used as filtervalue
for the average opening degree calcula-
tion when calculating the KT0
50021
-
Avg OD 3 hours
0
1000
100
per
mill
ü
ü
ü
Average OD, updated every 3 hours
50051
-
Sampling time
1
10
1
sec.
ü
ü
Algorithm sampling time
64200
LBO
Limited list
0
1
0
ü
ü
Modbus translation table for limited list
of sequential registers
64100
HWM
HW main switch
0
1
0
ü
ü
1 = S4 input is HW Main Switch
64309
-
Manual OD as
steps
0
1
0
ü
ü
Enable the manual OD in o45 to be
entered as halfsteps. Readouts are still in
percent
Service
Alarm
2046
RAL
Reset alarm
0
1
0
ü
1 = clear alarm
20001
-
EKC Error
0
1
0
Common error flag. EKC Error is SET if any
other Error Alarm is ON.
20002
-
S2 Error
0
1
0
S2 sensor error. If the sensor error
occurs, the valve OD will be set to 80%
of the Avg. opening (PNU 50021) - see
troubleshooting.
20005
-
Pe inp.error
0
1
0
AKS 32R out of range. If the sensor error
occurs, the valve OD will be set to 80%
of the Avg. opening (PNU 50021) - see
troubleshooting.
20006
-
No Rfg. Sel.
0
1
0
Refrigerant not selected
50006
-
LOC Alarm
0
1
0
Loss of charge alarm. No action will be
performed except setting the alarm.
Readout
2531
u16
S4 air temp
-200
200
0
°C
ü
S4 temperature in °C measured with PT
1000 sensor connected to KM2
2535
u22
Superheat Ref
0
100
0
K
ü
Current superheat reference
2536
u21
Superheat
0
100
0
K
ü
Current superheat (S2 - evaporator
temperature)
2537
u20
S2 Temp
-200
200
0
°C
ü
S2 temperature in °C measured with a PT
1000 sensor connected to KM1.
2542
u24
opening %
0
100
0
%
Actual opening degree
2543
u25
Evap Press P
e
-200
200
0
bar
(abs.)
ü
Evaporator pressure measured with
ratiometric pressure transmitter at KM6.
2544
u26
Evap Temp T
e
-200
200
0
°C
ü
Evaporator temperature (converted from
evaporator pressure)
3101
-
Closed valve T
0
2000
0
Closed valve timer
3102
-
LOC Tmr
0
2000
0
Loss Of Charge time
50033
-
Avg opening
0
100
0
%
Average opening degree. If it has never
run before it will give the value of PNU
50021 at start up.
64306
-
SWVer shdw
x
x
x
Copy of 2003. This displays the version
number in a non-EKC format. For
example 123 means vers 1.23