Cable lug and cable gland assembly cross section
Example of the equipment needed for the assembly
Description
Manufacturer's homepage Art.No./Part No.
Assembly equipment (example) Torque key and turnkey
head
730N/10-50
Key
SE30
Assembly example for a 50 mm
2
cable
Cable with nominal
cross-section of 50 mm
2
Radox Elastomer S
Cable lug
03903
Cable gland
Pflitsch blueglobe TRI bg
225ms tri
Screw
DIN 912 M8x16 (item:
10285)
Washer
DIN 2093, 8,2 x 16 x 0,9
(item: 17332)
Washer
DIN 125 D8
(item: 10285)
Cabling and wiring
Route the power cables as far from the control signal wires as possible. The minimum
separating distance is 100 mm. The crossings must be in an angle of 90º. Power cables and
control wires should be routed near the frame of the application. Make sure that all terminal
connections are tightened correctly.
Install the electric device by the instructions. Make sure that all the applications of the system, for
example, batteries are connected to the electric device by the instructions of this user guide and the
product specific guidelines.
User Guide
EC-LTS1200-410
Installation
©
Danfoss | July 2021
BC355449988603en-000201 | 31