• The heating cable must be protected against
excess strain and tension. Stepping on the ca-
bles or crossing the cables with vehicles should
be avoided, as this may damage the cables.
• The surface onto which the cable is to be in-
stalled must be clean and free of sharp objects.
• Never secure the cable with metal or metal
strips.
• Do not connect power to heating cable while
it is on the drum or shipping carton.
• When storing the cable, the ends must be
sealed to keep out moisture that could other-
wise damage the cable.
1.4
System Overview
Cable
Color
Application
Effect @ 230 V
Dimension
Cap
Mechanical Class
ECpipeguard 10
Blue
On pipes
10 W/m @ 10° C
5,5 x 11,8 mm
TPE
IEC 60800:M2
ECpipeguard 25
Red
On pipes
25 W/m @ 10° C
5,5 x 11,8 mm
TPE
IEC 60800:M2
ECpipeguard 33
Brown On pipes
33 W/m @ 10° C
5,5 x 11,8 mm
TPE
IEC 60800:M2
ECiceguard 18
Black
Roof & gutter
18 W/m @ 10° C
5,8 x 11,3 mm
TPE, UV
IEC 60800:M2
EChotwatt 45
Black
On pipes
7 W/m @ 45° C
5,5 x 11,8 mm
TPE
IEC 60800:M2
EChotwatt 55
Green On pipes
8 W/m @ 55° C
5,8 x 11,8 mm
TPE
IEC 60800:M2
EChotwatt 70
Red
On pipes
12 W/m @ 70° C
5,8 x 11,8 mm
TPE
IEC 60800:M2
ECpipeheat 10
Blue
On / in pipes
10 W/m @ 10° C
5,3 x 7,7 mm
TPE
IEC 60800:M2
Voltage 220V - 240V AC
Minimum installation temperature -50° C.
Max. temperature ON = 65° C.
Max. temperature OFF = 85° C.
Note:
• The stated effect is measured on the cable
installed on pipe under insulation.
• The Self-limiting cables have to be in good
thermal contact with the item to be heated.
• When self-limiting cables are surrounded
by thermal conducting materials (water /
concrete, etc.) the effect may be double in
relation to the nominal value.