7.18
Conversion table for sensors, PT-1000
When reading the resistance of the sensors, the sensor leads must first be disconnected from the control equipment. First measure the
sensor and cable. Then measure the sensor only.
°C
ohms
-30
882
-20
921
-10
960
0
1000
10
1039
20
1078
30
1117
40
1155
50
1924
60
1232
70
1270
80
1309
90
1347
100
1385
110
1422
120
1460
130
1497