Installation Guide
ECA 30 / 31 for ECL Comfort 210 / 210B / 310 / 310B
2.4 Override functions ECA 30 / 31
The table to the right shows the override functions.
The override functions are enabled when communication has been
established (see ECA MENU > ECA system > ECA override).
Furthermore, the function selector of the heating circuit must be in
scheduled mode.
If holiday mode is activated then holiday mode takes priority and
cancels the override mode.
Extended saving mode:
Extended comfort mode:
Holiday away from home:
Override functions:
Holiday at home:
DHW circuits cannot be temporarily overridden.
Example on override:
•
Go to ECA MENU
•
Place cursor at clock symbol (Function selector)
•
Push / turn dial to select override form
If scheduled mode is not selected, the cursor cannot be placed at the
function selector.
Extended saving mode
:
When selected, the override stop time can be set (max. 23 hours
ahead).
In addition, the desired room temperature in the override period
can be set.
Extended comfort mode
:
When selected, the override stop time can be set (max. 23 hours
ahead).
In addition, the desired room temperature in the override period
can be set.
Holiday away from home
:
When selected, the override stop date can be set (max. 365 days
ahead).
In addition, the desired room temperature in the override period
can be set.
Holiday at home
:
When selected, the override stop date can be set (max. 365 days
ahead).
In addition, the desired room temperature in the override period
can be set.
When “holiday” override is selected, the stop date is the last holiday
date.
Example:
Stop date is set to "15.11" (15th of November), meaning that from
midnight between the 15th of November and the 16th of November,
the override is disabled.
Danfoss District Energy
VI.GU.V1.02
DEN-SMT/DK
9