Installation Guide
DLX seriesL00410622-01
47
9. Technical Data
Parameter
DLX 2.0
DLX 2.9
DLX 3.8
DLX 4.6
AC
|S|
Rated apparent power
2000 VA
2900 VA
3800 VA
4600 VA
P
Rated active power @ cosphi = 1
2000 W
2900 W
3800 W
4600 W
Q
Reactive power range
0-1600 VAr
0-2320 VAr
0-3120 VAr
0-3680 VAr
Controlled power factor range
0.8 over-excited, 0.8 under-excided
V
ac,r
Rated output voltage
230 V
V
ac, min
; V
ac
,
max
AC voltage range (P-N. P-P)
230 V±20%, single or split phase
Nominal output current
9.0 A
13.0 A
17.0 A
20.0 A
I
acmax
Max output current
10.5 A
15.2 A
19.7 A
23.0 A
AC current distortion (THD %)
2.59%
3.36%
Cosphi
ac,r
Power Factor (cos φ)
0.8 over-excited, 0.8 under-excided
Night-time power loss
< 1 W
f
r
Mains frequency
50 Hz
f
min
, f
max
Grid frequency range
50 Hz ± 5 %
DC
Nominal DC power
2100 W
3000 W
4000 W
4800 W
Max recommended PV power
2625 W
3750 W
5000 W
6000 W
V
dc,r
Nominal voltage DC
220 – 480 V
220 - 480 V
V
mppmin
V
mppmax
MPP voltage-nominal power
230 – 480 V
250 - 480 V
MPP
efficiency
99.9%
Max. DC voltage
600 V
Turn on voltage
230 VDC
Turn off voltage
220 VDC
Max current DC
9.5 A
13.5 A
18.0 A
21.0 A
Max. short circuit current DC at STC
9.5 A
13.5 A
18.0 A
21.0 A
Min. on grid power
7 W
Efficiency
Maximum efficiency
97.2 %
97.2 %
97.2 %
97.3 %
CEC efficiency
96.8 %
96.8 %
97.0 %
97.0 %
EU efficiency
96.3 %
96.5 %
96.7 %
96.9 %
Other
Dimensions
610 x 353 x 158 mm(169.5 mm with bracket)
Mounting
recommendation
Wall
bracket
Weight
19 kg
21 kg
Sealing
grade
IP65
Acoustic noise level
< 37dB (A)
Operation temperature range
-25 to +65 °C (Possible power derating above +45 °C)
Storage temperature
-30 °C to + 80 °C
Relative humidity
4 to 99%
Number of PV string inputs
3
Number of MPP trackers
1
Protection against excessive PV power
Yes
Overvoltage category AC / DC
Class B / Class B
Reverse polarity protection
Yes
Ground
fault
monitoring
Yes
Integral DC switch
Yes
PV grounding
Field configurable for ungrounded, positive grounded or
negative grounded
Topology
High frequency transformer, galvanic isolation
Performance monitoring
Graphical colour display with 6 touch sense buttons, 3x
LEDs for visual status indication, Built-in Web Server
PV
connection
SunClix
AC/grid connection
Screw terminals
Ethernet
1 x RJ45
RS-485 / CAN
Screw terminals
Functional safety
Safety (protective class)
Class I
Islanding detection/ loss of mains
Active Frequency Shift
RCD type A recommendation
Yes
Indirect contact protection
Yes, (Start class I, grounded)
Voltage & frequency surveillance
Included
Insulation resistance surveillance
Included
DC content of AC current surveillance
Included