Installation Guide
ECA 30 / 31 for ECL Comfort 210 / 210B / 310 / 310B
ECA MENU > ECA settings > ECA sensor
RH offset (ECA 31 only)
Setting range
Factory setting
–10.0 ... 10.0 %
0.0 %
The measured relative humidity can be corrected with a
number of %-values. The corrected value is used by the
application in the ECL controller.
Minus
value:
The indicated relative humidity is lower.
0.0 %:
No correction of the measured relative humidity.
Plus
value:
The indicated relative humidity is higher.
Example:
RH offset:
0.0 %
Displayed relative humidity:
43.4 %
RH offset:
3.5 %
Displayed relative humidity:
46.9 %
ECA MENU > ECA system > ECA display
Backlight (display brightness)
Setting range
Factory setting
0 ... 10
5
Adjust the brightness of the display.
0:
Weak backlight.
10:
Strong backlight.
ECA MENU > ECA system > ECA display
Contrast (display contrast)
Setting range
Factory setting
0 ... 10
3
Adjust the contrast of the display.
0:
Low contrast.
10:
High contrast.
ECA MENU > ECA system > ECA display
Use as remote
Setting range
Factory setting
OFF / ON
*)
ECA 30 / 31 can act as a simple or normal remote control
for the ECL controller.
OFF:
Simple remote control, no room temperature signal.
ON:
Remote control, room temperature signal is available.
*):
Differently, depending on chosen application.
When set to OFF: The ECA menu shows date and time.
When set to ON: The ECA menu shows date and room temperature
(and for ECA 31 relative humidity).