Piping installation
Caution! To prevent leaks ensure that there are no stresses in the connecting lines!
Note! Ensure that the pipe installation is carried out in accordance with the dimensions and connection
diagrams.
Note! Pipe installation must be carried out by an authorized installer.
Caution! It is important that the heating system is bled after installation.
Caution! Bleed valves must be installed where necessary.
6.1
Safety valve
Note! The heat pump must be connected to the expansion tank and the safety valve according to applicable
regulations. The connection between the reservoir and the safety valve must be routed in a continuous
incline. A continuous upwards slope means that the pipe must not slope downwards from the horizontal at
any point.
Caution! The brine circuit must be filled with the correct amount of fluid otherwise the installation may
become damaged. Ensure that system has the necessary pressure, however, not above maximum pressure
of
6
bar.
Caution! Heating systems with closed expansion tanks must also be supplied with approved pressure gauges
and safety valves.
6.2
Heating system supply pipe and return pipe
1.
Install a filter (max mesh size 0.7 mm) in the heating system’s return pipe to protect the unit against foreign
particles.
2.
Install the supply line with all the accompanying components.
3.
Install the return line with all the accompanying components.
4.
Insulate the supply and return lines.
16 – Installation instructions
VMIFJ102