Table 4.
Outdoor sensor
°C
ohm, Ω
-30
1884
-25
1443
-20
1115
-15
868
-10
681
-5
538
0
428
5
343
10
276
15
224
20
183
25
150
30
124
35
103
40
86
Table 5.
other sensors
°C
kilo ohm, kΩ
0
66,3
5
52,4
10
41,8
15
33,5
20
27,1
25
22,0
30
18,0
35
14,8
40
12,2
45
10,1
50
8,5
55
7,1
60
6,0
65
5,0
70
4,2
75
3,7
80
3,1
85
2,7
7.11.1
Measurement checking sensors during fault tracing
1.
Disconnect the relevant sensor from I/O-card/terminal block.
2.
Measure the resistance for the sensor and any extension cables.
3.
Then measure the sensor only.
Note! To ensure the sensor value the actual temperature must be checked against the measured resistance.