Installation Guide
ECA 30 / 31 for ECL Comfort 210 / 210B / 310 / 310B
Example, continued:
ECA 30 / 31:
ECA MENU > ECA System > ECA communication:
Connection addr.:
•
Set to 15 (only one controller, the master, in the system)
•
Set to 1 ... 9 or 15 (when master and slave(s) controllers in the
system)
Alternative setting of address:
1. Choose ECA picture
2. Move the position indicator to the controller icon
3. Push the dial to select the controller icon
4. Turn the dial to select desired address
5. Push the dial to confirm your choice
Example showing connected ECL Comfort Controller address.
Example, continued:
ECA 30 / 31:
ECA MENU > ECA System > ECA override:
Override addr.:
•
Set to 15 (only one controller, the master, in the system)
•
Set to 1 ... 9 or 15 (when master and slave(s) controllers in the
system)
Override circuit:
•
Set the desired circuit number (1-4).
Note:
•
Only heating circuits can be overridden.
•
In the ECL Comfort controller the heating circuit in question
must be set to A or B.
8
DEN-SMT/DK
VI.GU.V1.02
Danfoss District Energy