DEVIreg™ 530M
5
Installation Guide
2
Mounting instructions
Place the thermostat at a suitable height on the wall
(typically 80-170cm).
The thermostat should not be placed in wet rooms.
Place it in an adjacent room. Always place the ther-
mostat according to local regulation on IP classes.
Note:
A floor sensor enables a more accurate
temperature control and is recommended in all floor
heating applications and
mandatory
under wooden
floors to reduce the risk of over-heating the floor.
• Place the floor sensor in a conduit in an appropriate
place where it is not exposed to sunlight or draft from
door openings.
• Equally distant and >2cm from two heating cables.
• The conduit should be flush with the floor surface -
countersink the conduit if necessary.
• Route the conduit to the connection box.
• The bending radius of the conduit must be min.
50 mm.