© Danfoss A/S (AC-MCI / sw), 2014-11
DKRCC.PS.RQ0.B7.02 /520H8832
13
Manual
Superheat Controller EIM 336
Group
PNU
Parameter Symbolic name
Min.
Max.
Default Units
e2 W
*10
Description
MOP
3013
n11
MOP
0
200
13.7
bar
(abs.)
ü
ü
ü
Maximum operation pressure. If Pe goes
above this value, the controller will
control on Pe, and not on superheat
3113
KpM
Kp MOP
0.5
10
0.5
ü
ü
ü
Kp proportional gain while in MOP
control mode
3114
TnM
Tn Mop
30
600
180
ü
ü
Tn integration time while in MOP control
mode
3121
DMO
Diff MOP
-20
0
0
bar
(abs.)
ü
ü
Differential MOP. A remote offset that is
added to the MOP. Needs to be written
every 5 seconds, else the offset is set
to 0.
Defrost
50011
DeA
Def Activate
0
1
0
ü
Defrost activating
50008
DHO
Def Hold OD
0
100
30
%
ü
ü
Defrost holding level
50009
DH1
Def Hold Ti 1
0
32000
120
s
ü
ü
Defrost holding timer 1
50010
DH2
Def Hold Ti 2
0
32000
60
s
ü
ü
Defrost holding timer 2
64305
DDO
Def hold OD
shdw
0
100
30
%
ü
ü
Copy of 50008. If it is required to write
Def Hold OD frequently, this should be
used instead.
T
e
Control
3115
KpTe
Kp Te
0.5
10
1
ü
ü
Kp proportional gain while in Te control
mode
3116
TnT
Tn Te
30
600
60
ü
ü
Tn integration time while in Te control
mode
3117
TeR
Te Reference
-200
200
0
°C
ü
ü
Te reference while in Te control mode
External
sensors
2643
PEV
ext. EvapPress
P0
0
65535
0
milli
bar
ü
External evaporator pressure. This value
can be used instead of a sensor. This
register must be written at least every 5
seconds, otherwise the sensor value will
be used.
2644
TS2
ext. S2 temp
-200
200
0
°C
ü
ü
External S2. This value can be used
instead of a sensor. This register must
be written at least every 5 seconds,
otherwise the sensor value will be used.
2646
TS4
ext. S4 Air temp
-200
200
0
°C
ü
ü
External S4. This value can be used
instead of a sensor. This register must
be written at least every 5 seconds,
otherwise the sensor value will be used.
LOC
50003
LTR
LOC Trig
0
100
95
%
ü
ü
Trigger value for loss of charge
50004
LRe
LOC Reset
0
100
85
%
ü
ü
Reset value for loss of charge
50005
LTm
LOC Timer
0
7200
3600
s
ü
ü
Timer to trigger LOC alarm
50007
LST
LOC SH Trig
0
50
20
K
ü
ü
ü
SH error trigger level for LOC alarm
Setup
Modbus
2008
003
Unit Addr
1
240
165
ü
ü
Primary unit address is used when
jumper KM7 is mounted
2009
UA2
Unit Addr 2
1
240
164
ü
ü
Secondary unit address is used when the
jumper KM7 is not mounted
50060
MBa
MB Baud
0
2
1
ü
ü
Communication setting baud rate, 0
=9600 , 1 = 19200, 2 = 38400
50061
MPa
MB Parity
0
2
2
ü
ü
Communication setting parity,
0 = no parity, 1 = odd parity, 2 = even
50062
MSB
MB StopB
1
2
1
ü
ü
Communication setting stop bit, 1 = 1
stop bit, 2 = 2 stop bit
64200
-
Modbus trans
0
3
1
ü
ü
1 = Enabling translation tables. If
the translation table is enabled, only
registers some are accessible.
Valve
3032
n37
Max steps
100
1000
384
ü
ü
Maximum number of steps
(384 x 10 microsteps = 480 half steps)
3033
n38
Max steps/sec
5
300
31
ü
ü
Steps per second
3034
n39
Start backlash
1
100
10
%
ü
ü
Backlash (steps) to close in percent at
startup (power on).
3035
n40
Backlash
0
100
20
%
ü
ü
Backlash (steps) for spindle play
compensation. This is active during
normal control
3037
n42
Comp. dir.
1
2
1
ü
ü
Compensation direction
3051
n56
Motor current
0
300
150
mA
ü
ü
Motor current
Regulation
(continued)