Service parameter(s) 21
32e
21 Total stop
Circuit
Setting range
Factory setting
I
ON / OFF
OFF
Decide whether you want a total stop during the setback
temperature period.
ON:
The desired flow temperature is lowered
to 10 °C. The min. setting of the flow
temperature (line 2, section 22) is overruled.
ON
OFF
2
oC
OFF:
No total stop
ON
OFF
2
oC
Frost protection is disabled if the setting in line 21 is set to ON:
The pump stops and the motorized control valve closes.
Frost protection is enabled if the setting in line 21 is set to OFF:
The pump starts if the outdoor temperature drops below 2
o
C
and the flow temperature is kept at 10
o
C. The post-run of the
circulation pump is set in line 40. See also lines 126 - 129.
ON
OFF
2
oC
Heating ON
Heating ON
Outdoor temp.
Heating OFF
Line 40
Time
Start date
Stop date
Heating ON
Heating ON
Outdoor temp.
Heating OFF
Line 40
Time
Start date
Stop date
Outdoor temp.
Line 40
Time