Service parameter(s) 17-20
20 Optimization based on room / outdoor temperature
Circuit
Setting range
Factory setting
I
ON / OFF
OFF
The optimized start and stop time can be based on either room or
outdoor temperature.
ON:
Optimization based on room temperature, if
measured.
OFF:
Optimization based on outdoor
temperature. Use this setting if the room
temperature is not measured.
17 Influence on desired flow temperature (T
flow.ref(I)
)
Circuit
Setting range
Factory setting
I
OFF / 1 ... 20 K
OFF
The desired flow temperature in heating circuit I can be
influenced by an external reference.
OFF:
The desired flow temperature in circuit I
is not influenced by any other controller
(slave).
1 ... 20:
The desired flow temperature is increased
by the set value (line 17), if the demand of a
slave is higher.
Temp.
Setting line 17
T
flow.ref(I)
T
flow.ref(II)
Example:
If a slave controller demands a higher temperature
than that of the master controller (T
flow.ref(I)
),
the temperature of the master will be increased
accordingly (T
flow.ref(II)
) + the setting (line 17).
The function of line 17 can compensate for heat losses between
master and slave controlled systems.