The grey
side of the
ECL Card
Ex
tended ser
vic
e
Service parameter(s) 31-34
32h
31 Return temperature limitation - upper limit (X-axis)
Circuit
Setting range
Factory setting
I
-30 ... 15 °C
15 °C
Set the outdoor temperature value (see drawing).
Set the outdoor temperature value (X coordinate)
for the upper limit.
(The corresponding Y coordinate is set in line 32).
32 Return temperature limitation - upper limit (Y-axis)
Circuit
Setting range
Factory setting
I
10 ... 110 °C
40 °C
Set the return temperature limitation referring to the outdoor
temperature value set in line 31 (see drawing).
Set the return temperature (Y coordinate) for the
upper limit.
(The corresponding X coordinate is set in line 31).
33 Return temperature limitation - lower limit (X-axis)
Circuit
Setting range
Factory setting
I
-30 ... 15 °C
-15 °C
Set the outdoor temperature value (see drawing).
Set the outdoor temperature value (X coordinate)
for the lower limit.
(The corresponding Y coordinate is set in line 34).
34 Return temperature limitation - lower limit (Y-axis)
Circuit
Setting range
Factory setting
I
10 ... 110 °C
60 °C
Set the return temperature limitation (see drawing).
Set the return temperature (Y coordinate) for the
lower limit.
(The corresponding X coordinate is set in line 33).
Summary of Contents for ECL Comfort 300
Page 4: ......
Page 9: ...Installation 11b...
Page 17: ...Installation...
Page 32: ...The grey side of the ECL Card Basic set up...
Page 59: ...The grey side of the ECL Card Extended service...