Installation Guide
ECA 30 / 31 for ECL Comfort 210 / 210B / 310 / 310B
The ECL menus are as described for the ECL controller.
Most of the settings done directly in the ECL controller can be done
via the ECA 30 / 31 too.
All settings can be seen even if the application key is not inserted in
the ECL controller.
For changing settings, the application key must be inserted.
The Key overview (MENU > 'Common controller settings' > 'Key
functions') does not show the applications of the key.
The ECA 30 / 31 will display this information (an X on the ECA 30 / 31
symbol) if the application in the ECL controller does not comply with
the ECA 30 / 31:
In the example 1.10 is current version and 1.42 is desired version.
Display part of ECA 30 / 31:
This display indicates that an application has not been uploaded or the
communication to the ECL controller (master) is not working properly.
An X on the ECL controller symbol indicates wrong setup of
communication addresses.
When ECA 30 / 31 is in ECA MENU mode, the date and measured
room temperature is displayed.
ECA MENU > ECA settings > ECA sensor
Room T Offset
Setting range
Factory setting
–10.0 ... 10.0 K
0.0 K
The measured room temperature can be corrected with
a number of Kelvin. The corrected value is used by the
heating circuit in the ECL controller.
Minus
value:
The indicated room temperature is lower.
0.0 K:
No correction of the measured room temperature.
Plus
value:
The indicated room temperature is higher.
Example:
Room T offset:
0.0 K
Displayed room temperature:
21.9 °C
Room T offset:
1.5 K
Displayed room temperature:
23.4 °C
Danfoss District Energy
VI.GU.V1.02
DEN-SMT/DK
19