Cabling
•
For the power cables, it is recommended to use Radox Elastomer S, screened automotive cable or
equivalent cable with similar specifications.
•
Use only EMI-shielded power cables to make sure the correct operation of the electric device and to
minimize the radiated emissions. Cable shields must be connected to the electric device ground at
both ends of the cable. All Danfoss products use EMI-shielded cable glands for power connections.
Wiring
To make sure of correct and steady operation, use EMI-shielded cables for the control signals of the
electric device. Cable shields must be connected to the electric device ground at both ends of the cable.
Recommendations for control signal cables
Cable
Cable type and properties
External temperature measurement (PT100/PT1000)
shielded cable (twisted pair)
High voltage connections
The high voltage connections have a common ground connector.
U
HV
≥ U
LV
Make sure the power cables exit straight from the terminals and do not rub against the sharp
cable through-holes or other sharp edges which could wear out the cable insulation over
time.
Do not place any excess weight on the connection box lid(s).
•
The electric device must be installed and connected according to the instructions.
•
Make sure that all the connected applications are connected to the electric device according to the
product specific operating voltage.
•
The electric device is delivered with the power terminal cover mounted. To access the power
connections, remove the mechanical safety feature and the connection box lid.
For more information, see appropriate chapters in this user guide and the product data sheets.
Low voltage connections
See the correct signal connections and product specific pin-layout from product data sheets,
.
User Guide
EC-LTS1200-410