Danfoss CCR3+ Operating Manual Download Page 6

6 | © Danfoss | 2019.02

VI.GM.A2.02 

CCR3+ Controller

LANGUAGE

ENGLISH

1.  Product description

The CCR3+ Controller is a controller used to 

control return temperature in one pipe heating 

systems with functions such as temperature 

registration and monitoring riser temperature. 

The controller is connected to thermo actuators 

type TWA-Z (NO) and remote temperature 

sensors PT1000, type ESMC installed on each 

riser.

2. Application

Temperature sensor (S0, S1-S20 / S21-36)

Pt1000, S0 – type ESMC/ESM11, S1-S20 / S21-36 – type ESMC 

Temperature range (registration)

–20 °C … +120 °C

Measuring accuracy

+/- 0.5 K

Inputs: B1, B2 & B3

Free contact (5 V 1 mA)

Number of control valves (risers)

20 basic, additional 16 with system extension via CCR+ Slave Unit

Output signal to actuators

24 VDC max. 1 A

Alarm signal output

24 VDC max. 1 A

Relay output

0-24 VDC max. 1A

Type of memory

Build-In

Capacity of memory

8 GB 

Timer: Real time clock

Built-in battery – powered for 10 years

Communication interfaces

- Wi-Fi (communication port only)
- TPC/IP port (LAN cable connection)
- Modbus RS485 RTU
- IP Modbus (LAN cable connection)

Default IP settings:

- Default LAN IP address (static): 192.168.1.100 
- Default WiFi acess IP address (static): 192.168.1.10 
- IP address mask: 255.255.255.0 
- Gateway address: 192.168.1.1 
- DNS address: 192.168.1.1 
- CCR name: ccrplus 
- Default password: admin1234 

Ambient temperature

0 … +50 °C ( for CCR3+ only. The ambient temperature for actuators TWA-Z (NO) 

should not be above 30 °C)

Transport temperature

–10 … +60 °C

IP rating

IP 20

Power supply

24 VDC 

Power consumption (Controller only) 

1)

10 VA

Power consumption (Slave Unit only) 

1)

3 VA

Weight

0.3 kg

Installation

DIN rail 35 mm

1)

 

To select proper power transformer please follow formula: 24 V 10 VA (controller) + 7 VA*/per each actuator

CCR3+ controller is part of AB-QTE solution 

for one-pipe heating systems. It converts 

one-pipe heating system (usually constant flow 

system) into efficient variable flow system. This 

innovative solution dynamically controls the 

flow in the riser according to the load in risers by 

return temperature control. There are few basic 

rules to be followed, even more valid in case of 

renovation:

•  Set AB-QM according to the required heat 

load of the riser/loop.

•  Ensure correct radiator bypass flow setting 

(typically around 25-35 %). If the resistance of 

the radiator is much too high compared to the 

bypass this may result in underflow through 

radiator if the flow in riser/loop is reduced.

•  Optimize flow temperature that is driven by 

substation control (too high flow temperature 

can influence efficiency of first radiators in the 

riser/loop and result in oscillation of flow).

•  Optimize return temperature that is driven 

by CCR3+ (too high return temperature can 

result in lower energy efficiency).

•  Install temperature sensor in front of AB-QM 

as close to last radiator in the riser/loop as 

possible.

Following above rules will ensure optimal 

control performance of CCR3+ as well as energy 

efficiency and reliability of heating systems. 

For further application insights please contact 

Danfoss representative.

3.  Technical data

Summary of Contents for CCR3+

Page 1: ...Danfoss 2019 02 VI GM A2 02 1 ENGLISH CCR3 Controller www danfoss com CCR3 Controller Operating Guide...

Page 2: ...2 Danfoss 2019 02 VI GM A2 02 CCR3 Controller Fig 1 Installation with CCR3 Controller up to 20 risers loops Fig 2 Installation with CCR23 Controller Master and CCR Slave Unit more that 20 risers...

Page 3: ...bus RS 485 C O1 O4 C common port dedicated to outputs O1 O4 O1 output Alert Broken Sensor O2 output Alert Low Temp O3 output Alert High Temp O4 output not in use C V1 4 C common port dedicated to actu...

Page 4: ...efined output O2 Defined output O3 Defined output O4 Risers temperature sensors S1 S20 Type of sensor PT1000 B1 Def input B1 B2 Def input B2 B3 Def input B3 CCR3 Master Wiring diagram S0 main sensor P...

Page 5: ...it Connector port Description 0V 24VDC 0V ground power supply 24 VDC power supply C V21 24 C common port dedicated to actuators V21 V24 outputs to actuators C V24 28 C common port dedicated to actuato...

Page 6: ...e 30 C Transport temperature 10 60 C IP rating IP 20 Power supply 24 VDC Power consumption Controller only 1 10 VA Power consumption Slave Unit only 1 3 VA Weight 0 3 kg Installation DIN rail 35 mm 1...

Page 7: ...connected to the controllers input and output connectors 1 Set all parameters on the controller 2 Make sure that there is no external voltage on the temperature sensor plugs 3 Make sure that the volta...

Page 8: ...password admin1234 Important Change of password to secure any unauthorized interaction from 3rd parties Note You can Skip login for access to data only in CCR3 reading overview only When the setup and...

Page 9: ...6 1 open valve output closed to C powered up taking PWM into account 0 valve closed valve output closed to C powered down taking PWM into account Valve is 1 Open if PWM min Valve PWM max 9 Valve valve...

Page 10: ...for Output which Over temperature or Broken Sensor Higher the value longer the reaction time alarm signal Factory setting 0 min 33 Alarm diff temp Set upper lower deviation temperature counted from R...

Page 11: ...ed Factory setting Odd 57 Modbus address Unit Address for Mobus RTU RS485 Factory setting 1 58 LAN IP address The IP address that the router assigned to this device when it joined the network This num...

Page 12: ...s reset to admin00X where x is the number of BT blue LED blinks Reset the setting only Go to firmware menu and click on Return Defaults Reset password only but not change other parameters Go to firmwa...

Page 13: ...sed B4 open closed RTC year RTC month RTC day RTC hour RTC minute B1 open closed B2 open closed B3 open closed S0 temp Ret Set Temp Status alert from 300 to 331 300 301 302 303 304 305 306 307 308 309...

Page 14: ...14 Danfoss 2019 02 VI GM A2 02 CCR3 Controller...

Page 15: ...Danfoss 2019 02 15 VI GM A2 02 CCR3 Controller...

Page 16: ...VI GM A2 02 16 Danfoss DHS SRMT SI 2019 02 CCR3 Controller...

Reviews: