DHP-AX – 24
VUBMI102
Sub-menu HEAT CURVE
5.1.2
In the HEAT CURVE menu the settings that affect the
indoor temperature are made. For further informa-
tion, see section ”2 About your heat pump”.
Menu text
Description
Adjusted by:
CURVE
The set value indicates the supply line
temperature of the water that is trans-
ported to the heating system at an out-
door temperature of 0°C.
By the customer, if
necessary.
MIN
Sets the lowest permitted supply tempe-
rature.
By the customer, if
necessary.
MAX
Sets the highest permitted supply tem-
perature.
By the customer, if
necessary.
CURVE 5
Used to adjust the heat curve at an out-
door temperature of +5°C.
By the customer, if
necessary.
CURVE 0
Used to adjust the heat curve at an out-
door temperature of 0°C.
By the customer, if
necessary.
CURVE - 5
Used to adjust the heat curve at an out-
door temperature of -5°C.
By the customer, if
necessary.
HEAT STOP
This function stops all production of
heat when the outdoor temperature is
equal to, or higher than, the set heat stop
value.
By the customer, if
necessary.
REDUCTION
The temperature can be lowered using
an outside timer. The control computer
lowers the indoor temperature using the
set value.
By the customer, if
necessary.
ROOM FACTOR
(Only displayed if
a Room sensor is
installed.)
Determines how large an impact the
room temperature is to have when cal-
culating the supply temperature. For
underfloor heating we recommend a set-
ting between 1-3 and for radiator heating
between 2-4.
Factory setting: 2 (inter-
val: 0 - 4)
(0 = no impact,
4 = large impact)
POOL
(Only displayed if
an Expansion card is
installed)
The temperature in the pool is controlled
by a separate sensor regardless of the
heating and hot water system.
By the customer, if
necessary.
CURVE
MIN
MAX
CURVE 5
CURVE 0
CURVE -5
HEAT STOP
40°C
22°C
70°C
0°C
0°C
0°C
17°C
HEAT CURVE