READINGS MENU:

No. Name

Description

1

O1..O4

Output status (Defined output O1..O4)

Open

 - no alarm or break alarm circuit

Closed 

– shortcut to ground in alarm circuit

See Outputs settings in Installer Menu.

2

B1..B3

Input status

Open

 - input Bx open

Closed

 – input B1 close to G

Free contact relay (not used in CCR3+ process, only for monitoring in BMS). Binary inputs or PT1000 
sensor (5V, 1mA).

3

RT Clock

The Real Time clock, show current time, date, day of the week.
Data used in archive file.

4

S0-main temp.

S0 – value of (°C) supply temperature. The same readings apply to sensors S1 … S20.

Open

 - no sensor or break sensor circuit

Closed

 – shortcut to ground in sensor circuit

Fault

 – temp. values exeed Fault temp. max or is bellow Fault temp. max (correspondent to Fault temp. 

settings in Installer Menu)

5

Ret.Set.Temp

Information about setting return temperature correspondent to current flow temperature, in °C degree. 
Required range set in points in the Installer Menu. Function used for temperature alarm output.

Set. Temperature is = Return Set. Tempe/- Shift T. Set.

6

Alerts

General information about CCR3+ status

OK

 – system is running without alarms

Alert (red)

 – system has alarms

Riser Status (sensors: S1-S36; valves: V1-V36)

7

Riser

Number of risers (look to: Advanced Menu)
Riser statuses are indicated with color. 

OK

 – riser status is OK

High (red)

 - if temp. on Sx sensor is higher then Ret.Set.Temp

Low (blue)

 - if temp. on Sx sensor is lower then Ret.Set.Temp.

Open (yellow)

 - no sensor or break sensor circuit

Closed (grey)

 -  shortcut to ground in sensor circuit

N/A (white)

 - non relevant (non selected) risers

8

Valve output

Status of valve: V1 … V36

1

 – open, valve output closed to C (powered up), (taking PWM into account).

0

 – valve closed, valve output closed to C (powered down), (taking PWM into account).

Valve is 1-Open if: PWM min < Valve % <PWM max

9

Valve [%]

… ..% – valve open ratio – percentage of filling the PWM function (0 … 100 % in 10 % steps)

10

Temperature 
[°C]

Temperature readings in riser

Open

 - no sensor or break sensor circuit

Closed

 – shortcut to ground in sensor circuit

11

Set. Temp.[°C]

Information about return temperature correspondent to Ret.Set.Temp and  Shift setting (correspondent 
to Shift T.Set in Shifting Menu)

Set. Temperature is = Return Set.
Tempe/- Shift T. Set.

12

Alerts

Temperatures status (same color as described in pos. “Riser status”):
Riser RX – riser status information:

OK

 – riser status is OK

High (red)

 - if temp. on Sx sensor is higher then Ret.Set.Temp

Low (blue)

 - if temp. on Sx sensor is lower then Ret.Set.Temp.

Open (yellow)

 - no sensor or break sensor circuit

Closed (grey)

 -  shortcut to ground in sensor circuit

N/A (white)

 - non relevant (non configurated) risers

INSTALLER MENU:

No. Name

Description

13

TRet(35)

Required return temperature for measure supply temperature: 35°C

Factory setting: 30°C

14

TRet(40)

Required return temperature for measure supply temperature: 40°C

Factory setting: 35°C

15

TRet(45)

Required return temperature for measure supply temperature: 45°C

Factory setting: 38°C

16

TRet(50)

Required return temperature for measure supply temperature: 50°C

Factory setting: 40°C

17

TRet(55)

Required return temperature for measure supply temperature: 55°C

Factory setting: 42°C

18

TRet(63)

Required return temperature for measure supply temperature: 63°C

Factory setting: 45°C

19

TRet(70)

Required return temperature for measure supply temperature: 70°C

Factory setting: 48°C

20

TRet(80)

Required return temperature for measure supply temperature: 80°C

Factory setting: 54°C

11.  CCR3+ DASHBOARD 
(Web App Screen) 

(continuous)

Summary of Contents for CCR3+

Page 1: ...Danfoss 2019 02 VI GM A2 02 1 ENGLISH CCR3 Controller www danfoss com CCR3 Controller Operating Guide...

Page 2: ...2 Danfoss 2019 02 VI GM A2 02 CCR3 Controller Fig 1 Installation with CCR3 Controller up to 20 risers loops Fig 2 Installation with CCR23 Controller Master and CCR Slave Unit more that 20 risers...

Page 3: ...bus RS 485 C O1 O4 C common port dedicated to outputs O1 O4 O1 output Alert Broken Sensor O2 output Alert Low Temp O3 output Alert High Temp O4 output not in use C V1 4 C common port dedicated to actu...

Page 4: ...efined output O2 Defined output O3 Defined output O4 Risers temperature sensors S1 S20 Type of sensor PT1000 B1 Def input B1 B2 Def input B2 B3 Def input B3 CCR3 Master Wiring diagram S0 main sensor P...

Page 5: ...it Connector port Description 0V 24VDC 0V ground power supply 24 VDC power supply C V21 24 C common port dedicated to actuators V21 V24 outputs to actuators C V24 28 C common port dedicated to actuato...

Page 6: ...e 30 C Transport temperature 10 60 C IP rating IP 20 Power supply 24 VDC Power consumption Controller only 1 10 VA Power consumption Slave Unit only 1 3 VA Weight 0 3 kg Installation DIN rail 35 mm 1...

Page 7: ...connected to the controllers input and output connectors 1 Set all parameters on the controller 2 Make sure that there is no external voltage on the temperature sensor plugs 3 Make sure that the volta...

Page 8: ...password admin1234 Important Change of password to secure any unauthorized interaction from 3rd parties Note You can Skip login for access to data only in CCR3 reading overview only When the setup and...

Page 9: ...6 1 open valve output closed to C powered up taking PWM into account 0 valve closed valve output closed to C powered down taking PWM into account Valve is 1 Open if PWM min Valve PWM max 9 Valve valve...

Page 10: ...for Output which Over temperature or Broken Sensor Higher the value longer the reaction time alarm signal Factory setting 0 min 33 Alarm diff temp Set upper lower deviation temperature counted from R...

Page 11: ...ed Factory setting Odd 57 Modbus address Unit Address for Mobus RTU RS485 Factory setting 1 58 LAN IP address The IP address that the router assigned to this device when it joined the network This num...

Page 12: ...s reset to admin00X where x is the number of BT blue LED blinks Reset the setting only Go to firmware menu and click on Return Defaults Reset password only but not change other parameters Go to firmwa...

Page 13: ...sed B4 open closed RTC year RTC month RTC day RTC hour RTC minute B1 open closed B2 open closed B3 open closed S0 temp Ret Set Temp Status alert from 300 to 331 300 301 302 303 304 305 306 307 308 309...

Page 14: ...14 Danfoss 2019 02 VI GM A2 02 CCR3 Controller...

Page 15: ...Danfoss 2019 02 15 VI GM A2 02 CCR3 Controller...

Page 16: ...VI GM A2 02 16 Danfoss DHS SRMT SI 2019 02 CCR3 Controller...

Reviews: